For the Omron MC4700
Page 41
..... 10.1.2 C ONNECTING V IA AN RM-1 M ODULE
The STI RM-1 Module provides force-guided relay outputs for machine control. (OSSD) Safety outputs 1 and 2 are connected to the RM-1 and provide the power necessary to energize its relays. See Figure 10-2 for the preferred connection method using the RM-1. The auxiliary non-safety output of the 4700 system can be used to signal light curtain status to a PLC.
POWER SUPPLY
Receiver
Transmitter
2.25A 24 VDC 54VA +24 VDC GROUND 0 VDC
1
0 VDC
2
34 33
TAN
32
4
GRAY
31
5
VIOLET
30
6
PINK
29
BROWN
28
WHITE
27
3
Must be accessible only by key.
RED YELLOW
+24VDC
7
4 8
START
9
START RETURN MPCE RETURN
BLACK
25
MPCE
BLUE
24
ORANGE
23
10 MPCE 1
MPCE 2
11
13 14
AUX 2 OUT AUX 1 OUT
CAN V+ DATA H
15 16 17
DATA L
2 3
26
12
3
1
FB/CS
CAN V-
22
2
21
1
OSSD 2
20
OSSD RTN
19
OSSD1
18
Interlock
4
Auxiliary Output 1: NPN, 100 mA max., 30 VDC max. Auxiliary Output 2: PNP, 500 mA max., Vsupply -2V MPCE sensing must be used with the RM1. The user can choose to monitor the MPCE contacts of the guarded machine directly or the safety relay outputs of the RM1. If remote START is not used, connect START output to START RETURN.
42 OSSD 1 41
Stop
32 OSSD 2
Run
31 24
0 VDC
Control Voltage
23 14
Monitor 13
Arc Suppressor MPCE 2 Arc Suppressor MPCE 1
RM1 MODULE
Figure 10-2 Connecting via an RM-1 Module
R
SCIENTIFIC TECHNOLOGIES INC. Fremont CA USA Tel: 1/888/510-4357 in USA and Canada
© STI 0806 PN99584-0050 Rev.D
39
Page 42
10
10.1.3 C ONNECTING V IA T WO F ORCE -G UIDED R ELAYS
FGR series relays provide force-guided relay outputs for machine control. See Figure 10-3 for the preferred connection method using two force-guided relays.
POWER SUPPLY
Receiver
Transmitter
2.25A 24 VDC 54VA +24 VDC EARTH 0 VDC
1
0 VDC
2
34 33
TAN
32
4
GRAY
31
5
VIOLET
30
6
PINK
29
BROWN
28
WHITE
27
3
Must be accessible only by key.
RED YELLOW
+24VDC
PROGRAM 7
4 8
START
9
START RETURN MPCE RETURN
BLACK
25
MPCE
BLUE
24
12
ORANGE
23
13
CAN V+
14
DATA H
AUX 2 OUT AUX 1 OUT
10
3
5
MPCE 1
11
15
17
DATA L
2 3
26
MPCE 2
16
1
FB/CS
CAN V-
5
22
2
21
1
OSSD 2
20
OSSD RTN
19
OSSD1
18
Interlock
4
6 Arc Suppressor MPCE 1
6
Auxiliary Output 1: NPN, 100 mA max., 30 VDC max. Auxiliary Output 2: PNP, 500 mA max., Vsupply -2V For the purpose of bench testing prior to installation, the user may select MPCE OFF. In this case, the MPCE input must be connected to MPCE RETURN. If remote START is not used, connect START output to START RETURN.
MPCE monitoring must be used when force-guided relays are used as the Final Switching Devices. Connect the MPCE output to MPCE RETURN through the NC contacts. The MPCE coils must be suppressed with the arc suppressor provided in the documentation kit.
6 Arc Suppressor
Stop
MPCE 2
Run
LCM Controller
Figure 10-3 Connecting Via Two Force-guided Relays
R
SCIENTIFIC TECHNOLOGIES INC. Fremont CA USA Tel: 1/888/510-4357 in USA and Canada
© STI 0806 PN99584-0050 Rev. D
40
Page 43
..... 10.2 M E T A L C H A S S I S C O N T R O L L E R S 10.2.1 C ONNECTING V IA T WO N ORMALLY O PEN R ELAY S AFETY O UTPUTS
See Figure 10-4 for the preferred connection diagram for a Two Normally Open contact arrangement control circuit.
Preferred Connection Diagram for Two Normally Open Contacts Terminals on Main Board Line / 24 VDC
TB1
Verify correct voltage requirement before applying power.
