Page 111

Ground and Shield Considerations

Proper grounding is necessary for operator safety, noise reduction, and the protection of equipment from voltage transients. Buildings - including any steelwork, all circuits, and all junction boxes - must be grounded directly to an earth ground in compliance with local and national electrical codes. RS-232 signals have a common signal ground (pin 7 of the 28-pin connector). Pin 7 is normally connected to pin 1 (chassis ground) in the scanner; however, under certain conditions (e.g., when potential differences exist between power outlet grounds) signal and chassis grounds can be isolated from each other inside the scanner by Microscan technicians. Any data line, as necessary, can be shielded. If used, shielding should be isolated from the scanner and grounded only to the host earth ground.

Noise Interference Noise interference can be minimized if cabling Host subject to noise interShielding ference is twisted and/ Com m unications or shielded or encased cable in grounded conduit, Earth ground and the conduit or shielding (“drain” line) Scanner is grounded only to earth ground at the host, as shown in figure Figure A-10 Grounding Diagram, Scanner-Host A-10. You might need to examine and if necessary cut the shielding connection at or near the scanner cable connector.

Ground Loops Ground loops, signal degradation due to different ground potentials in communicating devices, can be eliminated or minimized by ensuring that the host, scanner, and their power supplies are connected to a common earth ground.

MS-7100/7180 Industrial Scanner User’s Manual

A-9

Appendices

Appendix D, Ground and Shield Considerations

Page 112

Appendices

Appendices

Appendix E, Defaulting the Scanner Defaulting the scanner resets the scanner configuration parameters to their original default values and recalls factory calibration settings. Defaulting is necessary if: • You wish to quickly restore default settings to the configuration program after making some temporary changes.1 • You wish to restore factory calibration settings.2 • Communications between the scanner and another device are interrupted because of incompatible settings (for example, a terminal is set to communicate at 9600 baud, but the scanner is configured at 38.4K baud). • The scanner has been assigned a polling address and you wish to access the scanner’s menu. Note: Access to the configuration menus of a scanner that is in a polled mode can be forced by sending a <D> command from an auxiliary terminal via the auxiliary RS-232 port. You can default the scanner by shorting pins 7 and 26 together. This can be done with a mating connector that is made up with a jumper between pins 7 and 26, or by using a wire to short those same pins. Caution: Be certain that the correct pins are shorted. Shorting the wrong pins can cause serious damage to the unit. If no mating connector is available: 1. Turn power to the scanner ON. 1

2. Locate pins 7 and 26 on the host connector (figure A-11) and mark with a pen.

8

9

14

15

3. Using a small length of 18 to 26 gauge wire, momentarily short pins 7 and 26 by inserting mating connector or wire. Listen for a series of short beeps. 4. Within 3 seconds, short pins 7 and 26 again. A longer beep should be heard. If not, repeat the process.

3

4

20

21

25 26

28

Default pins (7 and 26) Figure A-11 Host Connector Default Pins

1. There are no menu options or host commands for resetting the configuration program. 2. Factory calibration settings can also be recalled from within the Calibration Setup menu (see Chapter 4, “Calibration”).

A-10

MS-7100/7180 Industrial Scanner User’s Manual

Page 113

Troubleshooting

The MS-7100/7180 scanner when used correctly should produce good reads. If not, table A-2 lists some of the more common problems associated with setting up and using the scanner. If you are unable to locate or correct the problem, call your Microscan representative. WARNING Do not look directly into laser aperture. Laser light can be hazardous to your eyes. Table A-2 Troubleshooting

Problem

Possible Cause

Solution

Menus do not display when configuration command is sent

Host cable defective or not wired properly

Check cable connections and wiring. (See page 1-8.)

Wrong configuration command (or lower case d) entered

Verify that a <D> serial command (with an upper case D) is being entered.

Scanner configuration settings do not match host's

Reset scanner to default and/or match host settings with scanner's.

Getting only “hieroglyphics” or unintelligible code

Host and scanner baud rates or parity not matched

Check baud rates and parity and change to match host's settings.

Menus display but getting 0% read rate when in read rate test (<C>) or Calibration Setup (<t>)

Wrong label type (different label type being scanned than that enabled in firmware)

Check label configuration settings to be certain that they match the label type being scanned. If label type is in doubt, enable Autodiscriminate All Codes (<P> command). Ensure that fixed length and check sums, if enabled, are set correctly.

Incorrect label range or label too long to be totally covered by scan beam.

See range data in Step 2, “Verify Read Range,” on page 1-3. Reposition label and check the read rate (<t> or <C> commands).

Poor label quality

Try a label that is known to be readable.

Excessive ambient light, sunlight, or strobes

Shield the bar code and/or scan head to verify that excessive light is not the problem.

Object detector or another scanner interfering with reads

Remedy by remounting, eliminating interference, or shielding. Many object detectors emit pulsed infrared signals that can seriously degrade the read rate if they shine into the scanner or onto the bar code label when it is being read.

