Instruction Manual RFL 9745 Teleprotection Channel: Section 3. INSTALLATION, pages 134 to 143

Pages 134 to 143 of 394, from Instruction Manual RFL 9745 Teleprotection Channel

The original document is the PDF (6.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the RFL RFL-9745

Page 134

3.6.5.6 INTERFACING THE RFL 9745 (107310) WITH AN IMUX 2000 (MA620) An RFL 9745 equipped with a 107310 (Short Haul Fiber module) can be connected to an IMUX 2000 as shown in Figure 3-31. There are no jumpers or settings on the 107310 or the MA620, however SW4-2 and SW4-3 on the DS562I must be set to the ON position. No Jumpers Or Settings

Short Haul Fiber (107310)

No Jumpers Or Settings

Tx

Tx Fiber

Rx

Rx

Rx Fiber

Tx

MA-620

RFL 9745

SW4-2 (ON) SW4-3 (ON)

DS-562I

IMUX 2000

Figure 3-31. Interfacing the RFL 9745 (107310) with an IMUX 2000 (MA-620)

RFL 9745 February 24, 2009

3 - 51

RFL Electronics Inc. (973) 334-3100

Page 135

3.6.6 FRONT PANEL MODULE The Front Panel Module (Assy. No. 105055) has two programmable jumpers, labeled "JP1" and "JP2." See the Figure below for jumper locations. These jumpers are set at the factory according to the type of front panel display being used: JP1

JP1 has three possible settings: A-B, B-C, and C-D. If an Optrex display is being used, jumpers are placed in Positions A-B and C-D at the factory. If a Seiko display is being used, a jumper is placed in Position B-C at the factory.

JP2

JP2 has two possible settings: E and F. If an Optrex display is being used, JP2 is placed in Position E at the factory. If a Seiko display is being used, JP2 is placed in Position F at the factory.

JP2

R2

R1

RZ4

C14 CR1 C13

12 Q1

330 OHM

E1 AA

P1A E1-A

DS4

DS8

E1 AC

C16 CR2DS7

DS3

SW8

SW7

E1-K

R3

C15

JP1

C28

C2 9

C9

C1 1

C8

C18 .1uF

CR3

C17

C20

C25

+ P1

U6+

U5

C4

C19

C10 R4

1

DS2

DS6

U7 *

CR4 U4 DS1

DS5

C21

RZ2

U9

C22

C6 TP1

U3

U2

C5R5 RZ3

CR5

A B C

E

F C1 R8R6R7 JP D C7 2 2 JP 1

C24

RZ1

C23 + J1

C26 +

2 1

TP2 C2

U1 C3

1 RZ5 2 1 J2

J3

5 9

U10

DS9

R11

1 6

SW1 C27

SW2

SW3

SW4

SW5

SW6

C1

Figure 3- 32. Location of jumpers on the Front Panel Module

RFL 9745 February 24, 2009

3 - 52

RFL Electronics Inc. (973) 334-3100

Page 136

3.6.7 SWC I/O MODULES There are three types of RFL 9745 SWC I/O Modules. They can be solid-state (Assy. No. 105005), relay/solid-state (Assy. No. 105010), or high speed relay (Assy. No. 105955). These modules have jumpers as shown in Figure 3-33. The input controlled by jumpers J1 through J4 will depend on whether the SWC I/O Module is installed in the top slot (serving as terminal block TBA) or the bottom slot (serving as terminal block TBB):

3.6.7.1 SOLID STATE SWC I/O MODULE When Installed In Top Slot: J1

Selects input voltage for INPUT 1A. Place in 48V position to accept 48-volt inputs, or 125V position for 110/125-volt inputs. (250-volt units have fixed jumpers that are not field-selectable.)

J2

Selects input voltage for INPUT 2A. Place in 48V position to accept 48-volt inputs, or 125V position for 110/125-volt inputs. (250-volt units have fixed jumpers that are not field-selectable.)

