For the Microscan MS-5000

Page 71

Mode and Data Switch Settings

Mode 2: Address Mode Switches

= On = Off

See mode 1 for switch settings.

Mode 3: Host Port Communications Mode Switches

= On = Off Data Switches

Baud Rate

Parity

Stop Bits

Data Bits

123

45

6

7

600

None

One

Seven

1200

Even

Two

Eight

2400

Odd

4800 9600 19200 38400

Mode 4: Preamble, Postamble Mode Switches

= On = Off

Data Switches

Postamble

1

2 Disable

Disable

Enable

Enable

MS-5000 Multidrop Concentrator User’s Manual

5–Profile Card

Preamble

5-5

Page 72

Chapter 5

Profile Card Configuration

Mode 5: Protocol, Host Port RS-422 = On

Mode Switches

= Off Data Switches

Protocol

RS-422

123

4 Point-to-Point

Disable

Point-to-Point with RTS/CTS

Enable

Point-to-Point with XON/XOFF Point-to-Point with RTS/XON Polling Mode D Multidrop User Defined User Defined Multidrop

Mode 6: Aux Port Mode Mode Switches

= On = Off

Data Switches

Aux Port Mode

12 Disable

5–Profile Card

Enable

5-6

MS-5000 Multidrop Concentrator User’s Manual

Page 73

Mode and Data Switch Settings

Mode 7: Aux Port Communications = On

Mode Switches

= Off Data Switches

Baud Rate

Parity

Stop Bits

Data Bits

123

45

6

7

2400

None

One

Seven

4800

Even

Two

Eight

9600

Odd

19.2K 38.4K

Mode 8: LAN Port Communications Mode Switches

= On = Off Data Switches

Baud Rate

Parity

Stop Bits

Data Bits

RS-422

123

45

6

7

8

600

None

One

Seven

Disable

1200

Even

Two

Eight

Enable

2400

Odd

4800

5–Profile Card

9600 19.2K 38.4K

MS-5000 Multidrop Concentrator User’s Manual

5-7

Page 74

Chapter 5

Profile Card Configuration

Mode 9: Host Port Turnaround Timeout Mode Switches

= On = Off

Mode 10: Host Port Intercharacter Timeout Mode Switches

= On = Off

Mode 11: LAN Port Turnaround Timeout Mode Switches

= On = Off

Mode 9, 10, and 11 will accept binary values from 1 to 250. To set these modes, multiply the desired number of seconds for timeout by 10 and enter the result in binary format. See mode 1 switch settings for timeout ranges from 0.1 seconds to 5 seconds. (Although not shown for mode 1, switches 7 and 8 are OFF for 1 through 50.) See “Binary Calculations” on page 5-9 for timeout ranges from 5.1 seconds to 25 seconds.

Mode 12: Blocking Factor1 Mode Switches

= On = Off

Mode 12 will accept binary values from 1 to 127. Values are set the same as mode 9, 10 and 11.

5–Profile Card

See mode 1 for switch settings.

1. See also, “<C>Send Partial Buffer to Host Command” on page 4-13 for related information.

5-8

MS-5000 Multidrop Concentrator User’s Manual

Page 75

Binary Calculations

Mode 13: RTS/CTS and XON/XOFF Mode Switches

= On = Off

Data Switches

RTS/CTS

XON/XOFF

1

2 Disable

Disable

Enable

Enable

Mode 14: Full Screens Mode Switches

= On = Off

Data Switches

Fulls Screens

1 234 Disable Enable

Binary Calculations Data switch settings for values 51 to 255 must be determined with binary calculation. (Specifically, the timeout values for 51 to 255 in mode 9 and various serial trigger character selections in mode 10.)

MS-5000 Multidrop Concentrator User’s Manual

5-9

5–Profile Card

The eight data switches on the profile card represent the eight data bits that define any number from 0 to 255 in binary format. To convert a number to its binary equivalent: 1. Determine which decimal equivalent (1, 2, 4, 8, 16, 32, 64, 128) is the largest number not exceeding the number to convert. 2. Put a one (1) above that number to indicate an ON position.