MS-7100/7180 Industrial Scanner User’s Manual

A-11

Appendices

Appendix F, Troubleshooting

Page 114

Appendices

Appendices

A-12

Problem

Possible Cause

Solution

Getting low percentage read rates during read rate test (<C>) or Calibration Setup (<t>)

Poor label, range, placement, etc.

See “Menus display...” problem on page A-11,. Do Step 9, “Test and Autocalibrate,” on page 1-15 and/or Step 10, “Adjust Other Scanning Parameters,” on page 1-16.

Read rate okay but getting only noread messages in triggered mode

Scanner not triggered when in external mode.

Ensure trigger device is operating properly. Do Read Rate Test <C>. If it reads successfully, the problem is triggering.

Scanner not triggered when in serial mode.

Ensure that correct serial trigger character is entered with start/stop characters (a left angle bracket < (unless redefined) and a right angle bracket >).

Label misaligned or reflecting direct laser light

Ensure the label is not excessively skewed, tilted, or otherwise disoriented. Ensure the bar code is in the scan line when it is supposed to be. Ensure that the bar code is pitched or skewed slightly so as to avoid specular reflection.

Triggering/timeout out of sync

Review triggering and timing. (See “Operations Menu,” on page 2-12.)

Object detector or another scanner interfering with reads

Remedy by remounting, eliminating interference, or shielding. Many object detectors emit pulsed infrared signals that can seriously degrade the read rate if they shine into the scanner or onto the bar code label when it is being read.

Window dirty or obstructed

Clean or remove obstruction.

Previous label read, but subsequent label will not read

Scanner configured in Continuous Read 1 mode

Scan a label that contains different data than that of one being read.

Scanner in polled mode

Check communications protocol.

Scanner not communicating in polled mode.

LRC disabled

Enable LRC.

Improper configuration

Check communications parameters (through Aux port or by defaulting unit and resetting).

Faulty or improper cabling or ground

See Step 6, “Attach Cabling,” on page 1-8 and in particular, “Ground and Shield Considerations,” on page A-9 for cabling information, or if applicable, refer to multidrop manual.

MS-7100/7180 Industrial Scanner User’s Manual

Page 115

Troubleshooting Possible Cause

Solution

Proper trigger levels not enabled

Ensure that the trigger pulse and the trigger polarity settings are correct. Ensure that the trigger circuit wiring meets the scanner requirements. (See Step 6, “Attach Cabling,” on page 1-8.) Check detector range and sensitivity. Try a detector that is known to be good. Ensure read cycle is active during the time the label is in the scan line.

Trigger circuit not correctly wired Object detector inoperative

Scanner not reading during the read cycle

“Bad Format” message

Object detector not positioned properly End of Read Cycle not properly defined for the application Illegal format for a UCC/ EAN-128 label has been detected in Ap. Rec. format.

Ensure that the proper End of Read Cycle is defined in scanner configuration. Correct label.

MS-7100/7180 Industrial Scanner User’s Manual

A-13

Appendices

Problem Scanner not entering read cycle (trigger not working)

Page 116

Appendices

Appendices

Appendix G, Bar Code Symbology Before choosing a bar code symbol, consider:1 • the type of information to be scanned (numeric only, alphanumeric) • the length of the messages to be encoded • how and where labels are to be applied • label printer capabilities

• scan speed • beam width • the space available on the object to be identified • host software limitations • range of the scanner • the speed of the conveyor

Microscan standard scanner firmware supports the following five bar code symbologies. (Firmware can also be custom ordered to support other symbologies.) Code 39. An alphanumeric code with unique start/stop code patterns, composed of 9 black and white elements per character, 3 of which are always wide. Considered the de facto standard for non-retail symbology. Codabar. A 16-character set (0 through 9, and the characters $, :, /, ., +, and –) with start/stop codes and 18 different bar widths. It is commonly used in libraries, photo finishing, and air parcel express applications. I 2 of 5. Interleaved 2 of 5 is a high-density, continuous numeric symbology used mainly in the distribution industry. I 2 of 5 encodes two digits: one in the bars, and one in the spaces. (A check digit is highly recommended.) UPC and EAN. UPC (Universal Product Code) is a fixed length numeric, continuous symbology used in the supermarket and retail industry. The European Article Numbering system (EAN) is a well-known variation of UPC. Both UPC and EAN can have 2 or 5 digit supplemental bar code data following the normal code. Code 128. A very high density alphanumeric symbology. Will encode all 128 ASCII characters, it is continuous, has variable length, and uses multiple element widths measured edge to edge. It is widely used in the nonfood distribution industry and shipping containers. UCC/EAN-128. A subset of Code 128. Breaks code into data fields separated by application identifiers that define data type and length.

