Instruction Manual RFL 9745 Teleprotection Channel: Section 3. INSTALLATION, pages 134 to 143
Pages 134 to 143 of 394, from Instruction Manual RFL 9745 Teleprotection Channel
The original document is the PDF (6.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the RFL RFL-9745
Page 134
3.6.5.6 INTERFACING THE RFL 9745 (107310) WITH AN IMUX 2000 (MA620) An RFL 9745 equipped with a 107310 (Short Haul Fiber module) can be connected to an IMUX 2000 as shown in Figure 3-31. There are no jumpers or settings on the 107310 or the MA620, however SW4-2 and SW4-3 on the DS562I must be set to the ON position. No Jumpers Or Settings
Short Haul Fiber (107310)
No Jumpers Or Settings
Tx
Tx Fiber
Rx
Rx
Rx Fiber
Tx
MA-620
RFL 9745
SW4-2 (ON) SW4-3 (ON)
DS-562I
IMUX 2000
Figure 3-31. Interfacing the RFL 9745 (107310) with an IMUX 2000 (MA-620)
RFL 9745 February 24, 2009
3 - 51
RFL Electronics Inc. (973) 334-3100
Page 135
3.6.6 FRONT PANEL MODULE The Front Panel Module (Assy. No. 105055) has two programmable jumpers, labeled "JP1" and "JP2." See the Figure below for jumper locations. These jumpers are set at the factory according to the type of front panel display being used: JP1
JP1 has three possible settings: A-B, B-C, and C-D. If an Optrex display is being used, jumpers are placed in Positions A-B and C-D at the factory. If a Seiko display is being used, a jumper is placed in Position B-C at the factory.
JP2
JP2 has two possible settings: E and F. If an Optrex display is being used, JP2 is placed in Position E at the factory. If a Seiko display is being used, JP2 is placed in Position F at the factory.
JP2
R2
R1
RZ4
C14 CR1 C13
12 Q1
330 OHM
E1 AA
P1A E1-A
DS4
DS8
E1 AC
C16 CR2DS7
DS3
SW8
SW7
E1-K
R3
C15
JP1
C28
C2 9
C9
C1 1
C8
C18 .1uF
CR3
C17
C20
C25
+ P1
U6+
U5
C4
C19
C10 R4
1
DS2
DS6
U7 *
CR4 U4 DS1
DS5
C21
RZ2
U9
C22
C6 TP1
U3
U2
C5R5 RZ3
CR5
A B C
E
F C1 R8R6R7 JP D C7 2 2 JP 1
C24
RZ1
C23 + J1
C26 +
2 1
TP2 C2
U1 C3
1 RZ5 2 1 J2
J3
5 9
U10
DS9
R11
1 6
SW1 C27
SW2
SW3
SW4
SW5
SW6
C1
Figure 3- 32. Location of jumpers on the Front Panel Module
RFL 9745 February 24, 2009
3 - 52
RFL Electronics Inc. (973) 334-3100
Page 136
3.6.7 SWC I/O MODULES There are three types of RFL 9745 SWC I/O Modules. They can be solid-state (Assy. No. 105005), relay/solid-state (Assy. No. 105010), or high speed relay (Assy. No. 105955). These modules have jumpers as shown in Figure 3-33. The input controlled by jumpers J1 through J4 will depend on whether the SWC I/O Module is installed in the top slot (serving as terminal block TBA) or the bottom slot (serving as terminal block TBB):
3.6.7.1 SOLID STATE SWC I/O MODULE When Installed In Top Slot: J1
Selects input voltage for INPUT 1A. Place in 48V position to accept 48-volt inputs, or 125V position for 110/125-volt inputs. (250-volt units have fixed jumpers that are not field-selectable.)
J2
Selects input voltage for INPUT 2A. Place in 48V position to accept 48-volt inputs, or 125V position for 110/125-volt inputs. (250-volt units have fixed jumpers that are not field-selectable.)
