Instruction Manual RFL 9745 Teleprotection Channel: Section 3. INSTALLATION, pages 144 to 153

Pages 144 to 153 of 394, from Instruction Manual RFL 9745 Teleprotection Channel

The original document is the PDF (6.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the RFL RFL-9745

Page 144

3.7.1.5 9745 BAUD RATE On the front panel of the unit press the “LEVELS” button, then press the “UP” button. The unit should display the baud rate. If it does not display 9600 press the “ENTER” button, then press the “UP” button to change the baud rate to 9600. Then press the “ENTER” button again.

3.7.1.6 RS-232 COMMUNICATIONS Set up the RS-232 communications by using the following procedure: 1. Connect a Laptop or PC computer to the front RS-232 port via a straight through 9 pin cable. 2. Click on the PC APRIL LITE icon on your desktop and go to “Setup.” 3. Set up your COM Options, then click on “Terminal.” 4. Hit the “ENTER” key to display a “9745>” prompt. 5. When you see the “9745>” prompt, you are receiving data from the 9745. 6. On your PC turn the Caps Lock on.

3.7.1.7 LOADING THE LOGIC AND BATCH FILES If RFL is supplying custom logic at the time of shipment of the chassis, the logic will be loaded and tested in the units at the factory. If the RFL 9745 does not contain the operating logic and parameters required for your application, you must load the proper custom logic files by following the steps below: 1. Click on “Upload to 9745.” 2. Click on “Upload Logic File.” 3. Browse to the location of the MHX file. 4. Click on “Send.” 5. When completed click on “OK” then “Exit.” To load the BAT file, do the following: 1. Click on “Upload to 9745.” 2. Click on “Upload Parameter File.” 3. Browse to the location of BAT file. 4. Click on “Send.” 5. When completed click on “OK” then “Exit.”

RFL 9745 February 24, 2009

3 - 61

RFL Electronics Inc. (973) 334-3100

Page 145

3.7.1.8 SYSTEM SETTINGS (PROGRAMMING MENU) 1. On the PC type the letter “P” to enter the Programming menu. 2. Enter the password. 3. Type the letter “D” to display the current settings. 4. Set the Transmit level for all active channels; lines 3, 18, 33 and 48. 5. On the front panel press the “LEVELS” button, then press the “DOWN” button until you get to Receive 1, Receive 2, Receive 3 and Receive 4. Record the levels displayed for each channel. In the programming menu set the Receive level settings for each channel on lines 7, 22, 37 and 52 to match the values from the Levels display. 6. If it is necessary to change the frequencies, bandwidth, channel shift, or FM or AM noise, refer to pages 5-10 and 5-11 of the 9745 instruction manual for suggested settings. 7. Set the RX ALARM detectors, lines 8, 23, 38 and 53 to 8 dB below the receiver level set in step 5 above. 8. If you set the Audio communications module to operate as a dual channel four wire system, then line 61 EE POT J10 should be set to “B”. 9. Set line 62 CHANNEL DELAY to the maximum communications channel delay your protection scheme can tolerate. 10. Set line 63 YEAR to the current year. 11. Set line 64 DATE to the current date. 12. Set line 65 TIME to the current time. 13. Set line 67 LOCAL ADDRESS to a user preferred value. This value must match the value of line 68 REMOTE ADDRESS on the remote chassis. 14. Set line 68 REMOTE ADDRESS to a user preferred value. This value must match the value of line 67 LOCAL ADDRESS on the remote chassis. 15. Type “SV” to save all the changes made in the programming menu. 16. Type “Q” to quit the programming menu.

RFL 9745 February 24, 2009

3 - 62

RFL Electronics Inc. (973) 334-3100

Page 146

3.7.1.9 INPUT, OUTPUT, AND ALARM RELAY LABELS If you would like to apply labels to the inputs, outputs or the alarm relays, use the following procedure: (Refer to Section 6 for more information) 1. Type “K” and “ENTER” to enter the Logic programming menu. 2. Enter the password. 3. Type “A” to go to the Alarm and I/O name menu. 4. Enter the line number of the item you would like to change. 5. Enter the label information. 6. Type “SV” to save the new labels, prior to leaving this menu.