J3

Selects input voltage for INPUT 3A. Place in 48V position to accept 48-volt inputs, or 125V position for 110/125-volt inputs. (250-volt units have fixed jumpers that are not field-selectable.)

J4

Selects input voltage for INPUT 4A. Place in 48V position to accept 48-volt inputs, or 125V position for 110/125-volt inputs. (250-volt units have fixed jumpers that are not field-selectable.) When Installed In Bottom Slot:

J1

Selects input voltage for INPUT 1B. Place in 48V position to accept 48-volt inputs, or 125V position for 110/125-volt inputs. (250-volt units have fixed jumpers that are not field-selectable.)

J2

Selects input voltage for INPUT 2B. Place in 48V position to accept 48-volt inputs, or 125V position for 110/125-volt inputs. (250-volt units have fixed jumpers that are not field-selectable.)

J3

Selects input voltage for INPUT 3B. Place in 48V position to accept 48-volt inputs, or 125V position for 110/125-volt inputs. (250-volt units have fixed jumpers that are not field-selectable.)

J4

Selects input voltage for INPUT 4B. Place in 48V position to accept 48-volt inputs, or 125V position for 110/125-volt inputs. (250-volt units have fixed jumpers that are not field-selectable.)

RFL 9745 February 24, 2009

3 - 53

RFL Electronics Inc. (973) 334-3100

Page 137

3.6.7.2 RELAY/SOLID STATE SWC I/O MODULE When Installed In Top Slot: J1

Selects input voltage for INPUT 1A. Place in 48V position to accept 48-volt inputs, or 125V position for 110/125-volt inputs. (250-volt units have fixed jumpers that are not field-selectable.)

J2

Selects input voltage for INPUT 2A. Place in 48V position to accept 48-volt inputs, or 125V position for 110/125-volt inputs. (250-volt units have fixed jumpers that are not field-selectable.)

J3

Selects input voltage for INPUT 3A. Place in 48V position to accept 48-volt inputs, or 125V position for 110/125-volt inputs. (250-volt units have fixed jumpers that are not field-selectable.)

J4

Selects input voltage for INPUT 4A. Place in 48V position to accept 48-volt inputs, or 125V position for 110/125-volt inputs. (250-volt units have fixed jumpers that are not field-selectable.)

J5

J5 has two possible settings: A and B. When in position A, the relay contacts for K1 are normally open (NO). When in position B, the relay contacts for K1 are normally closed (NC).

J6

J6 has two possible settings: A and B. When in position A, the relay contacts for K2 are normally open (NO). When in position B, the relay contacts for K2 are normally closed (NC).

J7

J7 has two possible settings: A and B. When in position A, the relay contacts for K3 are normally open (NO). When in position B, the relay contacts for K3 are normally closed (NC).

RFL 9745 February 24, 2009

3 - 54

RFL Electronics Inc. (973) 334-3100

Page 138

When Installed In Bottom Slot: J1

Selects input voltage for INPUT 1B. Place in 48V position to accept 48-volt inputs, or 125V position for 110/125-volt inputs. (250-volt units have fixed jumpers that are not field-selectable.)

J2

Selects input voltage for INPUT 2B. Place in 48V position to accept 48-volt inputs, or 125V position for 110/125-volt inputs. (250-volt units have fixed jumpers that are not field-selectable.)

J3

Selects input voltage for INPUT 3B. Place in 48V position to accept 48-volt inputs, or 125V position for 110/125-volt inputs. (250-volt units have fixed jumpers that are not field-selectable.)

J4

Selects input voltage for INPUT 4B. Place in 48V position to accept 48-volt inputs, or 125V position for 110/125-volt inputs. (250-volt units have fixed jumpers that are not field-selectable.)

J5

J5 has two possible settings: A and B. When in position A, the relay contacts for K1 are normally open (NO). When in position B, the relay contacts for K1 are normally closed (NC).