Neutral / 0 VDC
System control voltage Terminals on Relay Board TB2 arc suppressor
OSSD 1
MPCE 1
1
MPCE 1
MPCE 1 arc suppressor OSSD 2
1
Machine control contacts
MPCE 2
TB3
1 Auxiliary
2 Terminals on Main Board TB7
1 MCS 2 1
3
Sel 1 Sel 2 Must be accessible only by key.
Program 2
4
Notes: Arc suppression devices should only be installed across the coils of the machine control relays. Never install arc suppressors across the contacts of the safety light curtain. Failure of the arc suppressor in a short condition, across the contacts, will result in an unsafe condition. No external power is to be applied to terminals on TB7. The relay contacts on the MPCE1and MPCE2 must be force-guided contacts. To activate this function, Jumper 2 on the main board needs to be installed in the ON position. See Figure 3-5, item 22. A N.C. or N.O. Remote Start input is selectable; a momentary N.O contact is shown. The selection jumper, Jumper 1 is located under the lid. See Figure 3-5, item 19.
1 4
START 2
2 MPCE 1
MPCE 1
3
MPCE 2
Figure 10-4 Connecting with Two Normally Open Safety Outputs R
SCIENTIFIC TECHNOLOGIES INC. Fremont CA USA Tel: 1/888/510-4357 in USA and Canada
© STI 0806 PN99584-0050 Rev.D
41
Page 44
10
10.2.2 C ONNECTING V IA O NE N ORMALLY O PEN O NE N ORMALLY C LOSED S AFETY R ELAY O UTPUTS
See Figure 10-5 for preferred connection diagram for a One Normally Open, One Normally Closed contact arrangement control circuit.
Preferred Connection Diagram for One Normally Open, One Normally Closed Contacts Terminals on Main Board Line / 24 VDC TB1
Verify correct voltage requirement before applying power.
Neutral / 0 VDC
System control voltage Terminals on Relay Board arc suppressor
TB2
MPCE 1
OSSD 1
1 MPCE 1
MPCE 2 arc suppressor OSSD 2
1
Machine control contacts
MPCE 2
TB3
1 Auxiliary
2
No external power is to be applied to terminals on TB7.
3
The relay contacts on the MPCE1and MPCE2 must be force-guided contacts. To activate this function, Jumper 2 on the main board needs to be installed in the ON position. See Figure 3.5, item 22. A N.C. or N.O. Remote Start input is selectable; a momentary N.O contact is shown. The selection jumper, Jumper 1 is located under the lid. See Figure 3-5, item 19.
Terminals on Main Board TB7
1 MCS 2 1
Sel 1 Sel 2 Must be accessible only by key.
4
Program 2
Notes: Arc suppression devices should only be installed across the coils of the machine control relays. Never install arc suppressors across the contacts of the safety light curtain. Failure of the arc suppressor in a short condition, across the contacts, will result in an unsafe condition.
1 4
START 2
2 MPCE 1
MPCE 1
3
MPCE 2
Figure 10-5 Connecting with One Normally Open One Normally Closed Safety Outputs
R
SCIENTIFIC TECHNOLOGIES INC. Fremont CA USA Tel: 1/888/510-4357 in USA and Canada
© STI 0806 PN99584-0050 Rev. D
42
Page 45
..... 10.2.3 C ONNECTING S OLID S TATE S AFETY O UTPUTS TO T WO F ORCE -G UIDED R ELAYS
See Figure 10-6 for preferred connection diagram when connecting via Two FGR (force guided) relays. The FGR relays provide force-guided contacts for the machine control circuit.
Preferred Connection Diagram when Connecting Via Two Force-Guided Relays Terminals on Main Board TB1
+24 VDC 24VDC Supply Voltage 0 VDC
TVS TB4
1 MPCE 1
OSSD 1
MPCE 1
MPCE 2
Return TVS
Machine control contacts 1
MPCE 2
OSSD 2 Return
NPN Aux. 1
1
Notes: Suppression devices should be installed across the coils of the machine control relays. Two diode type devices are supplied in the documentation kit.
2
No external power is to be applied to terminals on TB 7 and TB8.
Aux. +24V 5 PNP Aux. 2 3
The relay contacts on the MPCE1and MPCE2 must be force-guided contacts. To activate this function pos. 3 on SWA & SWB must be active. A jumper is needed when MPCE is inactive. See figure 3-5, item 14 and 16.
4
A N.C. or N.O. Remote Start input is selectable, a momentary N.O contact is shown. The selection jumper, Jumper 1, is located on the User control board. See figure 3-5, Item 19.
5
Aux. Outputs may also connect to PLC.
Return
Terminals on Main Board TB7
1 MCS 2
Sel 1 Sel 2 Must be accessible only by key.
