Page 31
..... Ts = the stop time of the press (or machine) in seconds, measured from the final de-energized control element. Measured at maximum closing velocity. Tc = the response time, in seconds, of the press or machine control circuit to activate the machine’s brake. NOTE! Ts + Tc is usually measured together by a stop time measuring device.
Tr = the response time of the 4700 system, in seconds. This response time is given in Table 14-1, Table 14-2 and Table 14-3. WARNING! When using a STI RM-1 with the 4700, add 0.008 seconds to the response ! ▲ times stated in Table 14-1, Table 14-2 and Table 14-3.
Tbm = the additional stopping time, in seconds, allowed by the brake performance monitor before it detects stop time deterioration. The Tbm factor allows consideration for brake wear, adding extra stop time allowed by the brake monitor. Therefore, Tbm = Brake monitor set point - (Ts + Tc). NOTE! If the guarded machine is not equipped with a stop time performance monitor, a percentage increase factor should be applied to the stop time of the machine to allow for braking system wear. Contact your machine manufacturer for information.
Dpf = This is related to the minimum object sensitivity of the 4700 system. By knowing the minimum object sensitivity, S, of the 4700 system, Dpf is read directly from Table 5-5, Table 5-6, Table 5-7 or Table 5-8. For a 4700 system with 12 mm minimum object resolution and without Exact Channel Select or Floating Blanking active: S = 0.47 inches (12 mm) and Dpf = 0.67 inches (16.96 mm) For a 4700 system with 20 mm minimum object resolution and without Exact Channel Select or Floating Blanking active: S = 0.79 inches (20 mm) and Dpf = 1.75 inches (44.45 mm)
8.2 E U R O P E A N S A F E T Y D I S T A N C E F O R M U L A S The following discussion is based on standard EN999 and applies to light curtains used in industrial environments. 8.2.1
S AFETY D ISTANCE F ORMULA FOR S YSTEMS WITH A M INIMUM O BJECT R ESOLUTION OF 40 MM OR L ESS
When the minimum object resolution of the system is 40 mm or less, use the following formula: S = (K x T) + C where: S = the minimum distance in millimeters, from the danger zone to the detection point, line, plane or zone. K = 2000 mm/s T = the overall system stopping performance in seconds. T = t 1 + t2 t1 = response time of the safety light curtain in seconds. This response time is given in Table 14-1, Table 14-2 and Table 14-3.
R
SCIENTIFIC TECHNOLOGIES INC. Fremont CA USA Tel: 1/888/510-4357 in USA and Canada
© STI 0806 PN99584-0050 Rev.D
29
Page 32
8 t2 = maximum stopping time of the machine in seconds. C = 8(d-14 mm), but not less than zero. d = the minimum object detection of the 4700 in millimeters. i.e.: S = (2000 mm/s x T) + 8(d – 14 mm) This formula applies for all minimum distances of S up to and including 500 mm. The minimum value of S shall not be less than 100 mm. If S is found to be greater than 500 mm using the formula above, then the formula below can be used. In this case the minimum value of S shall not be less than 500 mm. S = (1600 mm/s x T) + 8(d – 14 mm) 8.2.2
S AFETY D ISTANCE F ORMULA FOR S YSTEMS WITH A M INIMUM O BJECT R ESOLUTION G REATER T HAN 40 MM
When the minimum object resolution of the system is greater than 40 mm, use the following formula: S = (K x T) + C where: S = the minimum distance in millimeters, from the danger zone to the detection point, line, plane or zone. K = 1600 mm/s T = the overall system stopping performance in seconds. T = t 1 + t2 t1 = response time of the safety light curtain in seconds. This response time is given in Table 14-1, Table 14-2 and Table 14-3. t2 = maximum stopping time of the machine is seconds. C = 850 mm. i.e.: S = (1600 mm/s x T) + 850 mm 8.2.3
F ACTORS A FFECTING T HE S AFETY D ISTANCE F ORMULA
When light curtains are used for machine initiation, their minimum object resolution must be 30 mm or smaller (based on EN999, other standards may vary). In this case the formula given in 8.2.1 - Safety Distance Formula for Systems with a Minimum Object Resolution of 40 mm or Less applies except that the minimum distance S shall be greater than 150 mm. For parallel approach the formula C becomes: C = 1200mm – (0.4 x H), but not less than 850 mm. H = the height of the detection zone above the floor in mm.
