Instruction Manual RFL 9745 Teleprotection Channel: Section 3. INSTALLATION, pages 124 to 133
Pages 124 to 133 of 394, from Instruction Manual RFL 9745 Teleprotection Channel
The original document is the PDF (6.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the RFL RFL-9745
Page 124
Clocking is embedded with the RS-449, X.21 and all direct fiber connections. J6 MUST be set to “A” regardless of any external clock provided by an external device such as a multiplexer. Note 1: For bench testing (back to back) using an electrical connection (RS-449 or X.21) clocking must be set on one side to “Clock Source Enable.” This is done on the 9745 via the front panel push-buttons. Note 2: For bench testing (back to back only) on the G.703 interface one 9745 jumper MUST be set to “A” and the other to “B.” Note 3: When using the E1 Serial Interface Adapter, dip switch SW1-4 on the adapter can be set as follows: UP SW1-4
Loop Timing
DOWN Internal Timing (Transmit a Clock)
See Section 3.6.5.5 for further information on the E1 Serial Interface Adapter.
RFL 9745 February 24, 2009
3 - 41
RFL Electronics Inc. (973) 334-3100
Page 125
9
6
5
1
P1
BNC1 RZ4
R7 C13
CR5
C14
C34
C35 CR1
CR4 C28
C29
CR3 C26
J6
C27
CR2 C24
C25
TP3 C12 C11
+
C10 C6 L4 2 1
TP4
C5
C9
C3 +
L6 P5
C4 +
C8
TP8 C7
C1
C2
L2
+
P3 1 16
1 +
+ TP6
C21
C18
C44 C47 C71
U3 4 Q1
C19
TP18
C72
U3 5
C46 U4 0
U3 9
U3 6
Y X O
R25
C20
R26
Q2
R8
C45
P4
C70
C17
C23
L9
16
RZ 11
U4 5
RZ 12
C15
+
C16 C22
C67
L3 C61 U4 4
TP19
R9
R32 TP1
R3
TP9
R5
TP2
U5
C60 U1
C3 C4 2 9
C62 U1 0
C63
C64
U3 3
C65
U4 3
C66
U4 2
C68
U3 2
C69
U4 1
J5
U3 1
B A
R4
A
C42 +
A
U4 6
C4 3
B R33
J4
C48 U2
U3 7
TP20
J6 C89
C31
B
R13
R1
L8
R15 Y1
R14
C39 C41
C40
C36 R2
C30
R30
R22
R24
R16
R17 R20 RZ6 C5 0
R21
R23
R19 TP10
C9 0
C9 1
R31
RZ7
TP11
TP14
TP15
TP16
TP17
TP12 C5 1
C58
U11
U3
TP13
J3 C38
56K
R12 R6 C33
U2 3
C78 U2 4
R29 RZ 2
49
50
RZ 1
R28
C57 C81 U1 8
U1 6 C55
R11 R10
C77
U12
R27
U38 64K
R18 C37
RZ 8
C82 U2 0
C83 U2 2
C79 U2 5
U1 5
C80 U2 8
B J1 U1 3 A
C87
U1 4
RZ 3
C54
C53 U29
C59
U30 C5 2
C5 6
C75
C73 U6
U7
U8
C84
C74 RZ 10
U9
C86
U1 7
U4
J2
U2 6
RZ 5 U1 9
A C88
RZ 9
B
C85 U2 1
U2 7
C76 1
P2
TP5
2
TP7
J1
J4
J5
J3
J2
Figure 3-24. Location of jumpers on the Digital Communications Module
RFL 9745 February 24, 2009
3 - 42
RFL Electronics Inc. (973) 334-3100
Page 126
3.6.5.1 RS-449 INTERFACE MODULE The RS-449 interface module (Assembly No. 105065-1) has two programmable jumpers labeled “J1” and “J2”. See the Figure below for jumper locations. If the RFL 9745 is interfaced with an IMUX 2000 refer to paragraph 3.6.5.1.1. J1
J1 is set to NORM position to select a normal TX Clock, or to INV position to select an inverted TX Clock. This jumper is set to INV position at the factory.
