Page 61

Section

Diagnostics

5-2

5-2

Diagnostics

Errors Errors that Stop Operation If a hardware error of the ID Controller has occurred, the STOP indicator lights, and RUN output is turned OFF. Errors that Allow Operation to Continue If an error has occurred during communications between the ID Controller and the host computer, or between the Controller and the R/W Head, the error code is displayed on the monitor (error code display mode). Up to 30 error codes are recorded and can be read by the host controller.

Indicators and Outputs Status

Test

RUN

Stop error Emergency stop

Indicator

Monitor

POWER

HEAD

STOP

Lower processing in progress

Lit

Lit

Not lit

---

Lower processing interval

Lit

Not lit

Not lit

Communication error occurrence

Lit

Not lit

Command reception wait Command processing in progress

Lit

Output RUN

End of processing

User 1

User 2

OFF

OFF

---

---

---

OFF

OFF

---

---

Not lit

Error code

OFF

OFF

---

---

Not lit

Not lit

---

ON

OFF

---

---

Lit

Lit

Not lit

---

ON

OFF

USR

USR

Communication error occurrence

Lit

Not lit

Not lit

Error code

ON

ON

---

---

CPU error

Lit

Not lit

Lit

92

OFF

OFF

---

---

Memory error

Lit

Not lit

Lit

93

OFF

OFF

External reset input ON

Lit

---

Lit

---

OFF

OFF

---

---

Note USR: Set by the controller control command.

52

Page 62

Section

Error Lists

5-3

5-3

Error Lists

Communication Error Location Host communication error

Error code 10

Parity error

11

Framing error

12 14

Overrun error Command input error

18

Frame length MAX error

Command or data length exceeding 266 characters.

70

Data carrier communication error

71

Unmatching error

Error during communication between R/W Head and DC. – Setting error such as passing speed and distance – Malfunctioning due to obstacle Read or write processing is not performed correctly.

72

Data carrier missing

7A

Address over

DC does not exist in specified area when write/read command is executed. Address exceeding memory area of DC is specified. When using MDS/MDL command, first address of the area is incorrectly specified.

7C

R/W head not connected

R/W Head is not connected.

7D

Write protect error

Production date area or write-protected area is specified for write command.

Lower communication error

Type

Note

Condition Error occurs during communication between host computer and ID Controller. – Incorrect setting of communication format – Malfunctioning due to noise Wrong command format.

1. The host communication error is an error that has occurred during communications between the host computer and ID Controller. 2. The lower communication error is an error that has occurred during communications between the ID Controller and R/W Head. These errors are all recorded in the ID Controller and their error codes and messages can be read using a command from the host computer. 3. These errors are all recorded in the ID Controller and their error codes can be read using a command from the host computer.

Warning Code Warning Code

Name

Meaning

7B

Data carrier battery low

The voltage of the Data Carrier’s built-in battery is low.

76

Excessive number of Data Carrier overwriting operations

76

Data Carrier memory check error

This warning will be returned when the data management command (MDS/MDL) is executed if the number of Data Carrier overwriting operations is 100,000 or over. This warning will be returned if a memory error is detected when the memory check command (MDC) is executed.

System Error Error code 92

Type CPU error

93

Memory error

Condition May be due to an ID Controller error or the influence of noise. Turn OFF power once and then turn it back ON again. Turn ON the reset input (if the error still persists, use the other ID Controller).

Note The system error (error that stops the operation) can be displayed on the monitor of the ID Controller but cannot be checked by the host computer.

53

Page 63

Section

Checking the Data Carrier Life

5-4

5-4

Checking the Data Carrier Life

5-4-1 SRAM-type Data Carrier Checking Battery Voltage Drop 1, 2, 3...

1. A voltage drop of the battery cannot always be checked but can be checked only when specific access is made.This is because, to check the battery voltage, a certain amount of current is temporarily allowed to flow through the internal circuit of the data carrier. If the battery voltage is checked each time the data carrier is accessed, the battery life is shortened. It is recommended that a routine that checks the battery once a day be incorporated in the system program. 2. Access to check battery voltage: The battery is checked only when the 2-byte data of addresses 0000 and 0001 are is read. <Battery voltage check command> a) Read command ... RD H 1 0000 02 b) Auto read command ... AR H 1 0000 02 c) Polling auto read ... PR H 1 0000 02 d) Expansion read command ... XR H 1000 02 3. Response when battery voltage drops: If the battery voltage has dropped, “7B” is returned as the end code of a response. Example: Normal state