1 Program 2 1 4
START 2
2 MPCE 1
MPCE 1
3
MPCE 2
Figure 10-6 Connecting with Two Force Guided Relay Outputs
R
SCIENTIFIC TECHNOLOGIES INC. Fremont CA USA Tel: 1/888/510-4357 in USA and Canada
© STI 0806 PN99584-0050 Rev.D
43
Page 46
10
10.2.4 C ONNECTING V IA A S AFETY M ONITORING D EVICE
See Figure 10-7 for preferred connection diagram when connecting via a safety monitoring device. Note that all safety devices are inputs to the Safety Monitoring Device, which performs the MPCE monitoring function. NOTE: Normally PLCs are not control reliable, however Safety rated PLCs and monitoring devices are now available. Preferred Connection Diagram when Connecting Via a Safety Monitoring Device Terminals on Main Board TB1
+24 VDC
24VDC Supply Voltage
0 VDC SAFETY MONITORING DEVICE
Suppressor 4
TB4
Output 1
OSSD 1
OSSD 1
MPCE1 Suppressor
Return
4 Output 2
MPCE2
OSSD 2
OSSD 2 Return
Safety Interlocks input
NPN Aux. 1
MPCE 1 MPCE MONITORING
Safety Mats input
Aux. +24V 1
Other Safety Devices
PNP Aux. 2
3
MPCE 2
MPCE 1
MPCE 2
Return
Terminals on Main Board TB7
1 MCS 2 1
Machine control contacts
Sel 1 Sel 2
Notes: 1
Auxilary outputs may also connect to PLC (optional).
2
No external power is to be applied to terminals on TB 7 & 8.
3
The relay contacts on the MPCE1and MPCE2 must be forced guilded contacts. The Safety Monitoring Device Must Monitor the MPCE's Normally Closed Contacts.
4
Suppression devices should be installed across the coils of the machine control relays. Two diode type devices are supplied in the Documentation Kit.
5
A N.C. or N.O. Remote Start input is selectable; a momentary N.O contact is shown. The Selection jumper, Jumper1, is located on the User control board.
6
When MPCE is Inactive, a jumper is needed.
Must be accessible only by key.
Program 2 1 5
START 2
MPCE
2
6
Figure 10-7 Connecting with Safety Monitoring Device
R
SCIENTIFIC TECHNOLOGIES INC. Fremont CA USA Tel: 1/888/510-4357 in USA and Canada
© STI 0806 PN99584-0050 Rev. D
44
Page 47
.....
11 C HECKOUT AND T EST P ROCEDURES
11
11.1 C H E C K O U T P R O C E D U R E Once the 4700 system has been configured, mounted, aligned and properly connected to the machine control system, the initial Checkout Procedure detailed in Appendix A must be performed by qualified personnel. A copy of the checkout results should be kept with the machine records.
11.2 T E S T P R O C E D U R E
! WARNING! The tests outlined in the Test Procedure in Appendix B must be performed ▲ at installation, according to the employer’s regular inspection program and after any maintenance, tooling change, set up, adjustment, or modification to the 4700 system or the guarded machine. Where a guarded machine is used by multiple operators or shifts, it is suggested that the test procedure be performed at each shift or operation change. Testing ensures that the light curtain and the machine control system work properly to stop the machine. Failure to test properly could result in serious injury to personnel.
The Test Procedure must be performed by qualified personnel. To test the 4700 system without Exact Channel Select and Floating Blanking disabled, use the STI-supplied test object. For applications where Exact Channel Select or Floating Blanking are enabled, see Table 5-5, Table 5-6, Table 5-7 and Table 5-8 to determine the proper size test object. When using a 4700 system for Automatic Start Mode operation, in conjunction with an RM-1 relay module, it is necessary to verify that the RM-1 outputs can properly change state by causing an intentional beam break at least every change of shift or 24 hours of operation.
11.3 U S I N G T H E T E S T O B J E C T
ST AR T ST OP
MicroSafe MC4700
MicroSafe MC4700
When using the test object, guide it through the detection zone as shown below. Pay particular attention to areas which may be affected by Exact Channel Select. If Floating Blanking is active, use a proper size test object.