3.7.1.10 MODEM TESTING If you are using channel 1 in the modem mode, perform the following steps: 1. From the main menu enter the Test menu by typing “T” and “ENTER”. 2. Enter the password. 3. Set line 6 TESTS/RESETS FROM THE FRONT PANEL to “ENABLED”. 4. From the front panel press the “TEST” button. Press “UP” or “DOWN” until you get to CHECKBACK TEST. Press “ENTER” to run a checkback and address test. 5. On the front panel press “UP” or “DOWN” until you get to PING PONG. Press “ENTER” to run the ping pong (channel delay) test.

3.7.1.11 END TO END TESTING Using the Primitive Logic drawing apply voltage to the keying inputs at the local end. On the remote end observe that the appropriate trip outputs energize. The TX and RX front panel LEDs should illuminate for all tripped channels. Exercise all aspects of the primitive and alarm logic observing all outputs for their correct response.

RFL 9745 February 24, 2009

3 - 63

RFL Electronics Inc. (973) 334-3100

Page 147

3.7.1.12 RESETTING RECORDS To reset the Log Counters from the front panel, do the following: 1. On the front panel press “LOG”, then press “UP” to access “RESET”. 2. Press “ENTER”, “UP” and “ENTER” to reset the log counters. To reset the Sequence of Events Log with a PC, do the following: 1. From the main menu type “S” and “ENTER” to enter the Sequence of Events menu. 2. Type “R” to select reset. 3. Type “Y” to select yes. 4. Press “ENTER” to reset the Sequence of Events Log. To disable the front panel with a PC, do the following: 1. From the main menu enter the Test menu by typing “T” and “ENTER”. 2. Enter the password. 3. Set line 6 TESTS/RESETS FROM THE FRONT PANEL to “DISABLED”. 4. Type “Q” to quit the test menu.

3.7.1.13 EXITING THE 9745 (Refer to Section 9 for more information) 1. On your PC click on “Terminal” then “Disconnect.” 2. Click on “OK.” 3. Then click “File” and “Exit” (no save necessary) to exit PC April Lite.

RFL 9745 February 24, 2009

3 - 64

RFL Electronics Inc. (973) 334-3100

Page 148

3.7.2 RFL 9745 DIGITAL COMMISSIONING PROCEDURE 3.7.2.1 EQUIPMENT REQUIRED 1. PC or Laptop computer 2. 9 pin straight through cable with male and female connector.

3.7.2.2 JUMPER SETTINGS The jumper settings are performed at RFL per customer application. Follow the list below for confirmation of the jumper settings. Refer to paragraph 3.6 for additional information. Digital Communications module: Set J1 to B. Set J2 to B. Set J3 to 56K or 64K (Refer to paragraph 3.6.5). Set J4 to A. Set J5 to A. Set J6 to B (Refer to paragraph 3.6.5). CPU module: check for jumpers J1-installed, J6-installed, and J7 in A position. Driver module: check for jumper J2-NORM. I/O modules: select J1, J2, J3 and J4 for proper input keying voltage 48/125 Vdc. For the 24 Vdc and the 250 Vdc modules there is no jumper selection. Power Supply module: If a 48/125 Vdc power supply is being used (105020-2) set SW1 to the 48V position if 48Vdc is being used, or set SW1 to the 125V position if 125 Vdc is being used. All of the other power supplies have no user settings. Front Panel module: no user settings:

3.7.2.3 WIRING Specific CD drawings are supplied with each order. Connect all external wiring to the unit in accordance with the rear view chassis wiring drawing, and Primitive and Alarm logic drawings supplied with the chassis.