R
SCIENTIFIC TECHNOLOGIES INC. Fremont CA USA Tel: 1/888/510-4357 in USA and Canada
© STI 0806 PN99584-0050 Rev. D
30
Page 33
.....
9
9 I NSTALLATION 9.1 R E F L E C T I V E S U R F A C E I N T E R F E R E N C E
A reflective surface adjacent to the detection zone can deflect the optical beam and may cause an obstruction in the zone not to be detected. (See Figure 9-2 and Figure 9-3.) The reflective surface may be part of the machine, mechanical guard or workpiece. Therefore, a minimum distance (d) must exist between the reflective object and the center line of the 4700 system detection zone. The Test Procedure (Appendix B) must be used to test for this condition. Operating Range, R Approach direction
Beam Angle, a Interruption a Light beam interrupted
Central beam
Receiver
Transmitter d
Reflective Surface Perimeter of danger area
Figure 9-1 Correct Mounting Example with Proper Alignment
The interruption is clearly detected. The reflective object is outside of the beam angle
Approach direction
Beam Angle, a
Interruption a
Light beam interrupted
Central beam Transmitter
Receiver d Reflection Reflective Surface Perimeter of danger area
Figure 9-2 Unsafe Mounting Example
The interruption is not detected because of the reflection. The reflective object is inside the beam angle.
R
SCIENTIFIC TECHNOLOGIES INC. Fremont CA USA Tel: 1/888/510-4357 in USA and Canada
© STI 0806 PN99584-0050 Rev.D
31
Page 34
9
Sensing Field
Interruption a Reflection
Transmitter
Receiver
Reflective Surface
Perimter of danger area
Figure 9-3 Unsafe Mounting Example
Interruption is not detected because of the reflection. Reflective surface interference may also appear above and below the sensing field.
Operating Range, R a Transmitter
Receiver a
Beam Angle, a d
Reflective Surface Perimeter of danger area
Figure 9-4 Worst Case Alignment Example
This example shows the minimum distance from the reflective surface, d, to one side of the beam center line.
1.3m
Minimum distance
1.1m
900
700 d(mm) 500
300
100 0 0.3m
2m
4m
6m
8m
10m
12m
14m
16m
18m
20m
Range (m)
Figure 9-5 Minimum Distance from a Reflective Surface as a Function of Range
R
SCIENTIFIC TECHNOLOGIES INC. Fremont CA USA Tel: 1/888/510-4357 in USA and Canada
© STI 0806 PN99584-0050 Rev. D
32
Page 35
..... 9.2. C O N N E C T I N G T R A N S M I T T E R A N D R E C E I V E R T O C O N T R O L L E R 9.2.1
C ABLE A SSEMBLIES
Receiver cable connectors are color-coded red and transmitter cable connectors are color-coded black. 9.2.2
C ABLE C ONNECTIONS
Transmitter and receiver connections are made at terminal positions 23 through 34. Insert and secure the appropriate color conductor in the numbered position. Positions 26, 27, and 28 accept identically colored conductors from both the transmitter and receiver. For ease of installation, the terminal block can be removed from the controller. See the table below for a color code/terminal number cross-reference. Table 9-1 Color Code/Terminal Number Cross Reference for DIN Controllers Terminal Number
Component
Conductor Color
23
Transmitter
Orange
24
Transmitter
Blue
25
Transmitter
Black
26
Transmitter and Receiver
Shield
27
Transmitter and Receiver
White
28
Transmitter and Receiver
Brown
29
Receiver
Pink
30
Receiver
Violet
31
Receiver
Gray
32
Receiver
Tan
33
Receiver
Yellow
34
Receiver
Red
Table 9-2 Color Code/Terminal Number Cross Reference Metal Chassis Controllers
R
TB5 Terminals
Component
Conductor Color
1
Receiver
White
2
Receiver
Brown
3
Receiver
Tan
4
Receiver
Yellow
5
Receiver
Red
6
Receiver
Grey
7
Receiver
Violet
8
Receiver
Pink
TB6 Terminals
Component
Conductor Color
1
Transmitter
White
2
Transmitter
Brown
3
Transmitter
Blue
4
Transmitter
Black
5
Transmitter
Orange
SCIENTIFIC TECHNOLOGIES INC. Fremont CA USA Tel: 1/888/510-4357 in USA and Canada
© STI 0806 PN99584-0050 Rev.D
33
Page 36
9
9.3 G E N E R A L C O N S I D E R A T I O N S 9.3.1
A DDITIONAL G UARDING
Areas of access to the point of hazardous operation not guarded by the 4700 system must be protected by suitable means such as a fixed barrier guard, an interlocked guard or a safety mat. See Figure 9-6.
