Instruction Manual RFL 9745 Teleprotection Channel: Section 6. USING THE RS-232 PORTS TO PROGRAM AND OPERATE THE RFL 9745, pages 190 to 199
Pages 190 to 199 of 394, from Instruction Manual RFL 9745 Teleprotection Channel
The original document is the PDF (6.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the RFL RFL-9745
Page 190
Section 6. USING THE RS-232 PORTS TO PROGRAM AND OPERATE THE RFL 9745 6.1 INTRODUCTION This section contains information on how to program, test, and control the sequence-of-events log of the RFL 9745 using the RS-232 ports. Before attempting to use the information in this section, the RFL 9745 must be accessed through APRIL using the information in Section 4 of this manual.
6.2 VIEWING APRIL COMMANDS Once you have connected a terminal or PC to the RFL 9745 (either directly or through an RFL 9660 Digital Switch), press the [ENTER] key on your keyboard. The RFL 9745 will send the following prompt to your terminal: 9745> This means that you have accessed the RFL 9745, and can now use APRIL commands to view lists of parameter settings, alarm conditions, and other information. To view a list of the APRIL commands, press the [H] and [ENTER] keys: 9745>H [ENTER] This tells the RFL 9745 to send a list of APRIL commands called the "main menu" to your terminal. A typical main menu for the Audio or Digital system appears in Figure 6-1.
RFL Electronics APRIL(t) Remote Communications, Version 2.0 (c)1993,1994 System Label H - Display the main menu A - Go to the alarms display V - Go to the values display P - Go to the programming menu (password required) D - Go to the read settings menu F - Go to the configuration and software version display K - Go to the logic programming menu (password required) T - Go to the test menu (password required) U - Enter the update mode X - Exit the update mode S - Go to sequence of events menu W - Window remote April 9745> Figure 6-1. Typical APRIL main menu for the Audio or Digital System
RFL 9745 September 20, 2007
6-1
RFL Electronics Inc. (973) 334-3100
Page 191
For more information on each APRIL command, refer to the paragraph numbers listed below. Command
Meaning
Paragraph
H
Display the main menu
.
.
.
.
6.3
C
Changing the password
.
.
.
.
6.4.2
A
Go to the alarms display
.
.
.
.
6.5
V
Go to the values display
.
.
.
.
6.6
P
Go to the programming menu (password)
.
.
6.7
D
Go to the read settings menu .
.
.
6.8
F
Go to the configure and software version display
.
6.9
K
Go to logic programming Menu (password) .
.
6.10
T
Go to the test menu (password)
.
.
.
6.11
U
Enter the update mode
.
.
.
.
6.12
X
Exit the update mode .
.
.
.
.
6.12
S
Go to sequence-of-events menu
.
.
.
6.13
W
Window remote April .
.
.
.
6.15
.
.
6.3 DISPLAYING APRIL HELP Any time you need to see a list of all the APRIL commands while the "9745>" prompt is displayed, use the "H" command. 9745>H [ENTER] When you invoke the "H" command, the APRIL command main menu shown in Figure 6-1 will reappear on your screen.
RFL 9745 September 20, 2007
6-2
RFL Electronics Inc. (973) 334-3100
Page 192
6.4 PASSWORD PROTECTION NOTE This is the only page where the superuser password is discussed and can be removed for added security.
Password protection is required to prevent unauthorized personnel from gaining access to the RFL 9745 settings and parameters. The three menus that are password protected are the Programming Menu, Logic Programming Menu, and the Test Menu.
6.4.1 ENTERING THE PROGRAMMING, LOGIC PROGRAMMING OR TEST MENUS When you invoke the "P", “K”, or “T” command, the following prompt appears: enter password: Enter either the super-user password ("BCELNR") or the password that has been stored in the RFL 9745's memory. The RFL 9745 gives you three chances to enter the correct password. After the third incorrect password is entered, the RFL 9745 enters a lock-out mode. This mode will last for about five minutes, during which you will not be able to enter the programming mode.
6.4.2 CHANGING THE PASSWORD You can use the "C" command to change the password that can be used to enter the programming, logic programming, or test modes. 9745-P>C [ENTER] When you invoke the "C" command, the RFL 9745 sends the following prompt to your terminal: enter super-user: Enter the super-user password ("BCELNR"), and then press [ENTER]. The following prompt will appear: Current password is (current password) enter new password: Enter the new password, and then press [ENTER]. The following prompt will appear: repeat new password: RFL 9745 September 20, 2007
6-3
RFL Electronics Inc. (973) 334-3100
Page 193
Enter the new password again, and then press [ENTER]. The following prompt will appear: password modified The new password is now stored in the RFL 9745's non-volatile memory. The password can have a maximum of six alphanumeric characters including spaces. The same password is used for all three menus (“P” program menu, “K” logic menu and “T” test menu). When you change the password in one menu it automatically changes the password for the other two menus. The software only allows one password. If a new password is entered it will write over the old password.
