Page 28

CDN060 User Manual revision 1.00

Chapter 5 – DeviceNet Specifications This chapter describes the CDN060 gateway DeviceNet specifications. DeviceNet Message Types The CDN060 is a Group 2 Slave Device that supports the following message types. CAN IDENTIFIER 10xxxxxx111 10xxxxxx110 10xxxxxx101 10xxxxxx100 xxxxxx = CDN060 MAC ID

GROUP 2 MESSAGE TYPE Duplicate MAC ID Check Message Unconnected Explicit Request Message Master I/O Poll Command Message Master Explicit Request Message

DeviceNet Class Services The CDN060 is a Group 2 Slave Device that supports the following class services and instance services. SERVICE CODE 05 (0x05) 14 (0x0E) 16 (0x10) 75 (0x4B) 76 (0x4C)

SERVICE NAME Reset Get Attribute Single Set Attribute Single Allocate Group 2 Identifier Set Release Group 2 Identifier Set

DeviceNet Object Classes The CDN066 device supports the following DeviceNet object classes. CLASS CODE 01 (0x01) 02 (0x02) 03 (0x03) 04 (0x04) 05 (0x05) 64 (0x40)

MKS Instruments, Inc.

OBJECT TYPE Identity Router DeviceNet Assembly Connection Serial Stream Object

D.I.P. Products Group

28

Page 29

CDN060 User Manual revision 1.00

IDENTITY OBJECT The Identity Object is required on all DeviceNet devices. It provides product identification and general information. Identity Object Class Access Attribute 1 Get 2 Get 6 Get 7 Get Instance Access Attribute 1 Get 2 Get 3 Get 4 Get

5

Get

6 7

Get Get

Class Code 01 (0x01) Name

Type

Value

Revision Max Object Instance Max Class Identifier Max Instance Attribute Name

UINT UINT UINT UINT Type

1 1 7 7 Value

Vendor Product Type Product Code Revision Major Revision Minor Revision Device Status

UINT UINT UINT STRUCT of USINT USINT WORD

59 = D.I.P. Products 12 = Communications 1

Serial Number Product Name Length Name

UDINT STRUCT of USINT STRING [6]

4 0 Bit 0 = owned (0 available, 1 allocated) Bit 2 = configured (0 no, 1 yes) Bit 4-7 = vendor specific (0) Bit 8 = minor configuration fault Bit 9 = minor device fault Bit 10 = major configuration fault Bit 11 = major device fault Bit 1, 3, 12-15 = reserved (0) Unique serial number for every device 6 CDN06x

Common Services Service Code 05 (0x05) 14 (0x0E)

Class No Yes

MKS Instruments, Inc.

Instance Yes Yes

Service Name Reset Get_Attribute_Single

D.I.P. Products Group

29

Page 30

CDN060 User Manual revision 1.00

ROUTER OBJECT The Message Router Object provides a messaging connection point through which a Client may address a service to any object class or instance residing in the CDN060 device. Router Object Class Access Attribute 1 Get 6 Get 7 Get Instance Access Attribute 2 Get

Class Code 02 (0x02) Name

Type

Value

Revision Max Class Identifier Max Instance Attribute Name

UINT UINT UINT Type

1 7 2 Value

Number of Connections UINT

2

Common Services Service Code 14 (0x0E)

Class Yes

MKS Instruments, Inc.

Instance Yes

Service Name Get_Attribute_Single

D.I.P. Products Group

30

Page 31

CDN060 User Manual revision 1.00

DEVICENET OBJECT The DeviceNet Object contains information about the CDN060 DeviceNet interface configuration. DeviceNet Object Class Access Attribute 1 Get Instance Access Attribute 1 Get/Set

Class Code 03 (0x03) Name

Type

Value

Revision Name

UINT Type

2 Value

MAC ID

USINT

Settable only if MAC ID switches > 63. Valid numbers are 0 to 63. Returns last value set or switch value.

2

Get/Set Baud Rate

USINT

Settable only if Baud switch > 2. Valid settings are 0 = 125K, 1 = 250K, 2 = 500K. Returns last value set or switch value.

3

Get/Set Bus Off Interrupt

BOOL

4

Get/Set Bus Off Counter

USINT

0 = hold CAN in OFF state (default) 1 = reset CAN Writing this attribute forces counter value to zero.