RD 0 0 AR 0 0

0990* 0990*

Normal completion code

Read data Produced in Sept., 1990

When battery voltage drops

RD 7 B AR 7 B

0990* 0990*

Battery error code

Read data Produced in Sept., 1990

Battery Life of the Data Carrier After Battery Voltage Drop The Data Carrier can still be used for about 1 month under ordinary operating conditions, even if the voltage of the battery has dropped below the rated level. However, it is recommended that the Data Carrier be replaced with a new one as soon as possible. The battery-replaceable V600-D2KR16 can still be used for about 2 weeks under ordinary operating conditions, even if the voltage of the battery has dropped below the rated level. However, it is recommended that the battery be replaced with a new one as soon as possible. Note SRAM-type Data Carriers (excluding the V600-D2KR16) have a built-in thionyl chloride lithium battery. Due to the characteristics of thionyl chloride lithium batteries, the internal resistance of the battery increases when it is unused for several months. If the battery voltage drop is checked on a Data Carrier in this condition, a voltage drop will result even though the battery life is still satisfactory. This phenomenon is due to the increase in the internal resistance, and does not indicate that the battery life is over. Accordingly, if a Data Carrier is purchased and

54

Page 64

Section

Checking the Data Carrier Life

5-4 left unused for several months, activate the battery by performing a read operation for about 10 minutes. (Activating the battery in this way will run current through it, which will return the internal resistance to its normal state. This will have almost no effect on the battery life.)

5-4-2 EEPROM-type Data Carrier The MDL and MDS commands can be used to check whether or not the number of overwriting operations for the EEPROM in an EEPROM-type Data Carrier has exceeded the allowable number. The MDS command subtracts the number of overwriting operations from a userspecified management area and makes it possible to check whether or not the number of overwriting operations has exceeded a user-specified number. The MDL command adds the number of overwriting operations to a user-specified management area and makes it possible to check whether or not the number of overwriting operations has exceeded 100,000. This command is for EEPROM-type Data Carriers with a specification of 100,000 for the allowable number of overwriting operations. Note The MDS command can be used only with version 2.1 or later. Refer to ??? for details on the method used to check the version. Command Format M

D

S/L

1

X

X

X

X

X

X

∗

CR

Specify a hexadecimal value (00H, 01H, 02H,..., FBH) for the number of overwriting operations to be added or subtracted. First address specification to or to Read/Write head word (fixed to 1) Mode specification S: Subtraction method used. The allowable number of overwriting operations is specified by the user (16,700,000 max.) Note that the specification for the allowable number of overwriting operations for an EEPROM-type Data Carrier is 300,000 at temperatures of less than 40°C. L: Addition method used. When using this command, the allowable number of overwriting operations is 100,000.

Response Format M

D

7

∗

5

CR

End code 75: The number of overwriting operations has not exceeded the allowable number. 76: The number of overwriting operations has exceeded the allowable number.

Note

1. The first address must be to or to Do not specify to or to as the first address, otherwise address error code 7A (hexadecimal) will be returned. 2. The unit number is required for 1-to-n procedure. MDS Command The management area consists of three bytes beginning with the first address of

55

Page 65

Section

Checking the Data Carrier Life

5-4 the area. When the MDS command is executed, the specified number of overwriting operations is subtracted from the present number and the result is written to this area. If it is 0 (00H), end code 76 will be returned as a warning. It is necessary to specify the allowable number of overwriting operations beforehand. This can, in theory, be set to any number up to 16,700,000 but the specification for the allowable number of overwriting operations for an EEPROM-type Data Carrier at temperatures of less than 40°C is 300,000 (0493E0H) so set to a number less than this. The number of overwriting operations up to the present time is written in the management area as hexadecimal data. The data can also be read using the read command. If the number of overwriting operations in the management area is already 0, the hexadecimal data value will not be renewed. In this case, only the warning will be returned when the MDS command is executed. If the MDS command is executed with 00H, nothing will be written to the hexadecimal data but the number of overwriting operations up to the present time can be checked.

First address of the area

Leftmost digit Middle digit

Three bytes

Rightmost digit

MDS Command Execution Example 1, 2, 3...

In the following example, three bytes beginning with address 0010H are specified as the management area for overwriting operations. 1. Input 300,000 overwriting operations with WTH100100493E0.

0010H

04H

0011H

93H

0012H

E0H

2. Input 5 overwriting operations with MDS1001005.

0010H

04H

0011H

93H

0012H

DBH

3. The following indicates that the number of overwriting operations is 300,000. MD76 will be returned to indicate an excessive number of overwriting operations if MDS1001000 is executed.

0010H

00H

0011H

00H

0012H

00H

Note Do not use MDS and MDL commands together in a Data Carrier. Doing so would disable lifetime management.

56

Page 66

Section

Checking the Data Carrier Life

5-4

MDL Command The management area consists of three bytes beginning with the first address of the area. When the MDL command is executed, the specified number of overwriting operations is added from the present number and the result is written to this area. If it is 100,000 (0186A0H) or over, end code 76 will be returned as a warning. The number of overwriting operations up to the present time is written in the management area as hexadecimal data. The data can also be read using the read command. If the number of overwriting operations in the management area is already 100,000 or over, the hexadecimal data value will not be renewed. In this case, only the warning will be returned when the MDL command is executed. If the MDL command is executed with 00H, nothing will be written to the hexadecimal data but the number of overwriting operations up to the present time can be checked.