1. For further information about symbology, see The Bar Code Book, by Roger C. Palmer, Helmers Publishing, Inc., 1989.

A-14

MS-7100/7180 Industrial Scanner User’s Manual

Page 117

Interface Standards

Interface Standards, established by the Electronic Industries Association (EIA), specify such things as the signaling voltage levels, maximum cable lengths, and number of drivers. With Microscan devices, selection of interface is made by pin assignment (see Appendix A, “Scanner Specifications,” on page A-2) and, in the case of the host communications, by software switching between RS-232 and RS-422. Microscan devices use RS-232, RS-422, and RS-485 multidrop.

RS-232 RS-232 defines an interface between two devices such as, for example, the scanner and host. It differs from the other interfaces by dedicating individual pins to specific functions and by requiring both devices to share a common ground line (pin 4). Since both device chassis are connected to a common ground, a ground loop potential and the possibility of noise interference exists. Therefore cable lengths are limited to a maximum of 50 feet (19.7 m). Despite being the most limited, this interface is used frequently because of the large installed base of RS-232 equipment.

RS-422 RS-422, unlike RS-232, measures signals differentially that is, the receiver looks at the potentials between the two receive (or transmit) wires rather than the potential between signal and ground. As a result, cables, if shielded, can be up to 4000 feet (1575 m) in length. Like RS-232, RS-422 communication is designed for only two devices on a single line. It can be used wherever RS-232 is used.

RS-485 RS-485, like RS-422, can transmit up to 4000 feet (1575 m) using differential voltages but unlike RS-422, its transmitters are turned off until a request for data is received from the host. RS-485 is used exclusively in Multidrop protocol. Note: See “Protocol,” on page 2-6 for additional information on standards.

MS-7100/7180 Industrial Scanner User’s Manual

A-15

Appendices

Appendix H, Interface Standards

Page 118

Appendices

Appendices

Appendix I, Auxiliary Monitor An auxiliary monitor, connected to the scanner can: 1. Echo data from the scanner or host. 2. Send data to the host. 3. Access and make changes to the scanner's configuration menus. The monitor can be configured to operate in one of three modes: • Transparent • Non-Buffered Full Duplex • Non-Buffered Half Duplex Note: Transparent can be used with all protocols. Full Duplex and Half Duplex operations can be used with any protocol except polled protocols (Polling Mode D, Multidrop, User Defined, and User Defined Multidrop).

Transparent Mode Used to batch data from the monitor to the host. The scanner buffers data from the monitor and displays the keyed data on the monitor. The scanner transmits monitor data to the host when a label is scanned or a carriage return is entered from the monitor.

Data Initiated from the Monitor • Monitor data is passed through to the host whenever a return key is pressed at the monitor or whenever bar code data is sent. If sent with bar code data, it is processed on a first-in/first-out basis. • Monitor data to the host is always sent with a preamble and a postamble. • If the MS-7100/7180 is in a polled mode to the host, monitor data will still pass through. • The <D> and <t> commands are the only commands accepted by the scanner from the monitor. All other commands will pass through to the host.

A-16

Host

MS-7100/7180 Industrial Scanner User’s Manual

Monitor

MS-7100 Scanner

Page 119

Auxiliary Monitor

Host

Monitor

MS-7100 Scanner

Data initiated from the Host • In polled mode, data echoed from the host to the monitor must be in the format <B ____> (e.g., to send the word “LUNCH” to the monitor, it must be sent in the format <BLUNCH>).In unpolled mode, all host data is echoed to the monitor.

Host

Monitor

MS-7100 Scanner

MS-7100/7180 Industrial Scanner User’s Manual

A-17

Appendices

Data initiated from the Scanner • Transmission to the monitor occurs immediately upon a good read. • Scan data to the monitor does not include a preamble or a postamble. • Communications with the monitor is always in Point-to-Point protocol, even if the host is in a polled protocol mode.

Page 120

Appendices Appendices

Half Duplex Mode In half duplex mode all monitor data and bar code data is sent directly to the host. Bar code data is displayed on the monitor screen at the same time the data is sent to the host.

Data initiated from the Monitor • Monitor data to the host is ignored if the scanner is in a polled mode. • Monitor data or scanned data is sent to the host whenever it is received. • Monitor data is not echoed. • Monitor data to the host is always sent without a preamble or a postamble. • <D> and <t> commands are the only commands that is accepted by the scanner from the monitor. All other commands are passed through to the host.

MS-7100 Scanner

Host

Data initiated from the Scanner • Scan data is transmitted to the monitor at the same time it is transmitted to the host. • Data transmission conforms with all parameters specified in the configuration menu (e.g., Preamble, Postamble, End of Read Cycle). Data is initiated from the Host • In polled mode, data echoed from the host to the monitor must be in the format <B____> (i.e.: to send the word “LUNCH” to the terminal, it must be sent in the format <BLUNCH>). • In unpolled mode, all host data is echoed to the monitor.

Monitor

Host

Monitor

MS-7100 Scanner

Host

Monitor

MS-7100 Scanner

A-18