Page 71
Section
Maintenance and Inspection
5-7
5-7
Maintenance and Inspection To always keep the ID Controller in the best condition, the Controller should be inspected daily or periodically. Although the ID Controller consists of semiconductor devices, without a limited life, the following troubles may occur depending on the environments and conditions in which the ID Controller is operated: 1, 2, 3...
1. Degradation of elements due to overcurrent and overvoltage. 2. Degradation of elements due to long-term stress, if the ID Controller is used at high temperatures. 3. Degradation of insulation and faulty connector contact of due to humidity and dust. 4. Faulty connector contact or corrosion due to corrosive gas.
Items of Inspection No. 1
2
Item Supply voltage fluctuation
Particulars Voltage measured at terminal block within rated range? Momentary power failure frequently occurs? Abrupt rise in supply voltage occurs?
Criteria Supply voltage must be within rated range. Supply voltage must be within rated range.
Environments: (a) Temperature
Remarks Tester Power analyzer
Thermometer, hygrometer (a), (b) Must be within rated values
(b) Humidity
(a) –10° to +55°C (b) 35 to 85% RH.
(c) Vibration, shock
(c) Is the Controller subject to (c) Must be in specified vibration or shock from range. surrounding machines?
(d) Dust
(d) Does dust or foreign object collect on the Controller?
(d) Must be free from dust and foreign objects.
(e) Corrosive gas
(e) Are the metallic parts discolored or corroded?
(e) Must be free from discoloration and corrosion.
(a) Is ventilation good?
(a) Natural ventilation, forced ventilation, and air conditioning are adequate?
(a) Good ventilation is --essential. Temperature in panel must be –10° to +55°C.
4
(b) Is packing damaged in the sealed panel? I/O power (a) Voltage fluctuation (b) Ripple
(b) Are panel packings loose or damaged? Is voltage measured at terminal block of each I/O within rated level?
(b) Must be free from damage. Must be within rated range.
Tester, oscilloscope
5
Mounting condition
(1) Is each device fixed securely? (2) Are connectors inserted securely? (3) Aren’t screws of terminal block loose? (4) Is the wiring damaged?
Must be tightened.
---
Must be free from damage.
---
(5) Are the communications specifications between DC and R/W Head satisfied?
Must be within rated range.
---
Check the DC date of production. Check error.
Must be within guaranteed period. ---
---
3
Condition of pane:
6
Battery life of DC
7
Error logging
62
Must be locked and tightened --with screws. Must not be loose. ---
---
Page 72
Section
Systems Check
!
5-8
WARNING
A lithium battery is provided with the Data Carrier in order to backup the memory. When the battery life ends, do not throw the battery into fire as it may explode.
5-8
Systems Check If a malfunction has occurred, carefully investigate the surrounding conditions and check whether the trouble still persists or is related to other equipment. Then track down the malfunction according to the following procedure:
Main Check
Main flow check
System connected correctly?
Make a decision depending on the nature of the error.
N
To System Connection Check (page 56)
Y
Host communications normal?
N
To Host Communication Check (page 57)
Y
Lower communications normal?
N
To Lower Communication Check (page 58)
Y
External environments normal?
N
To External Environments Check (page 59)
Y Replace Unit
63
Page 73
Section
Systems Check System Connection Check
Make a decision depending on the nature of the error.
START
Connector and cable correctly connected?
NO
YES Connect correctly.
Power ON
POWER indicator?
Not lit
Lit
Monitor display
“00” displayed
(STOP) LED
NO
92 or 93 displayed
Rated voltage supplied?
Supply rated voltage
YES
Lit
Not lit Reset input ON?
NO
YES Reset input OFF
OK
64
Power ON
5-8
Page 74
Section
Systems Check
5-8
Host Communication Check START
TS command from host
Response normal?
NO
YES To Lower Communication Check
Communication format correct?
NO
YES Match communication format
Connect wiring correct?
NO
YES
Correct connector wiring Host operates normally?
NO
YES Replace Unit
Correct host program or host computer
65
Page 75
Section
Systems Check Lower Communication Check
START
Set mode SW to 5
E70?
YES
NO
Moving speed OK?
YES
NO
YES
NO
DC OK?