J3
Selects input voltage for INPUT 3A. Place in 48V position to accept 48-volt inputs, or 125V position for 110/125-volt inputs. (250-volt units have fixed jumpers that are not field-selectable.)
J4
Selects input voltage for INPUT 4A. Place in 48V position to accept 48-volt inputs, or 125V position for 110/125-volt inputs. (250-volt units have fixed jumpers that are not field-selectable.) When Installed In Bottom Slot:
J1
Selects input voltage for INPUT 1B. Place in 48V position to accept 48-volt inputs, or 125V position for 110/125-volt inputs. (250-volt units have fixed jumpers that are not field-selectable.)
J2
Selects input voltage for INPUT 2B. Place in 48V position to accept 48-volt inputs, or 125V position for 110/125-volt inputs. (250-volt units have fixed jumpers that are not field-selectable.)
J3
Selects input voltage for INPUT 3B. Place in 48V position to accept 48-volt inputs, or 125V position for 110/125-volt inputs. (250-volt units have fixed jumpers that are not field-selectable.)
J4
Selects input voltage for INPUT 4B. Place in 48V position to accept 48-volt inputs, or 125V position for 110/125-volt inputs. (250-volt units have fixed jumpers that are not field-selectable.)
RFL 9745 February 24, 2009
3 - 53
RFL Electronics Inc. (973) 334-3100
Page 137
3.6.7.2 RELAY/SOLID STATE SWC I/O MODULE When Installed In Top Slot: J1
Selects input voltage for INPUT 1A. Place in 48V position to accept 48-volt inputs, or 125V position for 110/125-volt inputs. (250-volt units have fixed jumpers that are not field-selectable.)
J2
Selects input voltage for INPUT 2A. Place in 48V position to accept 48-volt inputs, or 125V position for 110/125-volt inputs. (250-volt units have fixed jumpers that are not field-selectable.)
J3
Selects input voltage for INPUT 3A. Place in 48V position to accept 48-volt inputs, or 125V position for 110/125-volt inputs. (250-volt units have fixed jumpers that are not field-selectable.)
J4
Selects input voltage for INPUT 4A. Place in 48V position to accept 48-volt inputs, or 125V position for 110/125-volt inputs. (250-volt units have fixed jumpers that are not field-selectable.)
J5
J5 has two possible settings: A and B. When in position A, the relay contacts for K1 are normally open (NO). When in position B, the relay contacts for K1 are normally closed (NC).
J6
J6 has two possible settings: A and B. When in position A, the relay contacts for K2 are normally open (NO). When in position B, the relay contacts for K2 are normally closed (NC).
J7
J7 has two possible settings: A and B. When in position A, the relay contacts for K3 are normally open (NO). When in position B, the relay contacts for K3 are normally closed (NC).
RFL 9745 February 24, 2009
3 - 54
RFL Electronics Inc. (973) 334-3100
Page 138
When Installed In Bottom Slot: J1
Selects input voltage for INPUT 1B. Place in 48V position to accept 48-volt inputs, or 125V position for 110/125-volt inputs. (250-volt units have fixed jumpers that are not field-selectable.)
J2
Selects input voltage for INPUT 2B. Place in 48V position to accept 48-volt inputs, or 125V position for 110/125-volt inputs. (250-volt units have fixed jumpers that are not field-selectable.)
J3
Selects input voltage for INPUT 3B. Place in 48V position to accept 48-volt inputs, or 125V position for 110/125-volt inputs. (250-volt units have fixed jumpers that are not field-selectable.)
J4
Selects input voltage for INPUT 4B. Place in 48V position to accept 48-volt inputs, or 125V position for 110/125-volt inputs. (250-volt units have fixed jumpers that are not field-selectable.)
J5
J5 has two possible settings: A and B. When in position A, the relay contacts for K1 are normally open (NO). When in position B, the relay contacts for K1 are normally closed (NC).