RFL 9745 September 20, 2007
6-4
RFL Electronics Inc. (973) 334-3100
Page 194
6.5 VIEWING THE ALARMS DISPLAY To view the current status of all RFL 9745 alarms, enter the "A" command. 9745>A [ENTER] The "A" command tells the RFL 9745 to send a copy of the alarms display to your terminal. This display is for viewing only and cannot be changed by the user. Typical alarms displays for the Audio and Digital systems are shown in Figures 6-2 and 6-3 respectively.
# ALARM STATUS (I/A) ------------------------------085 Comms CPU Error I 087 Left PS Low V I 089 Battery Low I 093 Channel Delay I 1 2 3 4 094 Fail to Trip A A I A I 096 Output Shorted A I I I I 101 Signal to Noise I I A I 103 AM Filter 1 High I I I I 105 AM Filter 1 Low I I A I 107 Low Signal A D A A Programmable Alarms: 120 COMMS WARNING 122 NOT USED 124 HARDWARE WARNING 126 ANNUNC1 OUT TEST 128 ANNUNC3 OUT TEST 130 ANNUNC5 OUT TEST 9745>
# ALARM STATUS (I/A) --------------------------------086 Bus Error I 088 Right PS Low V A 091 Address Failure I
095 Fail to Trip B 097 Output Shorted B 102 FM Noise 104 AM Filter 2 High 106 AM Filter 2 Low
A I A A I A
121 OUTPUT ALARM 123 COMMS ALARM 125 HARDWARE ALARM 127 ANNUNC2 OUT TEST 129 ANNUNC4 OUT TEST 131 ANNUNC6 OUT TEST
1 2 3 4 A I A I I I I I I I A I I I I I I I A I
I A I A I I
Figure 6-2. Typical alarms display for the Audio System
In Figures 6-2 and 6-3, parameters 126 through 131 are displayed only when parameter 060 (optional status board) shown in the menu of Figure 6-7 is set to “yes”. This parameter should be set to “yes” only if your 9745 has the optional status board installed.
RFL 9745 September 20, 2007
6-5
RFL Electronics Inc. (973) 334-3100
Page 195
# ALARM STATUS (I/A) --------------------------------085 Comms CPU Error I 087 Left PS Low V 089 Battery Low 093 Channel Delay I 1 2 3 4 094 Fail to Trip A A I A I 096 Output Shorted A I I I I 111 Major Data Error I 113 Config Error I 115 Frame Errors I 117 BER Warning I Programmable Alarms: 120 COMMS WARNING 122 NOT USED 124 HARDWARE WARNING 126 ANNUNC1 OUT TEST 128 ANNUNC3 OUT TEST 130 ANNUNC5 OUT TEST 9745>
A I A A I A
# ALARM STATUS (I/A) --------------------------------086 Bus Error I 088 Right PS Low V A 091 Address Failure I
095 Fail to Trip B 097 Output Shorted B 112 Minor Data Error 114 Clock Errors 116 TX Fail
1 2 3 4 A I A I I I I I I I I
121 OUTPUT ALARM 123 COMMS ALARM 125 HARDWARE ALARM 127 ANNUNC2 OUT TEST 129 ANNUNC4 OUT TEST 131 ANNUNC6 OUT TEST
I A I A I I
Figure 6-3. Typical alarms display for the Digital System
Parameters 085 through 117 are conditions that exist in the unit. The alarm logic programming will determine if these conditions result in alarms 120 through 131. The alarms displays shown in Figures 6-2 and 6-3 show the parameter number for each alarm, a brief description of its meaning, and its status. "I" indicates that the alarm is "inactive" or that there is no alarm. "A" indicates that the alarm is "active" or that there is an alarm. “D” indicates that the channel is “disabled” (This applies only to item 107, which is the Low Signal Alarm for channels 1,2,3 and 4). Full descriptions for each alarm are as follows: 085 - Comms CPU Error
Active when an error has occurred involving the communications CPU.
086 - Bus Error
Active when an error has occurred involving one of the RFL 9745's buses.
087 - Left PS Low V
Active when the output of the left (main) power supply module is below the preset level.
088 - Right PS Low V
Active when the output of the right (redundant) power supply module is below the preset level.
RFL 9745 September 20, 2007
6-6
RFL Electronics Inc. (973) 334-3100
Page 196
089 - Battery Low
Not used on units with capacitor backed RAM.
091 - Address Failure
Active when an address test has returned an incorrect address from the remote end.
093 - Channel Delay
Active when the measured channel delay is greater than the programmed value.
094 - Fail to Trip A
Active when Output 1A, 2A, 3A or 4A should be in its trip or closed state, but less than 150 ma is being sensed through its contacts.
095 - Fail to Trip B
Active when Output 1B, 2B, 3B, or 4B should be in its trip or closed state, but less than 150 ma is being sensed through its contacts.
096 - Output Shorted A
Active when Output 1A, 2A, 3A, or 4A should be open, but a current greater than 150 ma is being sensed through its contacts.