5

Get

Allocation Information Choice Byte

STRUCT of BYTE

Master Node Address

USINT bit 0 = explicit msg, set to 1 to allocate bit 1 = polled IO, set to 1 to allocate bit 2 = strobed IO, not supported bits 3-7 = reserved, set to 0 Allocated to this DeviceNet master

Common Services Service Code 14 (0x0E) 16 (0x10) 75 (0x4B) 76 (0x4C)

Class Yes No No No

MKS Instruments, Inc.

Instance Yes Yes Yes Yes

Service Name Get_Attribute_Single Set_Attribute_Single Allocate Master/Slave Release Master/Slave

D.I.P. Products Group

31

Page 32

CDN060 User Manual revision 1.00

ASSEMBLY OBJECT The Assembly Object instances bind attributes of multiple objects to allow data to or from each object to be sent or received over a single connection. Assembly Object Class Access Attribute 1 Get 2 Get Instance Access Attribute 3 Get

Class Code 04 (0x04) Name

Type

Value

Revision Max Class ID Name

UINT UINT Type

2 2 Value

Data Stream note 1

Instance 1 for input data stream. Instance 2 for output data stream.

Common Services Service Code 14 (0x0E) 16 (0x10)

Class Yes No

Instance Yes Yes

Service Name Get_Attribute_Single Set_Attribute_Single

Instance 1 Input Data Stream and Instance 2 Output Data Stream are structured as either an array of bytes or as a Short_String consisting of a single byte length field and N data bytes. The Input Data Stream is the data returned in the Poll Response Message. The Output Data Stream is the data returned in the Poll Command Message. See Chapter 3 for a complete description of the the Poll Format. Poll Response: [Status byte][Receive Sequence Number byte][Short_String Length byte][RX data bytes] Poll Command: [Status Clear byte][Transmit Sequence Number byte][Short_String Length byte][TX data bytes]

MKS Instruments, Inc.

D.I.P. Products Group

32

Page 33

CDN060 User Manual revision 1.00

CONNECTION OBJECT The Connection Object instances manage the characteristics of each communication connection. The CDN060 is a Group 2 Only Slave device that supports 1 Explicit Message Connection (Instance 1) and 1 Poll Message Connection (Instance 2). Connection Object Class Access Attribute 1 Get Instance Access Attribute 1 Get

Class Code 05 (0x05) Name

Type

Value

Revision Name

UINT Type

1 Value

State

USINT

0 = non-existent 1 = configuring 2 = established 3 = timed out

USINT

0 = Explicit Message 1 = I/O Message 0x83 for Explicit Message 0x82 for I/O Message Explicit Message: 10xxxxxx011 = produced connection id I/O Message: 01111xxxxxx = produced connection id Explicit Message: 10xxxxxx100 = consumed connection id I/O Message: 10xxxxxx101 = consumed connection id 0x21 for Explicit Message 0x01 for I/O Message 67 for Explicit Message See Stream Object for I/O Message 71 for Explicit Message See Stream Object for I/O Message Default 2500 msec 0 = Timeout (Explicit Message default) 1 = Auto Delete 2 = Auto Reset (I/O Message default) 0 for Explicit Message 6 for I/O Message Null for Explicit Message STRUCT for I/O Message 0x20 0x04 0x24 0x01 0x30 0x03 0 for Explicit Message 6 for I/O Message

2

Get

Instance Type

3

Get

Transport Class Trigger USINT

4

Get

Production Connection

UINT

5

Get

Consumed Connection

UINT

6

Get

USINT

7

Get

Initial Communication Characteristics Production Size

8

Get

Consumed Size

UINT

Get/Set Expected Packet Rate Get/Set Timeout Action

UINT USINT

9 12

UINT

13

Get

Production Path Length USINT

14

Get

Production Path

STRUCT of

Get

Log. Seg., Class Class Number Log. Seg., Instance Instance Number Log. Seg., Attribute Attribute Number Consumed Path Length

USINT USINT USINT USINT USINT USINT USINT

15

MKS Instruments, Inc.

D.I.P. Products Group

33

Page 34

CDN060 User Manual 16

17 revision 1.00

Get

Consumed Path

STRUCT of

Get

Log. Seg., Class Class Number Log. Seg., Instance Instance Number Log. Seg., Attribute Attribute Number Production Inhibit

USINT USINT USINT USINT USINT USINT UINT

Null for Explicit Message STRUCT for I/O Message 0x20 0x04 0x24 0x02 0x30 0x03 0

Common Services Service Code 05 (0x05) 14 (0x0E) 16 (0x10)

Class Yes Yes No

MKS Instruments, Inc.

