Chapter 6 – RSNetworx Configuration Example This chapter shows how to set up configure a CDN066 gateway using the Rockwell Software RSNetworx software and your gateway’s Electronic Data Sheet (EDS) file. The system configuration uses an Allen-Bradley 1770-KFD DeviceNet adapter (MAC ID 62) to connect the PC running RSNetworx to the DeviceNet network. A SLC500 system with a 1747-SDN DeviceNet Scanner (MAC ID 00) is the DeviceNet master. CDN066 gateway has MAC ID 03. Allen Bradley SLC500 4 Slot Rack, 1746-A4 L
N 120VAC Input
Fuse 3A
Power Sup.
Slot 0
Slot 1
Slot 2
Slot 3
24vdc output
SLC502
DeviceNet
8 pt. Input
8 pt.Output
1747-P1 120/240VAC
PLC CPU
Scanner module module
1747-L524
1747-SDN
1746-IV8
1746-OB8
Comm.
Comm.
Neutral GND
DeviceNet network 24VDC Power Supply
Fuse 1A
Fuse 6A
+ 24VDC
-to pin 1 DeviceNet connector
GND
PC Interface To PC RS232 25
Module
Pin Serial Interface
1747-PIC
For Used with
RS232-PLC
RSLogic Prog.
RS232 serial communication To PC RS232 9 pin to pin 5 DeviceNet connector
120VAC
PS to DeviceNet Dist. Pin
Color
Description
1 black
BUS-
3 clear
Shield (Drain)
5 red
BUS+ (24vdc)
(0vdc)
PC Interface Mod.
Serial Interface For
1770-KFD
DIP790 Device
Used with RSLinx,
RS232-DeviceNet
Net Dist. Board
& RSNetWorx Prog.
Terminal Connector
DeviceNet 9 pin DIN RS232 Serial
Gateway Module
Pin
Color
Interface to Barcode
CDN066
1 black
V- (BUS-)
Reader, Scanner
RS232-DeviceNet
2 blue data low (CAN L)
3 clear shield (Drain)
4 white data high (CAN H)
5 red
V+ (BUS+)
Weigh Scale or etc.
RS232 Pin Layout
Description
Pin
Func. Pin Func.
DeviceNet Male Connector
Pin
Color
Description
2
RXD
7
RTS
4
1 clear shield (Drain)
3
TXD
8
CTS
2 red
V+ (BUS+)
5
GND
3 black
V- (BUS-)
4 white data high (CAN H)
5 blue data low (CAN L)
Pin 1,4,6,9 are unused
3 5
1
2
DeviceNet Connector
Figure 1. CDN066 Integrated with Allen Bradley SLC500
MKS Instruments, Inc.
D.I.P. Products Group
37
Page 38
CDN060 User Manual revision 1.00
Configure DeviceNet Interface Follow instructions in Chapter 4 to set the gateway’s rotary switches to 125Kbps baud rate and MAC ID to 03. Set the RS232 Baud Rate switch to PRG mode. Connect the gateway to the DeviceNet network to power it up. During power-up, the NET and MOD LEDs cycle through a sequence of alternating red and green. After power-up, the NET LED should be flashing green and the MOD LED should be solid green. Connect & Register EDS File 1) Start up the RSNetworx program. Select the Online operation from the Network menu.
MKS Instruments, Inc.
D.I.P. Products Group
38
Page 39
CDN060 User Manual revision 1.00
2) The following text box should pop up, showing the networks connected to your computer.
3) Click on the 1770-KFD-1 + to show all connected DeviceNet devices. The gateway is at MAC ID 03, verifying its DeviceNet connection. It is an Unrecognized Device until the gateway’s EDS file is registered with RSNetworx.
MKS Instruments, Inc.
D.I.P. Products Group
39
Page 40
CDN060 User Manual revision 1.00
4) Click Cancel to close Browse for network window. Select the EDS Wizard… operation from the Tools menu. Click Next> to continue.
5) Select the Register an EDS file(s) option and click Next>.
MKS Instruments, Inc.
D.I.P. Products Group
40
Page 41
CDN060 User Manual revision 1.00
6) Select Register a single file option. Browse for your gateway’s EDS file. You can download the latest EDS and ICON files from the www.mksinst.com website. Click Next> when you have the correct path and EDS file name in the Named: box.
7) The next screen shows the RSNetworx installation test results. Click View file… to view the actual EDS file text. Click Next> to continue.
MKS Instruments, Inc.
D.I.P. Products Group
41
Page 42
CDN060 User Manual revision 1.00
8) The next screen allows you to customize the gateway’s icon for RSNetworx. Click on Change icon…
9) The Change Icon screen pops up. Click Browse to enter path for CDN066 icon file. You can download the icon file from www.mksinst.com.
10) Enter the path to CDN066 icon file in the File name: box. Click Open to continue. MKS Instruments, Inc.
D.I.P. Products Group
42
Page 43
CDN060 User Manual revision 1.00
11) The CDN066 icon should have changed to the proper icon. Click Next to continue.
MKS Instruments, Inc.
D.I.P. Products Group
43
Page 44
CDN060 User Manual revision 1.00
12) The final step is to finish EDS file registration. Click Next> to complete the registration process. Click Finish to close the EDS Wizard window.
MKS Instruments, Inc.
D.I.P. Products Group
44
Page 45
CDN060 User Manual revision 1.00
13) Repeat steps 1, 2, and 3 to browse the DeviceNet network. RSNetworx should now recognize the device at MAC ID 03 as a CDN066 gateway, and display the CDN066 icon. Click Cancel when finished.
MKS Instruments, Inc.
D.I.P. Products Group
45