J2
J2 is set to NORM position to select a normal Rx Clock, or to INV position to select an inverted Rx Clock. This jumper is set to INV position at the factory.
30
SD
2
CONNECTOR. FEM. AT ANGLE
RD
ST
RT C2
29
1
C
P1
C1
R2 0
R2 1
R2 2
R1 9
+
U1
C15 R12 CR CR 15 14
C5 C20
R13
R10
C3
K1
K2
U3 1
CR CR 16 17
CR 2
R11
1
C14
CR R2 1
R3
C8
U2
19 97 RF L EL EC TR ON IC S IN C. BO ON TO N, NJ, U. S.A .
R6 R7
U4
U5
R2 4
R2 6
R4 C1 1
R5
C1 0
R2 3
R2 5
C16 1
R16 R17
RZ 2
R14
RZ 3
1
RZ 1
R15 K3 J2
K4
J1 IN V
RX
NO IN RM V
NO RM
TX
CRZ1 1
19
P2
CONN. PLUG, MALE 37 PIN 37
20
J2
R1
J1
Figure 3-25. Location of jumpers on the RS-449 Interface Module
RFL 9745 February 24, 2009
3 - 43
RFL Electronics Inc. (973) 334-3100
Page 127
3.6.5.1.1 INTERFACING THE RFL 9745 WITH AN IMUX 2000 (RS-449) Interfacing an RFL 9745 with an IMUX 2000 can be accomplished as follows: A. The programmable jumpers on the RFL 9745 RS-449 interface module, as shown in Figure 3-25, shall be positioned as follows: J1 (Send Timing) should be set to select the inverted TX clock. J2 (Receive Timing) should be set to select the inverted Rx clock. B. The Configuration of the IMUX 2000 RS-449 Channel Card shall be as follows: 1. If a DS-562I is used with an MA-406IA I/O (DCE Mode), set switch 4 as follows: Switch 4-2 (Receive Clock Polarity) set to Normal - ON (Right) Switch 4-3 (Transmit Clock Polarity) set to Normal - ON (Right) C. Confirm Clock and Data Transitions to insure proper system operation as follows: 1. RFL 9745 RS-449 I/O - The positive edge of the Rx Clock (TP4 or RT) must be in the center of the Rx Data bit (TP2 or RD). 2. IMUX 2000 DS-562I -
The positive edge of the TX Clock (TP3) must be in the center of the TX Data bit (TP1).
If more information is needed refer to the IMUX 2000 Instruction Manual.
RFL 9745 February 24, 2009
3 - 44
RFL Electronics Inc. (973) 334-3100
Page 128
3.6.5.2 G.703 CONTRA-DIRECTIONAL INTERFACE MODULE The G.703 Contra-Directional Interface module (Assembly No. 105065-2) has two programmable jumpers labeled “J1” and “J2”. See the Figure below for jumper locations. J1
J1 is set to Position A to select a normal TX Clock, or to Position B to select an inverted TX Clock. This jumper is set to position A at the factory.
J2
J2 is set to Position A to select an inverted Rx Clock, or to Position B to select a normal Rx Clock. This jumper is set to position B at the factory.
J2
J1
Figure 3-26. Location of jumpers on the G.703 Contra-Directional Interface Module
RFL 9745 February 24, 2009
3 - 45
RFL Electronics Inc. (973) 334-3100
Page 129
3.6.5.3 X.21 INTERFACE MODULE The X.21 Interface module (Assembly No. 105065-10) has two programmable jumpers labeled “J1” and “J2”. See the Figure below for jumper locations. J1
J1 is set to NORM position to select a normal TX Clock, or to INV Position to select an inverted TX Clock. This jumper is set to NORM position at the factory.
J2
J2 is set to NORM position to select a normal Rx Clock, or to INV position to select an inverted Rx Clock. This jumper is set to NORM position at the factory.