YES
NO
Slow down
E71? or E72? or E7B?
DC located with correct direction?
YES
DC OK?
NO
Adjust distance and direction
Replace DC
YES
NO Replace DC
E7C?
YES
NO
R/WH R/WA OK?
YES
NO Replace R/W Head
Communication OK?
YES
NO
Distance between R/W Head and DC correct? NO Adjust distance
Normal completion?
YES
DC OK?
YES
NO Replace DC
NO
YES OK
66
Replace Unit
5-8
Page 76
Section
Systems Check
5-8
External Environments Check START
Operating conditions OK?
NO
Refer to Maintenance and Inspection of User’s Manual
NO
Refer to Troubleshooting of User’s Manual
YES Noise environments OK? YES START
67
Page 77
Appendix A Codes JIS 8 Code List (ASCII List) Higher digits Lower digits Row Column
Undefined
Undefined
Undefined
Undefined
Undef.
Undef.
Note 1. The code at the 5th row, 12th column is “\” in ASCII code. 2. CR cannot be used as text data.
69
Page 78
Appendix B Auto Read/Auto Write Use of Auto Read/Auto Write Command Generally, the read or write command is used while the DC is not moving. The auto command, in contrast, is used while the DC is moving.
Read/Write Commands • The communication distance width is wider than when the DC is moving, so that communications can be accurately performed. R/W Head or R/W Antenna
DC Not moving
Auto Read/Write Commands • By using the auto command, the approaching or missing DC can be automatically detected. • If the DC moving speed is low and positioning is accurate, the communication is not limited by distance (within reason). R/W Head or R/W Antenna
DC Moving
71
Page 79
Appendix B
Auto Read/Auto Write
Application Example of Command Item
Application
Command transmission by timer
Transmits next auto command after response is returned.
R/W Head or R/W Antenna
Trigger
Transmits next auto command when some trigger is received after a response is returned.
Trigger R/W Head or R/W Antenna
Description
Note
–When DC passes through the communications area of R/W Head at fixed intervals. – If a long time elapses before next DC arrives. – Overlapping of the same communication with the same DC can be avoided if wait time during which DC leaves the communication area elapses after the end of communication.
– Keep transportation speed constant. – Valid only for systems where communication is not made more than once with same DC. – Make sure that another DC does not pass through the area.
– For example, auto command is transmitted after end of processing of preceding process is confirmed. – Trigger must be input before the next DC approaches.
– Trigger processing is necessary. – Make sure that the trigger is accurately input.
Communications Connector Plug XM2A-0901
72
Hood XM2S-0911
Type Solder
Maker OMRON
Page 80
Appendix C Specifications and Ratings General Ratings and Characteristics Ratings Supply voltage
24 VDC
Operating voltage range
20.4 to 26.4 VDC (24 +15%/–15% VDC)
Power consumption
7.2 W max. (24 V, 0.3 A)
Insulation resistance
50 MΩ min. (at 500 VDC) between: Power terminals and case I/O terminals and case Power terminals and I/O terminals
Dielectric strength
1,000 VAC 50/60 Hz for 1 minute. Leakage current: 10 mA max. for each of the above combinations. 1,500 Vp-p, pulse width: 100 ns to 1 µs, rise time: 1 ns (common mode noise) 600 Vp-p (normal mode noise) 10 to 150 Hz, 0.3 mm double amplitude for 32 minutes in X, Y, and Z directions.
Noise immunity Vibration
Mechanical durability Malfunction durability
10 to 150 Hz, 0.2 mm double amplitude for 32 minutes in X, Y, and Z directions.
Shock
200 m/s2, three times in X, Y, and Z directions.
Operating temperature
–10° to 55°C
Operating humidity
35% to 85% RH (without condensation)
Atmosphere
Must be free from corrosive gas.
Storage temperature
–25° to 65°C
Protection Class
Class I (with protective conductor terminal)
Protection rating
IEC60529: IP30 (panel mounting)
Approved standards
EN50081-2 (see note) EN50082-2 (see note) FCC Part 15 Subpart B
Pollution degree
2
Weight
360 g
Note For V600-CD1D-V3.
Characteristics Self-diagnosis function
CPU error, memory error, power failure, communications error check
73