First address of the area

Leftmost digit Middle digit

Three bytes

Rightmost digit

MDL Command Execution Example 1, 2, 3...

In the following example, three bytes beginning with address 0010H are specified as the management area for overwriting operations. 1. Clear the management area first with WTH10010000000.

0010H

00H

0011H

00H

0012H

00H

2. Input 4 overwriting operations with MDL1001004.

0010H

00H

0011H

00H

0012H

04H

3. Input 5 as the next number of overwriting operations with MDL1001005 make the total overwriting operations 9.

0010H

00H

0011H

00H

0012H

09H

4. The following indicates that the number of overwriting operations is 100,000. MD76 will be returned to indicate that an excessive number of overwriting operations will result if MDL1001000 is executed.

57

Page 67

Section

Checking Function of the Data Carrier’s Memory

5-5

0010H

01H

0011H

86H

0012H

A0H

5-5

Checking Function of the Data Carrier’s Memory A Data Carrier memory check is possible by executing the data check command MD. CRC (Cyclic Redundancy Check) code calculation, data writing, and data collation are possible in a check block specified by the user. A CRC code is calculated with the generating function X16 + X12 + X5 +1.

Command Format

M

D

C/K

1

X

X

Processing specification (C: Collation; K: Calculation)

X

X

X

X

∗

CR

Specify a hexadecimal value (03H, 04H,..., FEH, FFH, 00H) for the number of overwriting operations to be added. 00H means 256 bytes.

Read/Write head word (fixed to 1) Check block first address (0000H to FFFDH)

Response Format

M

D

0

0

∗

CR

Note:

The unit number is required for 1-to-n procedure(s).

End code 00: Normal completion (at the time of calculation processing only) 75: Normal data (at the time of collation processing only) 76: Data abnormal warning (at the time of collation processing only)

In each check block consisting of the first address and the number of bytes specified by the user, the area excluding the last two bytes is the calculation area and the last two-byte area is the check code area of the check block. If check code write processing is specified with processing code K, the CRC of the data in the calculation area is calculated and the result is written to the check code area. If data collation is specified with processing code C, the CRC of the data in the calculation area is calculated and the result is compared with the data in the check code area. If the result coincides with the data in the check code area, end code 75 will be returned. If they do not coincide with each other, end code 76 will be returned as a warning.

58

Page 68

Section

Checking Function of the Data Carrier’s Memory

5-5

Address 0000H 0001H

First address of the area

Check code calculation area (the number of check block bytes less two bytes)

The number of check block bytes

CRC (right digit) CRC (left digit)

Data Carrier Memory Check Command Example

Check code area (two bytes)

In the following example, the data in addresses 0010H to 0012H are checked on condition that the following data exists in these addresses.

0010H

12H

0011H

34H

0012H

56H

0013H 0014H

1, 2, 3...

1. Execute MDK1001005 (calculation processing) so that the CRC code (5CD6H) of the data “123456” is written to addresses 0013H and 0014H.

0010H

12H

0011H

34H

0012H

56H

0013H

5CH

0014H

D6H

2. Execute MDC1001005 (collation processing). If the result coincides with the data in the check code area, MD75 will be returned as a normal response.

59

Page 69

Section

Checking Function of the Data Carrier’s Memory

0010H

12H

0011H

34H

0012H

56H

0013H

5CH

0014H

D6H

5-5

3. If the result does not coincide with the data in the check code area, MD76 will be returned as a warning.

60

Page 70

Section

Troubleshooting

5-6

5-6

Troubleshooting The following are the major causes of ID Controller malfunctioning: Cause

Measures

Influence of noise Malfunctioning of external devices Malfunctioning of ID Controller Others

Take countermeasures against noise. Repair is needed.

Influence of Noise If the system malfunctions due to noise, take appropriate countermeasures against noise by referring to the following table: 1

No.

Occurrence On power application to motor, transformer, or capacitor.

2

Irregular.

3

Input signal turns ON when it should be OFF.

Possible cause

Countermeasures

Momentary voltage drop due to inrush current of large load. Common mode noise due to the above.

Increase the capacity of the power supply facility or use larger power cables. Supply power through 1:1 non-grounded insulated transformer. Do not share the ground lines with other high-capacity loads. Independently ground at less than 100 Ω.

Noise superimposed on power lines. Inductive noise of input wiring.

Supply power through 1:1 non-grounded insulated transformer or noise filter. Separate input signal lines from other power lines. If the influence of noise is high, route input lines using a grounded metal conduit or use shielded cables.

(1) Improvement of grounding Other equipment

Other equipment ID Controller

ID Controller Grounding at 100 Ω

(2) Countermeasures against noise ID Controller

Power supply Noise filter

Use twisted pair cables. Do not route the cables in parallel with power lines.

61