J6

J6 has two possible settings: A and B. When in position A, the relay contacts for K2 are normally open (NO). When in position B, the relay contacts for K2 are normally closed (NC).

J7

J7 has two possible settings: A and B. When in position A, the relay contacts for K3 are normally open (NO). When in position B, the relay contacts for K3 are normally closed (NC).

NOTE J5 - J7 are set to position A at the factory or according to customer specifications.

RFL 9745 February 24, 2009

3 - 55

RFL Electronics Inc. (973) 334-3100

Page 139

3.6.7.3 HIGH SPEED RELAY SWC I/O MODULE There are eight types of High Speed Relay SCI I/O modules as shown in the table below. The part number of the board is stamped in black ink on the non-component side of the board. Table 3-10. High Speed Relays

RFL Part Number 105955-1 105955-12 105955-13 105955-14 105955-3 105955-4 105955-5 105955-6

Connection Type Terminal block Compression plug Compression plug Compression plug Terminal block Terminal block Terminal block Terminal block

Input Voltage 48/125 Vdc 48/125 Vdc 250 Vdc 24 Vdc 250 Vdc 24 Vdc 48/110 Vdc 220 Vdc

When Installed In Top Slot: J1

Selects input voltage for INPUT 1A. Place in 48V position to accept 48-volt inputs, or 125V position for 110/125-volt inputs. (250-volt units have fixed jumpers that are not fieldselectable.)

J2

Selects input voltage for INPUT 2A. Place in 48V position to accept 48-volt inputs, or 125V position for 110/125-volt inputs. (250-volt units have fixed jumpers that are not fieldselectable.)

J3

Selects input voltage for INPUT 3A. Place in 48V position to accept 48-volt inputs, or 125V position for 110/125-volt inputs. (250-volt units have fixed jumpers that are not fieldselectable.)

J4

Selects input voltage for INPUT 4A. Place in 48V position to accept 48-volt inputs, or 125V position for 110/125-volt inputs. (250-volt units have fixed jumpers that are not fieldselectable.)

J5

J5 has two possible settings: A and B. When in position A, the relay contacts for K1 are normally open (NO). When in position B, the relay contacts for K1 are normally closed (NC).

J6

J6 has two possible settings: A and B. When in position A, the relay contacts for K2 are normally open (NO). When in position B, the relay contacts for K2 are normally closed (NC).

J7

J7 has two possible settings: A and B. When in position A, the relay contacts for K3 are normally open (NO). When in position B, the relay contacts for K3 are normally closed (NC).

J8

J8 has two possible settings: A and B. When in position A, the relay contacts for K4 are normally open (NO). When in position B, the relay contacts for K4 are normally closed (NC).

RFL 9745 February 24, 2009

3 - 56

RFL Electronics Inc. (973) 334-3100

Page 140

When Installed In Bottom Slot: J1

Selects input voltage for INPUT 1B. Place in 48V position to accept 48-volt inputs, or 125V position for 110/125-volt inputs. (250-volt units have fixed jumpers that are not field-selectable.)

J2

Selects input voltage for INPUT 2B. Place in 48V position to accept 48-volt inputs, or 125V position for 110/125-volt inputs. (250-volt units have fixed jumpers that are not field-selectable.)

J3

Selects input voltage for INPUT 3B. Place in 48V position to accept 48-volt inputs, or 125V position for 110/125-volt inputs. (250-volt units have fixed jumpers that are not field-selectable.)

J4

Selects input voltage for INPUT 4B. Place in 48V position to accept 48-volt inputs, or 125V position for 110/125-volt inputs. (250-volt units have fixed jumpers that are not field-selectable.)

J5

J5 has two possible settings: A and B. When in position A, the relay contacts for K1 are normally open (NO). When in position B, the relay contacts for K1 are normally closed (NC).