Instance Yes Yes Yes

Service Name Reset Get_Attribute_Single Set_Attribute_Single

D.I.P. Products Group

34

Page 35

CDN060 User Manual revision 1.00

SERIAL STREAM OBJECT The Serial Stream Object configures the CDN060 serial channel. Serial Stream Object Class Access Attribute 1 Get 2 Get 6 Get 7 Get Instance Access Attribute 3 Get 4 Get/Set

Class Code 64 (0x40) Name

Type

Value

Revision Max Object Instance Max Class Identifier Max Instance Attribute Name

UINT UINT UINT UINT Type

1 1 7 22 (CDN066), 24 (CDN067) Value

Receive Data Transmit Data

Data Format Received message data. Returned in Poll Response Data Format Message data to transmit. Received in Poll Command. USINT Bit 0 – Transmit Channel Blocked Bit 1 – Transmit Buffer Empty Bit 2 – Receive Parity Error (0 to clear) Bit 3 – Receive Buffer Empty Bit 4 – Receive Buffer Overflow Error (0 to clear) Bit 5 – Framing Error (0 to clear) Bit 6 – Transmit Buffer Overflow Error (0 to clear) Bit 7 – CTS Signal State (1 = asserted) USINT 0 = 9600 bps 4 = 600 bps 1 = 4800 bps 5 = 300 bps 2 = 2400 bps 6 = 19200 bps 3 = 1200 bps USINT 0 = no parity 5 = mark (force to 1) 1 = even parity 6 = space (force to 0) 2 = odd parity

5

Get/Set

Status

6

Get/Set

Baud Rate

7

Get/Set

Parity

8 9 10

Get Get Get/Set

Data Size Stop Bits Flow Control

USINT USINT USINT

11 12 13 14

Get/Set Get/Set Get/Set Get/Set

Receive Count Transmit Count Maximum Receive Size Data Format

USINT USINT USINT USINT

15

Get/Set

Block Mode

USINT

16 17 18

Get/Set Get/Set Get/Set

Delimiter Pad Character Maximum Transmit Size

USINT CHAR USINT

MKS Instruments, Inc.

7 (parity enabled) or 8 (no parity) 1 0 = none 2 = CTS / RTS 1 = XON / XOFF 4 = CTS Detect Mode Number of bytes in Receive Buffer. Write to clear. Number of bytes in Transmit Buffer. Write to clear Maximum # bytes returned by Receive Buffer read. Bit 0 – String Format (0 = Short_String, 1 = Array) Bit 1 – Strip Parity Bits (0 = retain, 1 = strip) Bit 2 – Pad Justification (0 = left, 1 = right) Bit 3 – Pad Received Message (0 = no, 1 = yes) Bit 0 – Pre/Post Delimiter (0 = Pre-, 1 = Post-) Bit 1 – Strip Delimiter (0 = keep, 1 = strip) Bit 2 – Delimiter Enable (0 = no, 1 = yes) Bit 3 – Enable Receive Sequence Number Bit 4 – Enable Transmit Sequence Number Bit 5 – Resend (0 = no, 1 = yes) Bit 6 – Synchronization (0 = no, 1 = yesl) Delimiter byte value Pad byte value Defines maximum # bytes that can be transmitted.

D.I.P. Products Group

35

Page 36

CDN060 User Manual revision 1.00

19

Get/Set

Idle String

20

Get/Set

Fault String

21 22 23 24

Get/Set Get/Set Get/Set Get/Set

Status Enable Status Clear Enable Four Wire Option Switch

Short_String Byte string transmitted when gateway receives null Poll (no input bytes). Length = 0 for no Idle String. Short_String Byte string transmitted when gateway’s Polled I/O connection times out. Length=0 for no Fault String USINT Nonzero value enables Status input byte. USINT Nonzero value enables Status Clear output byte. USINT CDN067 only. Enables RS422 4-wire operation. USINT CDN067 only. Option rotary switch position (0-9)

Common Services Service Code 05 (0x05) 14 (0x0E) 16 (0x10)

Class No Yes No

MKS Instruments, Inc.

Instance Yes Yes Yes

Service Name Reset Get_Attribute_Single Set_Attribute_Single

D.I.P. Products Group

36