Ds
LIGHT CURTAIN
Supplemental Guarding
Hazard Zone
Mechanical Barrier
Supplemental Guarding Example Supplemental Guarding
Supplemental Guarding
Supplemental Guarding
Figure 9-6 Correct Light Curtain Installation Examples
R
SCIENTIFIC TECHNOLOGIES INC. Fremont CA USA Tel: 1/888/510-4357 in USA and Canada
© STI 0806 PN99584-0050 Rev. D
34
Page 37
..... 9.3.2
I NSTALLATION OF M ULTIPLE S YSTEMS light curtains.
Transmitter
Receiver
PREFERRED INSTALLATION The receivers are mounted back to back.
Machine 2
Transmitter
Machine 1
Receiver
This arrangement may be subject to interference between the two
Machine 2
Receiver
Transmitter
Machine 1
NOT RECOMMENDED INSTALLATION
Receiver
Transmitter
Receiver
Transmitter
When two or more 4700 systems are mounted in close proximity and in alignment with each other, precautions should be taken to avoid one curtain interfering with another. This can be corrected by mounting the transmitters and receivers back-to-back or stacked. See Figure 9-7 for reference.
PREFERRED INSTALLATION An alternating receiver to
Receiver
Transmitter transmitter orientation is suggested.
Machine 1
Figure 9-7 Multiple Light Curtain Installation Configurations
Corner access and grey shaded area needs mechanical guarding.
Corner access and grey shaded area needs mechanical guarding.
Beam starts here
Beam starts here
Beam starts here
Corner access and grey shaded area needs mechanical guarding.
Corner access and grey shaded area needs mechanical guarding.
Beam starts here
STI recommends overlapping the light curtains in corder to have better coverage.
Figure 9-8 Mounting Orientation
R
SCIENTIFIC TECHNOLOGIES INC. Fremont CA USA Tel: 1/888/510-4357 in USA and Canada
© STI 0806 PN99584-0050 Rev.D
35
Page 38
9
9.3.3
D ETECTION Z ONE
The 4700 detection zone is delineated by the inside edge of the transmitter and receiver endcaps. The area outside these marks is not protected. Position the 4700 so that it is only possible to access the danger point through the detection zone. 9.3.4
M ARKING M INIMUM O BJECT R ESOLUTION
Serial number labels on the transmitter and receiver indicate three possible minimum object resolutions. During installation, use a permanent marker to obscure the object resolutions not set. This will depend on whether no floating blanking, 1-beam or 2-beam floating blanking is set. See Section 5.5 on page 23 for information. 9.3.5
A LIGNMENT
Physical alignment of the transmitter and receiver units is easiest when the 4700 system is in the automatic start operating mode with Exact Channel Select inactive. The units should be in the same plane and at equal height. The Individual Beam Indicators will light when a beam is out of alignment. See Section 6.2 - Individual Beam Indicators for details. 9.3.6
I NPUT P OWER R EQUIREMENTS /C ONNECTIONS
• DIN controller and DC metal chassis controller:
The 4700 system operates directly from 24 VDC ± 20%, 2.25A*. Power to the 4700 system must come from a dedicated power supply which must meet the requirements of IEC60204-1 and IEC 61496-1, STI part number 42992 or equivalent. The 4700 system internally generates voltages for its own use. No other devices should be connected to these voltages. *Internal consumption of power by the controller is less than 10 watts (415mA)
• AC metal chassis controller:
100 - 230 VAC @ 30 VA. 9.3.7
S PECIAL R EQUIREMENTS FOR P ERIMETER G UARDING
In perimeter guarding applications the 4700 detection zone is placed around the outside perimeter of a guarded machine or robot. This placement leaves space for personnel to stand between the detection zone and the hazardous machine. In this case, the guarded machine must only be restarted using a switch located outside and with a full view of the area of hazardous motion. Operation of the 4700 system in the start/restart interlock operating mode is suitable for perimeter guarding. 9.3.8
P RESENCE S ENSING D EVICE I NITIATION
Using the light curtain to initiate a machine after an object is removed from the sensing area is called Presence Sensing Device Initiation (PSDI). Use of PSDI places additional requirements on the guarding and safety controls. It can restrict advanced light curtain features such as Floating Blanking and Exact Channel Select. Contact STI for further information. Good sources of reference for PSDI include: ANSI RIA 15.06-1999, OSHA 1910.217(h), and ANSI B11.2-1995.