TP4
TP3
TP2
CR17
CR16
CR14
R19
R20
CR15
SN75174
U1 1K 1K 1K 1K
15
15
R26
15
R24
12V (98439)
1
15
182
.1uF
1N4003 CR1
C10
R2
12V (98439)
1
RZ1
RZ3
RZ2
SOFTWARE
CR2
.1uF
182
1N4003
C11
R3
R22 R21
C17 .1uF
C8 .1uF
.1uF
SOCKET 97259 U5
60.4 60.4
C6 C4
10K
R4 R5
.1uF
10K
1K 1K
C3
.1uF
100K
100pF
R6 R7
C18
C21
74HC244
C14
.01uF
U4
60.4
+ .1uF
SN75175
60.4
R11
.01uF
33uF
.01uF
U2
R10
TP1
SN75174
U3
12V
(98439)
1K
C5
C1
R8
CR3 X.21 I/O 1 K1 ECB NO. 105903-1 REV-A
R13
C19
47uF
100pF 1K
.1uF
C2
1
C12
.1uF
C15 R12
33uF C9
+
C7
P1
.1uF
182
1N4003
C 1997 RFL ELECTRONICS INC. BOONTON, NJ, U.S.A.
GND
29
(101723)
+ C20
2
30
CONNECTOR,FEM,RT ANGLE,30P
R25
R23
K3
K2
R1
NORM
TX
INV
RX
(ALTERNATE FOR CRZ1)
NORM
INV
CRZ1
J1
J2
CRZ3 (103392)
(103392)
LCA08C
CRZ2 100
1
8
(ALTERNATE FOR CRZ1)
P2
(103342) 9 CONN.,PLUG,MALE 15 PIN
J2
15
J1
Figure 3- 27. Location of jumpers on the X.21 Interface Module
RFL 9745 February 24, 2009
3 - 46
RFL Electronics Inc. (973) 334-3100
Page 130
3.6.5.4 G.703 CO-DIRECTIONAL INTERFACE MODULE The G.703 Co-Directional Interface module (Assy. No. 105065-11) has one programmable jumper, labeled "J1". See the Figure below for the jumper location. When this jumper is installed the module will generate octet timing.
30
2
U4
B RF E G. O L C 70 O EL B 3 NT E 10 C O CT 59 ON, R 68 DI NJ O R R. O , NI U. C CT S
R18
P1
1
R19 R20
C1 U3
U1 +
C2
C19 U2 R11
+ C6
C5
TP 10
C4
C7
C15
J2
TP 4 C13
C1 6 C3
C1 8
TP 3
R16 C12
TP 1
R15
1
C14 TP 2
R13
R8
R14
R10
TP 9
R12 C8 C10 R17 J1
C11
C17
R5
C9
R7
R9 R6 CR11 CR12 K2
CR1 T1
K1
CR6 1
CR2
R2
TP 5
CR3
1
8
T2
1
CR7
TP 7
CR8
CR4 R4
CR10 TP 6
R1
15
9
P2
CR5
TP 8
R3 CR9
J1
Figure 3- 28. Location of jumper on the G.703 Co-Directional Interface Module
RFL 9745 February 24, 2009
3 - 47
RFL Electronics Inc. (973) 334-3100
Page 131
3.6.5.5 E1 SERIAL INTERFACE ADAPTER
SW1-1
SW1-10
E1 INTERFACE
SW1
YELLOW ALARM
DATA
120 OHM
TX
RX
75 OHM 107320
Figure 3- 29. E1 Serial Interface Adapter Front Panel
The 9745 Serial Interface Adapter (107320) allows the 9745 to plug directly into a 2.048 Mb/s G.704 & G.703 compliant port on a higher order multiplexer. A 15 pin D-subminiature connector and two 75 Ohm BNC connectors are provided for this connection. A bank of DIP switches, a slide switch, and two programmable jumpers are provided for setting up the interface adapter. Loss of Sync and Yellow Alarm indicators are provided to assist the user with setup of the module. When this interface adapter is used with the 9745, all performance criteria is the same as specified for any other digital version of the 9745 when run at 64 kb/s. Trip times are unchanged from 64 Kb/s. When this interface is installed, the 9745 reports the interface type as “Short Haul Fiber”. Connectors The interface uses either a 15-pin D-subminiature connector or two BNC connectors for connection to the network. J3 is a 15-pin D-subminiature connector that provides a 120 ohm interface using dual shielded-twisted-pair E1 cable. J4 and J5 are BNC connectors that provide a 75 ohm interface using RG-59 coax cables. J4 is the transmit output and should be connected to the receive input of the multiplexer. J5 is the receive input and should be connected to the transmit output of the multiplexer. Indicators There are two LED indicators on the unit. Their functions are as follows: DATA – If this indicator is illuminated, then the interface is properly receiving a valid framed E1 signal from the multiplexer. YELLOW ALARM - If this indicator is illuminated then the interface is receiving a yellow alarm from the multiplexer. This is the G.704 remote alarm indication. The remote alarm may be generated by the multiplexer or from the remote 9745 depending on the multiplexer set up. In either event, it is an indication that the transmit signal from the 9745 with the yellow alarm indicator illuminated is not getting to the device generating the yellow alarm.