J6
J6 has two possible settings: A and B. When in position A, the relay contacts for K2 are normally open (NO). When in position B, the relay contacts for K2 are normally closed (NC).
J7
J7 has two possible settings: A and B. When in position A, the relay contacts for K3 are normally open (NO). When in position B, the relay contacts for K3 are normally closed (NC).
NOTE J5 - J7 are set to position A at the factory or according to customer specifications.
RFL 9745 February 24, 2009
3 - 55
RFL Electronics Inc. (973) 334-3100
Page 139
3.6.7.3 HIGH SPEED RELAY SWC I/O MODULE There are eight types of High Speed Relay SCI I/O modules as shown in the table below. The part number of the board is stamped in black ink on the non-component side of the board. Table 3-10. High Speed Relays
RFL Part Number 105955-1 105955-12 105955-13 105955-14 105955-3 105955-4 105955-5 105955-6
Connection Type Terminal block Compression plug Compression plug Compression plug Terminal block Terminal block Terminal block Terminal block
Input Voltage 48/125 Vdc 48/125 Vdc 250 Vdc 24 Vdc 250 Vdc 24 Vdc 48/110 Vdc 220 Vdc
When Installed In Top Slot: J1
Selects input voltage for INPUT 1A. Place in 48V position to accept 48-volt inputs, or 125V position for 110/125-volt inputs. (250-volt units have fixed jumpers that are not fieldselectable.)
J2
Selects input voltage for INPUT 2A. Place in 48V position to accept 48-volt inputs, or 125V position for 110/125-volt inputs. (250-volt units have fixed jumpers that are not fieldselectable.)
J3
Selects input voltage for INPUT 3A. Place in 48V position to accept 48-volt inputs, or 125V position for 110/125-volt inputs. (250-volt units have fixed jumpers that are not fieldselectable.)
J4
Selects input voltage for INPUT 4A. Place in 48V position to accept 48-volt inputs, or 125V position for 110/125-volt inputs. (250-volt units have fixed jumpers that are not fieldselectable.)
J5
J5 has two possible settings: A and B. When in position A, the relay contacts for K1 are normally open (NO). When in position B, the relay contacts for K1 are normally closed (NC).
J6
J6 has two possible settings: A and B. When in position A, the relay contacts for K2 are normally open (NO). When in position B, the relay contacts for K2 are normally closed (NC).
J7
J7 has two possible settings: A and B. When in position A, the relay contacts for K3 are normally open (NO). When in position B, the relay contacts for K3 are normally closed (NC).
J8
J8 has two possible settings: A and B. When in position A, the relay contacts for K4 are normally open (NO). When in position B, the relay contacts for K4 are normally closed (NC).
RFL 9745 February 24, 2009
3 - 56
RFL Electronics Inc. (973) 334-3100
Page 140
When Installed In Bottom Slot: J1
Selects input voltage for INPUT 1B. Place in 48V position to accept 48-volt inputs, or 125V position for 110/125-volt inputs. (250-volt units have fixed jumpers that are not field-selectable.)
J2
Selects input voltage for INPUT 2B. Place in 48V position to accept 48-volt inputs, or 125V position for 110/125-volt inputs. (250-volt units have fixed jumpers that are not field-selectable.)
J3
Selects input voltage for INPUT 3B. Place in 48V position to accept 48-volt inputs, or 125V position for 110/125-volt inputs. (250-volt units have fixed jumpers that are not field-selectable.)
J4
Selects input voltage for INPUT 4B. Place in 48V position to accept 48-volt inputs, or 125V position for 110/125-volt inputs. (250-volt units have fixed jumpers that are not field-selectable.)
J5
J5 has two possible settings: A and B. When in position A, the relay contacts for K1 are normally open (NO). When in position B, the relay contacts for K1 are normally closed (NC).