R
SCIENTIFIC TECHNOLOGIES INC. Fremont CA USA Tel: 1/888/510-4357 in USA and Canada
© STI 0806 PN99584-0050 Rev. D
36
Page 39
.....
10 C ONNECTING T O T HE M ACHINE C ONTROL C IRCUIT
10
10.1 D I N C O N T R O L L E R
! WARNING! This product is designed for use on a 24 VDC, negative ground (protective ▲ earth) electrical system only. Never connect the 4700 to a positive ground (protective earth) system. With a positive ground (protective earth) wiring scheme, certain simultaneous shorts of both safety outputs may not be detected and the guarded machine may not stop resulting is severe operator injury.
! WARNING! Never use only a single safety output to control the machine. Should this ▲ single output fail, the machine may not stop, resulting in severe operator injur y. The machine must be connected using both safety outputs.
R
SCIENTIFIC TECHNOLOGIES INC. Fremont CA USA Tel: 1/888/510-4357 in USA and Canada
© STI 0806 PN99584-0050 Rev.D
37
Page 40
10
10.1.1 C ONNECTING TO A S AFETY M ONITORING D EVICE
The wiring from the 4700 system to the machine control circuit must be control reliable as described in ANSI B11.19-1990. Normally PLCs are not designed to be control reliable. Safety devices, such as the 4700 system should not depend on a PLC to stop a guarded machine. However, safety related monitoring devices are now available. See Figure 10-1 for connection to such a device. Note that all safety inputs are directed to the monitoring device which also performs the MPCE monitoring function.
POWER SUPPLY 0 VDC
Receiver
EARTH
Transmitter
2.25A 24 VDC 54VA +24 VDC
1
0 VDC
2
34 33
TAN
32
4
GRAY
31
5
VIOLET
30
PINK
29
BROWN
28
WHITE
27
3
Must be accessible only by key.
RED YELLOW
+24VDC
6 PROGRAM 7
3 8
START
9
START RETURN MPCE RETURN
BLACK
25
MPCE
BLUE
24
ORANGE
23
10 11
26
12 13
CAN V+
14
DATA H
AUX 2 OUT AUX 1 OUT
15 16
DATA L
17
CAN V-
FB/CS
22
2
21
1
Auxiliary Output 1: NPN, 100 mA max., 30 VDC max.
2
Auxiliary Output 2: PNP, 500 mA max., Vsupply -2V
3
If remote START is not used, connect START output to START RETURN.
Arc Suppressor
OSSD 2
20
OSSD RTN
19
OSSD1
18
Interlock
1
LCM INPUT 1
Output 1
LCM INPUT 2
Output 2
MPCE 1 Arc Suppressor
Stop
MPCE 2
SAFETY INTERLOCK INPUTS
Run
OTHER SAFETY DEVICES
LCM Controller
MPCE 1 MPCE Monitoring
MPCE 2
Safety Monitoring Device
Figure 10-1 Connecting to a Safety Monitoring Device
R
SCIENTIFIC TECHNOLOGIES INC. Fremont CA USA Tel: 1/888/510-4357 in USA and Canada
© STI 0806 PN99584-0050 Rev. D
38