3.7.2.4 POWER Turn the unit on by pressing the rocker switch at the rear of the unit. Check Station Battery voltage at TB1-9 (+) and TB1-10 (-) for proper voltage. The green LED on the Power Supply should be lit. On the Driver module check the positive 5 and 15 Vdc. TP1 is common, TP6 is +15Vdc (14.25 to 15.75Vdc), and TP2 is +5Vdc (4.75 to 5.75Vdc).

RFL 9745 February 24, 2009

3 - 65

RFL Electronics Inc. (973) 334-3100

Page 149

3.7.2.5 9745 BAUD RATE On the front panel of the unit press the “LEVELS” button, then press the “UP” button. The unit should display the baud rate. If it does not display 9600 press the “ENTER” button, then press the “UP” button to change the baud rate to 9600. Then press the “ENTER” button again.

3.7.2.6 RS-232 COMMUNICATIONS Set up the RS-232 communications by using the following procedure: 1. Connect a Laptop or PC computer to the front RS-232 port via a straight through 9 pin cable. 2. Click on the PC APRIL LITE icon on your desktop and go to “Setup.” 3. Set up your COM Options, then click on “Terminal.” 4. Hit the “ENTER” key to display a “9745>” prompt. 5. When you see the “9745>” prompt, you are receiving data from the 9745. 6. On your PC turn the Caps Lock on.

3.7.2.7 LOADING THE LOGIC AND BATCH FILES If RFL is supplying custom logic at the time of shipment of the chassis, the logic will be loaded and tested in the units at the factory. If the RFL 9745 does not contain the operating logic and parameters required for your application, you must load the proper custom logic files by following the steps below: 1. Click on “Upload to 9745.” 2. Click on “Upload Logic File.” 3. Browse to the location of the MHX file. 4. Click on “Send.” 5. When completed click on “OK” then “Exit.” To load the BAT file, do the following: 1. Click on “Upload to 9745.” 2. Click on “Upload Parameter File.” 3. Browse to the location of BAT file. 4. Click on “Send.” 5. When completed click on “OK” then “Exit.”

RFL 9745 February 24, 2009

3 - 66

RFL Electronics Inc. (973) 334-3100

Page 150

To enable hidden parameters, do the following: 1. Type “T” and press “ENTER” to access the Test Menu. 2. Type in the password. 3. Type “99” and then press “ENTER”. 4. Type “E” to enable “DEBUG INFORMATION” and then press “ENTER”.

3.7.2.8 SYSTEM SETTINGS (PROGRAMMING MENU) 1. On the PC type the letter “P” to enter the Programming menu. 2. Enter the password. 3. Type the letter “D” to display the current settings. 4. Set line 63 YEAR to the current year. 5. Set line 64 DATE to the current date. 6. Set line 65 TIME to the current time. 7. Set line 67 LOCAL ADDRESS to a user preferred value. This value must match the value of line 68 REMOTE ADDRESS on the remote chassis. 8. Set line 68 REMOTE ADDRESS to a user preferred value. This value must match the value of line 67 LOCAL ADDRESS on the remote chassis. 9. Type “SV” to save all the changes made in the programming menu. 10. Type “Q” to quit the programming menu.

RFL 9745 February 24, 2009

3 - 67

RFL Electronics Inc. (973) 334-3100

Page 151

3.7.2.9 INPUT, OUTPUT, AND ALARM RELAY LABELS If you would like to apply labels to the inputs, outputs or the alarm relays, use the following procedure: (Refer to Section 6 for more information) 1. Type “K” and “ENTER” to enter the Logic programming menu. 2. Enter the password. 3. Type “A” to go to the Alarm and I/O name menu. 4. Enter the line number of the item you would like to change. 5. Enter the label information. 6. Type “SV” to save the new labels, prior to leaving this menu.