J6
J6 has two possible settings: A and B. When in position A, the relay contacts for K2 are normally open (NO). When in position B, the relay contacts for K2 are normally closed (NC).
J7
J7 has two possible settings: A and B. When in position A, the relay contacts for K3 are normally open (NO). When in position B, the relay contacts for K3 are normally closed (NC).
J8
J8 has two possible settings: A and B. When in position A, the relay contacts for K4 are normally open (NO). When in position B, the relay contacts for K4 are normally closed (NC).
NOTE J5 – J8 are set to position A at the factory or according to customer specifications.
RFL 9745 February 24, 2009
3 - 57
RFL Electronics Inc. (973) 334-3100
Page 141
J1
C R2 R9 5
T1 C R2 1
C2 1
1 C22
RZ2 C2
U1
R14 R24
R18 K1 CR18
CR5 G
D
R1
S
R5
U2
K2
R1 2
CR4
R25
R26
R27
CR6
CR7
CR8
48 R6 V N/ R3 12 A 5V J3 J2 48 V 12 5V
R2
12 5V
R7
C R2 8
C R2 7
1N C 40 R2 03 9
48V J4 125V
R4
C R2 4
S
C R2 3
Q4 G
K3
R1 9
R8
Q3 D
G
1
U4
CR3
1
C34
U3
CR2
J1 48 V
Q2
T4 1
1993 RFL ELECTRONICS INC.
R11 T3
CR1
Q 1
C
RZ1 C1
C3 C4
CR22
S
P1
C
C R2 6
R1 7 D
1 A
32 R1 0
G
J4
1
T2
R1 3
C R1 7
J3
J2
R2 R2C 1 2 R3 0
C R3 1
R2 3
C R1 9
K7
C C3 R1 6 5 C2 R1 3 5
C R2 0
D S
R2 R1 C2 0 6 4
C3 7 C R1 6
1
1
CR13
K5
C35
K6 C1 8
CR14 C13
C1 4
C1 5
C1 6
C6 C7
L9 L1 1
L10
C1 0
C5
L1 2
C9
C8 L5
L2 L3
C2 5
C1 1
L6
C2 6
C1 2 L1 7
L7
L4
C2 7
L1 8
C2 8
L1 9
L2 2
L2 3
C2 9
L2 0
C3 2 L2 4
L2 5
C1 9 K4 1
C1 7
C3 3
L1 3
L1 4
L1 6
L1 5
C20
L2 1
L8
L1
C3 0
C3 1
TB 1
Solid-state (Assy. No. 105005). J1
J2
J3
P1
R9 R1 0
C1 3
J4
32 CR 16
CR 15
1
RZ2 RZ1
RZ3
RZ4 C24
C1 CR 14
R1 1 G
D
S
T1
C22
C2
U1
Q1 K4 U5
U2
C4
U3
C23
U4
CR5
CR6
CR7
CR8
R18
R19
R20
R21
CR1
CR2
CR3
CR4
J1 48V
J2 48V
J3 48V
J4 48VCR23
125 V
125 V
125 V
125 V
CR17
103338
C3
R15
R16 CR24
R12 CR18
1 K1
R17 CR25
U7 CR21
R13
R14
CR20
K6
K5
U6 CR19
CR22
K7
K2
K3 A
C34 R5
CR13
R3
R2
A
R8
R7
R6
A R1
R4
C14
B B
B
J6
J7
J5 L9
C7
C1 5 C1 6
L10
C6 C1 7
C8
C1 0
C9
C5
C1 1
C2 5
C1 2
C2 7
C2 6
C2 8 L14
L1 L2
L3
L4
L5
L6
L7
L8
L11
L12
L13
C2 9
C3 0
C3 1
L16
L17
L18
C3 2
C3 3
C1 8
C2 C1 0 9
C2 1
L15 L19
TB1
J5
J6
J7
Relay/solid-state (Assy. No. 105010). Figure 3- 33. Location of jumpers on the SWC I/O Modules
RFL 9745 February 24, 2009
3 - 58
RFL Electronics Inc. (973) 334-3100
Page 142
J1
J2
C R1 4
32 C R1 6
T1
Q1
RZ1
RZ3 C24
C22
C2
U1
C34 U5
K1 A
R6
R1
R15
J348 V 12 5V
J448 CR23 V 12 5V
R7
R8
R3
R2
A