RFL 9745 February 24, 2009
3 - 48
RFL Electronics Inc. (973) 334-3100
Page 132
SW1
SW2
J6
J7
Figure 3- 30. Location of jumpers and switches on E1 serial interface adapter
RFL 9745 February 24, 2009
3 - 49
RFL Electronics Inc. (973) 334-3100
Page 133
Switches SW1 is a 10 position DIP switch mounted facing the rear panel. The switches are numbered 1 to 10 from left to right. The operation of the switches is shown in the table below. SW2 is a slide switch mounted on the printed circuit board. It is used to select the impedance of the I/O connectors. When using the 120 ohm D-subminiature connector, SW2 is set in the position labeled “120”. When using the 75 ohm BNC connectors, SW2 is set in the position labeled “75”. Table 3-9. E1 Serial Interface Adapter Switch Settings Switch SW11 2 3 4 5 6 7 8 9 10
Function CRC Generation Digital Loop-back Data Encoding Timing Mode Receive All Ones Transmit All Ones Local Loop-back Jitter Attenuator Remote Loop-back Jitter Attenuator Selection
Description UP– Generate CRC-4 DOWN – do not generate CRC-4 UP – Normal operation DOWN – Enable Digital Local Loop-back UP – HDB3 encoding and decoding DOWN – AMI encoding UP – Loop Timing DOWN – Internal Timing UP – Receive All Ones DOWN – Normal operation UP – Transmit All Ones DOWN – Normal operation UP – Normal operation DOWN – Enable Local Loop-back UP – Enable Jitter Attenuator DOWN – Disable Jitter Attenuator UP – Normal operation DOWN – Enable Remote Loop-Back - With SW1-8 UP (Jitter Attenuator enabled): UP – Jitter Attenuator in the transmit path DOWN – Jitter Attenuator in the receive path
Typical Setting UP-Generate CRC-4 UP-Normal Operation UP-HDB3 Encoding No Default DOWN-Normal Operation DOWN-Normal Operation UP-Normal Operation UP-Enable Jitter Attenuator UP-Normal Operation DOWN-Jitter Attenuator in RX
- With SW1-8 DOWN (Jitter Attenuator disabled): SW1-10 must be DOWN
Programmable Jumpers Jumpers J6 and J7 are used to ground the outer conductors of BNC connectors J4 and J5 respectively. When in the position labeled “G”, the outer conductor of the corresponding BNC connector is grounded by connecting it to chassis. When in the position labeled “U” the outer conductor of the corresponding BNC connector is ungrounded. When using the 15 position d-sub connector, J6 and J7 should be in the position labeled “U”. This leaves all the TX and RX connectors floating which is required since the 120 ohm twisted pair is a balanced connection. When using the BNC connectors, J6 should be in the position labeled “G” and J7 should be in the position labeled “U”. This configuration grounds the outer conductor of the TX connection and leaved the RX connection ungrounded.