3.7.2.10 MODEM TESTING 1. From the main menu enter the Test menu by typing “T” and “ENTER”. 2. Enter the password. 3. Set line 6 TESTS/RESETS FROM THE FRONT PANEL to “ENABLED”. 4. From the front panel press the “TEST” button. Press “UP” or “DOWN” until you get to CHECKBACK TEST. Press “ENTER” to run a checkback and address test. 5. On the front panel press “UP” or “DOWN” until you get to PING PONG. Press “ENTER” to run the ping pong (channel delay) test.

3.7.2.11 END TO END TESTING Using the Primitive Logic drawing apply voltage to the keying inputs at the local end. On the remote end observe that the appropriate trip outputs energize. The TX and RX front panel LEDs should illuminate for all tripped channels. Exercise all aspects of the primitive and alarm logic observing all outputs for their correct response.

RFL 9745 February 24, 2009

3 - 68

RFL Electronics Inc. (973) 334-3100

Page 152

3.7.2.12 RESETTING RECORDS To reset the Log Counters from the front panel, do the following: 1. On the front panel press “LOG”, then press “UP” to access “RESET”. 2. Press “ENTER”, “UP” and “ENTER” to reset the log counters. To reset the Sequence of Events Log with a PC, do the following: 1. From the main menu type “S” and “ENTER” to enter the Sequence of Events menu. 2. Type “R” to select reset. 3. Type “Y” to select yes. 4. Press “ENTER” to reset the Sequence of Events Log. To disable the front panel with a PC, do the following: 1. From the main menu enter the Test menu by typing “T” and “ENTER”. 2. Enter the password. 3. Set line 6 TESTS/RESETS FROM THE FRONT PANEL to “DISABLED”. 4. Type “Q” to quit the test menu.

3.7.2.13 EXITING THE 9745 (Refer to Section 9 for more information) 1. On your PC click on “Terminal” then “Disconnect.” 2. Click on “OK.” 3. Then click “File” and “Exit” (no save necessary) to exit PC April Lite.

RFL 9745 February 24, 2009

3 - 69

RFL Electronics Inc. (973) 334-3100

Page 153

3.8 WIDEBAND AUDIO COMMUNICATIONS MODULE UPGRADE INSTALLATION INSTRUCTIONS The instructions in this section describe how to upgrade an RFL 9745 terminal from one using a narrowband audio communications module to one using a wideband audio communications module. Equipment Required 1. 2. 3.

Wideband Audio Communications Module (Assembly No. 105920-1, -2, -3 or -4) RFL 9745 PC April Lite software CD (Part No. SW9745PALXX)* RFL 9745 Wideband system software CD (Part No. SW9745SY0XX)*

* XX = Revision level. Basic Steps 1. 2. 3. 4. 5.

Remove narrowband module Set jumpers on wideband module Install wideband module Install new April software Install wideband system software

3.8.1 REMOVING THE NARROWBAND MODULE The Audio Communications Module is mounted at the front of the RFL 9745 chassis, and extends to the rear where it is attached to a plate along the top of the chassis. To remove the narrowband audio communications module, proceed as follows: 1.

On the RFL 9745 rear panel, place the POWER switch on the power supply I/O module behind the Main Power Supply Module to the OFF position.

2.

If the RFL 9745 is equipped with a redundant power supply, place the POWER switch on the power supply I/O module behind the Redundant Power Supply Module to the OFF position.

3.

Open the door on the front of the RFL 9745 by loosening the two thumbscrews that hold it closed, and lower the door to its opened position.

4.

Disconnect the ribbon cables from the front edge of the Communications module.

5.

Disconnect all cables from the connectors on the plate behind the Communications module. (Rear RS-232 connector)

6.

Disconnect all wires from terminal blocks (TB2) on the plate behind the communications module. Tag all wires before removing them if they aren’t already labeled. This will simplify reassembly.

7.

Using a cross blade screwdriver, remove all screws near the connectors and terminal blocks on the plate behind the communications module. Do not remove the screws in the corners of the plate. These hold the plate in position.

8.

Pull the communications module out of the front of the chassis.

RFL 9745 February 24, 2009

3 - 70

RFL Electronics Inc. (973) 334-3100