CR8 R21 CR4
J2 48 V 12 5V
R5
C23
U4
CR7 R20 CR3
J148 V 12 5V
CR17 R12 CR18
C4
U3
CR6 R19 CR2
U8 CR27
C3
U2
CR5 R18 CR1
CR26
K4
2000 RFL ELECTRONICS INC, BOONTON NJ U.S.A. 9745 RELAY I/O ECB NO 105958 REV-A RZ4
1
RZ2
C1
R1 1
R22
J4
P1
R9 R1 0 C R1 5
C1 3
J3
R16
R17
CR24
CR25 K6
K5
U6
U7
CR19 R13
CR21 R14
CR20
CR22
K7
K3 K2 A
A
R4
B
B
J8
B
C35
B
J6
J7
J5 C7 C3 6
C1 6
C6 C1 7 L1
L2
L3
TB1
J8
C8
C5 L4
L5
C1 0
C9
L6
C1 1
L7
C2 5
C1 2
L8
L1 1
C2 7
C2 6 L1 2
L1 3
L1 4
J5
C2 8 L1 5
C2 9
C3 0
C3 1
L1 6
L1 7
L1 8
C3 2
C3 3
C1 8
C2 C1 0 9
C2 1
L1 9
J6
J7
High speed relay (Assy. No. 105955).
Figure 3-33. continued. Location of jumpers on the SWC I/O Modules
RFL 9745 February 24, 2009
3 - 59
RFL Electronics Inc. (973) 334-3100
Page 143
3.7 COMMISSIONING PROCEDURES 3.7.1 RFL 9745 AUDIO TONE COMMISSIONING PROCEDURE 3.7.1.1 EQUIPMENT REQUIRED 1. PC or Laptop computer 2. 9 pin straight through cable with male and female connector. 3. Selective Voltmeter (optional)
3.7.1.2 JUMPER SETTINGS The jumper settings are performed at RFL per customer application. Follow the list below for confirmation of the jumper settings. Refer to paragraph 3.6 for additional information. Wide Band Audio Comms module: for 4 wire single: set J3, J10 to A, J5 and J11 to 4W. for 4 wire dual: set J3, J10 to B, J5 and J11 to 4W. for 2 wire single: set J3, J10 to A, J5 and J11 to 2W. for 2 wire dual: set J3, J10 to B, J5 and J11 to 2W. CPU module: Ref. Section 3.6.1 Driver module: check for jumper J2-NORM. I/O modules: select J1, J2, J3 and J4 for proper input keying voltage 48/125 Vdc. For the 24 Vdc and the 250 Vdc modules there is no jumper selection. For outputs Ref. 3.6.7 Power Supply module: No user settings: Front Panel module: No user settings:
3.7.1.3 WIRING Specific CD drawings are supplied with each order. Connect all external wiring to the unit in accordance with the rear view chassis wiring drawing, and Primitive and Alarm logic drawings supplied with the chassis.
3.7.1.4 POWER Turn the unit on by pressing the rocker switch at the rear of the unit. Check Station Battery voltage at TB1-9 (+) and TB1-10 (-) for proper voltage. The green LED on the Power Supply should be lit. On the Driver module check the positive 5 and 15 Vdc. TP1 is common, TP6 is +15Vdc (14.25 to 15.75Vdc), and TP2 is +5Vdc (4.75 to 5.75Vdc).
RFL 9745 February 24, 2009
3 - 60
RFL Electronics Inc. (973) 334-3100