097 - Output Shorted B
Active when Output 1B, 2B, 3B, or 4B should be open, but a current greater than 150 ma is being sensed through its contacts.
101 - Signal to Noise
Active when there is too much amplitude-modulated noise on the incoming signal.
102 - FM Noise
Active when there is too much frequency-modulated noise on the incoming signal.
103 - AM Filter 1 High
Active when a narrow filter centered at the lower frequency of channel 1, 2, 3, and 4 is measuring an energy level above the maximum acceptable limit.
104 - AM Filter 2 High
Active when a narrow filter centered at the upper frequency of channel 1, 2, 3, and 4 is measuring an energy level above the maximum acceptable limit.
105 - AM Filter 1 Low
Active when a narrow filter centered at the lower frequency of channel 1, 2, 3, and 4 is measuring an energy level below the minimum acceptable limit.
106 - AM Filter 2 Low
Active when a narrow filter centered at the upper frequency of channel 1, 2, 3, and 4 is measuring an energy level below the minimum acceptable limit.
107 - Low Signal
Active when the received signal level for channel 1, 2, 3, or 4 is lower than the programmed Rx Alarm Level shown in parameters 008, 038 and 053 of Figure 6-10.
RFL 9745 September 20, 2007
6-7
RFL Electronics Inc. (973) 334-3100
Page 197
111 - Major Data Error
Active when the number of errors exceeds the Major Data Error limit set in the programming menu by the user.
112 - Minor Data Error
Active when the number of errors exceeds the Minor Data Error limit set in the programming menu by the user.
113 - Config Error
Active when a Digital I/O module is not installed.
114 - Clock Errors
Active when the variation in the received word exceeds the min/max frequency limits or the max jitter setting.
115 - Frame Errors
Active when the receiver has lost synchronization with the incoming bit stream.
116 - TX Fail
Active when a hardware failure has been detected on the optic I/O board.
117 - BER Warning
Active when the BER exceeds the value set in the programming menu.
The following alarms have programmable names or labels. Their factory-default names are given below. You can use the procedure given in Section 5 of this manual to rename them to suit your application. Space is provided below for you to write in what each of these alarms means in your system:
120 - COMMS WARNING (Annunce Relay 1A)
________________________________________________
121 - OUTPUT ALARM (Annunce Relay 2A)
________________________________________________
122 - NOT USED (Annunce Relay 3A)
________________________________________________
123 - COMMS ALARM (Annunce Relay 1B)
________________________________________________
124 - HARDWARE WARNING (Annunce Relay 2B)
________________________________________________
125 - HARDWARE ALARM (Annunce Relay 3B)
________________________________________________
RFL 9745 September 20, 2007
6-8
RFL Electronics Inc. (973) 334-3100
Page 198
Items 126 through 131 are displayed only when parameter 060 (optional status board) is set to “yes”. See parameter 060 in the menu of Figure 6-7.
126 - ANNUNC1 OUT
________________________________________________
127 - ANNUNC2 OUT
________________________________________________
128 - ANNUNC3 OUT
________________________________________________
129 - ANNUNC4 OUT
________________________________________________
130 - ANNUNC5 OUT
________________________________________________
131 - ANNUNC6 OUT
________________________________________________
RFL 9745 September 20, 2007
6-9
RFL Electronics Inc. (973) 334-3100
Page 199
6.6 VIEWING THE VALUES DISPLAY To view a list of all measured parameter values, enter the "V" command. 9745>V [ENTER] The "V" command tells the RFL 9745 to send a copy of the most recently measured values to your terminal. This display is for viewing only and cannot be changed by the user. Typical values displays for the Audio and Digital Systems are shown in Figures 6-4 and 6-5 respectively.
NAME VALUE # NAME VALUE ---------------------------------------------------------------------- 140 Tx Chan Delay 6 ms 141 Next Auto Test N/A 142 Rx Chan Delay 6 ms 143 Last Reset Date 16:38:59 03/03/94 144 Cum Outage Time 00:00:00.000 145 Current Time 00:32:56 03/15/94
154 155 156 157 158 159 160 161
170 171 172 173 174 9745>
Input 1A Input 1B Input 2A Input 2B Input 3A Input 3B Input 4A Input 4B
(I/A) I I I I I I I I
LOG 1 0 4 0 0 1 0 0
162 163 164 165 166 167 168 169
Output 1A Output 1B Output 2A Output 2B Output 3A Output 3B Output 4A Output 4B
Function Rcvd Signal Lvl Tx Function Tx Squelch Rx High Freq Rx Low Freq
#1 -19 I I I I
#2 -15 I I I A
#3 -15 I I I I
#4 -15 dBm A I A I
(I/A) A A A A I I I I
LOG 0 2 0 2 0 2 0 2
Figure 6-4. Typical values display for the Audio System
RFL 9745 September 20, 2007
6 - 10
RFL Electronics Inc. (973) 334-3100