J6

J6 has two possible settings: A and B. When in position A, the relay contacts for K2 are normally open (NO). When in position B, the relay contacts for K2 are normally closed (NC).

J7

J7 has two possible settings: A and B. When in position A, the relay contacts for K3 are normally open (NO). When in position B, the relay contacts for K3 are normally closed (NC).

J8

J8 has two possible settings: A and B. When in position A, the relay contacts for K4 are normally open (NO). When in position B, the relay contacts for K4 are normally closed (NC).

NOTE J5 – J8 are set to position A at the factory or according to customer specifications.

RFL 9745 February 24, 2009

3 - 57

RFL Electronics Inc. (973) 334-3100

Page 141

J1

C R2 R9 5

T1 C R2 1

C2 1

1 C22

RZ2 C2

U1

R14 R24

R18 K1 CR18

CR5 G

D

R1

S

R5

U2

K2

R1 2

CR4

R25

R26

R27

CR6

CR7

CR8

48 R6 V N/ R3 12 A 5V J3 J2 48 V 12 5V

R2

12 5V

R7

C R2 8

C R2 7

1N C 40 R2 03 9

48V J4 125V

R4

C R2 4

S

C R2 3

Q4 G

K3

R1 9

R8

Q3 D

G

1

U4

CR3

1

C34

U3

CR2

J1 48 V

Q2

T4 1

1993 RFL ELECTRONICS INC.

R11 T3

CR1

Q 1

C

RZ1 C1

C3 C4

CR22

S

P1

C

C R2 6

R1 7 D

1 A

32 R1 0

G

J4

1

T2

R1 3

C R1 7

J3

J2

R2 R2C 1 2 R3 0

C R3 1

R2 3

C R1 9

K7

C C3 R1 6 5 C2 R1 3 5

C R2 0

D S

R2 R1 C2 0 6 4

C3 7 C R1 6

1

1

CR13

K5

C35

K6 C1 8

CR14 C13

C1 4

C1 5

C1 6

C6 C7

L9 L1 1

L10

C1 0

C5

L1 2

C9

C8 L5

L2 L3

C2 5

C1 1

L6

C2 6

C1 2 L1 7

L7

L4

C2 7

L1 8

C2 8

L1 9

L2 2

L2 3

C2 9

L2 0

C3 2 L2 4

L2 5

C1 9 K4 1

C1 7

C3 3

L1 3

L1 4

L1 6

L1 5

C20

L2 1

L8

L1

C3 0

C3 1

TB 1

Solid-state (Assy. No. 105005). J1

J2

J3

P1

R9 R1 0

C1 3

J4

32 CR 16

CR 15

1

RZ2 RZ1

RZ3

RZ4 C24

C1 CR 14

R1 1 G

D

S

T1

C22

C2

U1

Q1 K4 U5

U2

C4

U3

C23

U4

CR5

CR6

CR7

CR8

R18

R19

R20

R21

CR1

CR2

CR3

CR4

J1 48V

J2 48V

J3 48V

J4 48VCR23

125 V

125 V

125 V

125 V

CR17

103338

C3

R15

R16 CR24

R12 CR18

1 K1

R17 CR25

U7 CR21

R13

R14

CR20

K6

K5

U6 CR19

CR22

K7

K2

K3 A

C34 R5

CR13

R3

R2

A

R8

R7

R6

A R1

R4

C14

B B

B

J6

J7

J5 L9

C7

C1 5 C1 6

L10

C6 C1 7

C8

C1 0

C9

C5

C1 1

C2 5

C1 2

C2 7

C2 6

C2 8 L14

L1 L2

L3

L4

L5

L6

L7

L8

L11

L12

L13

C2 9

C3 0

C3 1

L16

L17

L18

C3 2

C3 3

C1 8

C2 C1 0 9

C2 1

L15 L19

TB1

J5

J6

J7

Relay/solid-state (Assy. No. 105010). Figure 3- 33. Location of jumpers on the SWC I/O Modules