Figure 11-1 Test Object Pattern
R
SCIENTIFIC TECHNOLOGIES INC. Fremont CA USA Tel: 1/888/510-4357 in USA and Canada
© STI 0806 PN99584-0050 Rev.D
45
Page 48
12
11.4 T E S T C O N S I D E R A T I O N S W H E N U S I N G E X A C T C H A N N E L S E L E C T O R FLOATING BLANKING !! Warning! Use of Exact channel Select and/or Floating Blanking will make the 4700 system less ▲ sensitive to objects in the detection zone. Improper use of either can result in severe injury to personnel. Exact Channel Select may require a hard barrier guard (see section 5.8), Floating Blanking requires an increase in the safety distance. Read section 5 carefully. When Exact Channel Select and/or Floating Blanking are active the user must verify that the detection zone is being used as intended, including the size and location of the selected/blanked beams. Check for the following condition: 1. That unauthorized modification of the detection zone is not possible. The controller should be installed in an enclosure with supervisor-controlled access. 2. That the area selected by Exact Channel Select is: a. Completely blocked by an obstruction; or b. that those areas not blocked by an obstruction are protected by supplemental guarding. If neither of these conditions can be met, the safe mounting distance of the 4700 system should be modified in accordance with the safe mounting distance formulas presented in Section 8 - Safe Mounting Distance. 3. Using a proper size test object and the method described in Section 11.3 - Using the Test Object, check those areas which have not been programmed by Exact Channel Select. Be sure that they have not been accidientally selected as well.
12
12 T ROUBLESHOOTING
The controller contains a two-digit diagnostic display, which presents numeric codes indicating both normal operation and system fault status. The operational codes are described in the table below. Table 12-1 Operational Codes
R
Code Displayed
System Status
Corrective Action
88
Power-up indication.
None required.
00
Normal operation; no floating blanking or exact channel select.
None required.
01
Normal operation; waiting for start signal.
Press and release start switch.
02
Normal operation; floating blanking active.
None required.
03
Normal operation; exact channel select active.
None required.
04
Normal operation: floating blanking and exact channel select active.
None required.
SCIENTIFIC TECHNOLOGIES INC. Fremont CA USA Tel: 1/888/510-4357 in USA and Canada
© STI 0806 PN99584-0050 Rev. D
46
Page 49
..... Table 12-2 DIP Switch Fault Codes Code Displayed
System Status
Corrective Action
20
Incorrect operating mode or floating blanking switch setting.
1. Check setting of operating mode switches 1 and 2. 2. Check setting of floating blanking switches 5 and 6.
21
Invalid switch setting.
1. Check to see that settings of switch positions 1 through 7 are valid and identically set between switches A and B.
22
DIP switch settings changed during operation.
1. Press and release start switch or cycle power.
23
Invalid switch settings.
1. Check channel select and MPCE switches for valid settings.
Table 12-3 Safety Output (OSSD) Faults Code Displayed
System Status
Possible Cause/Corrective Action
30
General safety output (OSSD) fault.
1. OSSD A shorted to OSSD B. Check wiring. Wiring according to manual. 2. OSSD A or OSSD B shorted to power. Check wiring. Wire according to manual. 3. OSSD A or OSSD B shorted to ground. Check wiring. Wire according to manual.
Table 12-4 MPCE Faults
R
Code Displayed
System Status
Corrective Action
40
General MPCE fault.
1. Possible incorrectly wired MPCE circuit. Check and wire according to manual.
41
MPCE Open before safety output (OSSD) activation.
1. Check to confirm that MPCE circuit is closed before OSSD activation.
43
MPCE open when power is applied.
1. Check to confirm that MPCE circuit is closed when power is applied.
SCIENTIFIC TECHNOLOGIES INC. Fremont CA USA Tel: 1/888/510-4357 in USA and Canada
© STI 0806 PN99584-0050 Rev.D
47
Page 50
13
Table 12-5 Controller Faults Code Displayed
System Status
50
Internal controller fault.
Corrective Action
1. Return controller to STI for repair.
51
Receiver fault.
1. Check receiver to controller wiring connections. Correct errors. 2. Check receiver cable for cuts, and proper connection to quick-disconnect fitting. Replace or properly connect cable as required. 3. If none of the above, return receiver to STI for repair.
52
Transmitter fault.
1. Check transmitter to controller wiring connections. Correct errors. 2. Check transmitter cable for cuts, and proper connection to quick-disconnect fitting. Replace or properly connect cable as required. 3. If none of the above, return transmitter to STI for repair.
53
Transmitter and receiver length mismatch or transmitter and receiver not connected.
1. Check to determine that transmitter and receiver are identical in protected height. 2. Check to determine that transmitter and receiver are properly connected to controller and that their cables are not damaged.
59
24 VDC power supply fault.
1. Check voltage supplied to unit. Correct so that it is 24 VDC ± 20%.
70
Grounding/Shielding Fault
1. Check the controller is properly grounded. 2. Check to see that the transmitter and receiver shield is connected properly. 3. Check for cross-talk from other I.R. light source.
13
13 C LEANING
Accumulation of oil, dirt and grease on the front filter of the 4700 transmitter and receiver can effect the system operation. Clean filters with a mild detergent or glass cleaner. Use a clean, soft, lint-free cloth. Painted 4700 surfaces may be cleaned with a mild de-greasing cleaner or detergent.