Page 401

Appendices 11. At the “Import Configuration” window, link the first two items to the module name assigned earlier:

12. Link “:I” to the input assembly:

QX-870 Industrial Raster Scanner User Manual

A-115

Page 402

Allen-Bradley Version 16 PLC Setup 13. Link “:O” to the output assembly:

14. Delete any empty rungs:

A-116

QX-870 Industrial Raster Scanner User Manual

Page 403

Appendices 15. Select one CPS instruction per rung, the “_small_pt” on the left, or the “_big_pt” on the right. Keep the one that corresponds to the assembly sizes configured for the module, and delete the other:

QX-870 Industrial Raster Scanner User Manual

A-117

Page 404

Allen-Bradley Version 16 PLC Setup 16. In this example, the small assembly set has been kept:

In this example, the big assembly set has been kept:

For the remainder of this document, the big assembly set is demonstrated. The system is now configured to test communication with the QX-870. A-118

QX-870 Industrial Raster Scanner User Manual

Page 405

Appendices 17. Select the control button next to “Offline”, and select “Download”:

18. Once the program has downloaded, make sure the PLC is in Run Mode:

QX-870 Industrial Raster Scanner User Manual

A-119

Page 406

Allen-Bradley Version 16 PLC Setup 19. To open the Program Tags, right-click on “Program Tags” and select “Monitor Tags”:

20. Expand the “QXHawk_IO_big_pt” so that the .IN and .OUT structures and values are visible:

A-120

QX-870 Industrial Raster Scanner User Manual

Page 407

Appendices 21. Change the “.OUT.usertag” to non-zero:

QX-870 Industrial Raster Scanner User Manual

A-121

Page 408

Allen-Bradley Version 16 PLC Setup The “.IN.usertag_echo” will change to match the same value as the “.OUT.usertag”:

This confirms that two-way communication with QX-870 is successful. It is left to the programmer to move or modify the CPS instructions in the Main Program according to the application’s requirements. Operation of the data fields within the assemblies is described in the object model documentation.

A-122

QX-870 Industrial Raster Scanner User Manual

Page 409

Appendices

Appendix M, Allen-Bradley Version 20 PLC Setup • To add a new EDS file to RSLogix 5000 Version 20 select the EDS Hardware Installation Tool from the menu item under Tools.

• Click the Next button.

QX-870 Industrial Raster Scanner User Manual

A-123

Page 410

Allen-Bradley Version 20 PLC Setup • Make sure the Register an EDS file(s) radio button is selected, then click Next.

• Click the Browse button to locate the new EDS file on your PC. Then click Next.

A-124