RFL 9745 February 24, 2009

3 - 58

RFL Electronics Inc. (973) 334-3100

Page 142

J1

J2

C R1 4

32 C R1 6

T1

Q1

RZ1

RZ3 C24

C22

C2

U1

C34 U5

K1 A

R6

R1

R15

J348 V 12 5V

J448 CR23 V 12 5V

R7

R8

R3

R2

A

CR8 R21 CR4

J2 48 V 12 5V

R5

C23

U4

CR7 R20 CR3

J148 V 12 5V

CR17 R12 CR18

C4

U3

CR6 R19 CR2

U8 CR27

C3

U2

CR5 R18 CR1

CR26

K4

2000 RFL ELECTRONICS INC, BOONTON NJ U.S.A. 9745 RELAY I/O ECB NO 105958 REV-A RZ4

1

RZ2

C1

R1 1

R22

J4

P1

R9 R1 0 C R1 5

C1 3

J3

R16

R17

CR24

CR25 K6

K5

U6

U7

CR19 R13

CR21 R14

CR20

CR22

K7

K3 K2 A

A

R4

B

B

J8

B

C35

B

J6

J7

J5 C7 C3 6

C1 6

C6 C1 7 L1

L2

L3

TB1

J8

C8

C5 L4

L5

C1 0

C9

L6

C1 1

L7

C2 5

C1 2

L8

L1 1

C2 7

C2 6 L1 2

L1 3

L1 4

J5

C2 8 L1 5

C2 9

C3 0

C3 1

L1 6

L1 7

L1 8

C3 2

C3 3

C1 8

C2 C1 0 9

C2 1

L1 9

J6

J7

High speed relay (Assy. No. 105955).

Figure 3-33. continued. Location of jumpers on the SWC I/O Modules

RFL 9745 February 24, 2009

3 - 59

RFL Electronics Inc. (973) 334-3100

Page 143

3.7 COMMISSIONING PROCEDURES 3.7.1 RFL 9745 AUDIO TONE COMMISSIONING PROCEDURE 3.7.1.1 EQUIPMENT REQUIRED 1. PC or Laptop computer 2. 9 pin straight through cable with male and female connector. 3. Selective Voltmeter (optional)

3.7.1.2 JUMPER SETTINGS The jumper settings are performed at RFL per customer application. Follow the list below for confirmation of the jumper settings. Refer to paragraph 3.6 for additional information. Wide Band Audio Comms module: for 4 wire single: set J3, J10 to A, J5 and J11 to 4W. for 4 wire dual: set J3, J10 to B, J5 and J11 to 4W. for 2 wire single: set J3, J10 to A, J5 and J11 to 2W. for 2 wire dual: set J3, J10 to B, J5 and J11 to 2W. CPU module: Ref. Section 3.6.1 Driver module: check for jumper J2-NORM. I/O modules: select J1, J2, J3 and J4 for proper input keying voltage 48/125 Vdc. For the 24 Vdc and the 250 Vdc modules there is no jumper selection. For outputs Ref. 3.6.7 Power Supply module: No user settings: Front Panel module: No user settings:

3.7.1.3 WIRING Specific CD drawings are supplied with each order. Connect all external wiring to the unit in accordance with the rear view chassis wiring drawing, and Primitive and Alarm logic drawings supplied with the chassis.

3.7.1.4 POWER Turn the unit on by pressing the rocker switch at the rear of the unit. Check Station Battery voltage at TB1-9 (+) and TB1-10 (-) for proper voltage. The green LED on the Power Supply should be lit. On the Driver module check the positive 5 and 15 Vdc. TP1 is common, TP6 is +15Vdc (14.25 to 15.75Vdc), and TP2 is +5Vdc (4.75 to 5.75Vdc).

RFL 9745 February 24, 2009

3 - 60

RFL Electronics Inc. (973) 334-3100