Page 76

Chapter 5

Profile Card Configuration For example, table 5-2 shows the calculation process for the number 250. The first one (1) is placed in the eighth bit column over the number 128, since that is the largest possible decimal equivalent to use. Table 5-2 Calculating Binary Conversion Data Switches

1

2

3

= On

4

5

6

7

8

Data Switches (bit representation) Data Switch Settings

1

1

1

1

1

1

Binary Code

2

10 26 58 122

Remainder Numbers 250

1

= Off

2

4

8

16 32 64 128

<--- Number to Convert Decimal Equivalent

3. Subtract the decimal equivalent from the original number. 4. Place the remainder above the next largest decimal equivalent that does not exceed the remainder number. 5. Put a one (1) above that number. 6. Continue this process until the remainder equals zero (0), as follows: 250 -128=122, -64=58, -32=26, -16=10, -8=2, -2=0

5–Profile Card

OFF positions on the data switches result from: • Decimal equivalent numbers passed over because they are greater than the remainder (the third bit in table 5-2), • Decimal equivalent numbers not used because the formula has terminated with a remainder of zero (0) (the first bit in table 5-2).

5-10

MS-5000 Multidrop Concentrator User’s Manual

Page 77

Contents Appendix A, MS-5000 Specifications ........................................... A-2 Appendix B, Quick Reference Tables ........................................... A-3 Appendix C, Defaulting the MS-5000 .......................................... A-6 Appendix D, Ground and Shield Considerations .......................... A-7 Appendix E, Terminal Resistor ..................................................... A-9 Appendix F, Interface Standards ................................................ A-10 Appendix G, Glossary of Terms ................................................. A-11

MS-5000 Multidrop Concentrator User’s

A-1

Appendices

Appendices

Page 78

Physical Characteristics:

Communications Settings

Length: 6.2 in. (157.5 mm) Height: 1.36 in. (34.5 mm)

Host Port Communications Interfaces: RS-232, RS-422, RS-485 ACSII Character Format: 7 or 8 Data Bits Stop Bits: 1 or 2 Baud Rates: 600, 1200, 2400, 4800, 9600, 19.2K, 38.4K Selectable Parity: Odd, Even, or None Protocols: Point-to-Point, Polling Mode D, Multidrop, User Defined, and User Defined Multidrop LAN Port Communications Interface: 4-wire, RS-485, RS-422 ACSII Character Format: 7 or 8 Data Bits Stop Bits: 1 or 2 Baud Rates: 600, 1200, 2400, 4800, 9600, 19.2K, 38.4K I/O Port: 6-pin, 6-wire modular Protocols: Multidrop, User Defined Multidrop (up to 50 devices per concentrator) Auxiliary (Monitor) Port Communications Interface: RS-232 ACSII Character Format: 7 or 8 Data Bits Stop Bits: 1 or 2 Baud Rates: 2400, 4800, 9600, 19.2K, 38.4K I/O Port: 9-pin, D-subminiature plug Protocol: Point-to-Point

0.5"(12.7)

Width: 6.61 in. (167.9 mm) Weight: 16 oz. (453 grams) 5.6" (142.24) Front

1.85" (46.99) CAUTION: The6-32mountingscrews should not extend more than 0.12 in. (3 mm) into the mounting holes.

6.2" (157.48)

2.5" (63.5)

6/32 threads (6.35mm) 4 places

Inches (mm)

Rear

5.8" (147.32) 0.030" (7.62)

5.8" (147.32)

Electrical Characteristics

5.2" (132.08)

3.8" (96.52)

0.160" (4.06) DIA (4 places)

4.5" (114.30)

Front

Figure A-1 MS-5000 Dimensions

A-2

+12 VDC @ 40 mA max., 20 mV p-p max. allowed ripple –12 VDC @ 40 mA max., 20 mV p-p max. allowed ripple +5 VDC @ 300 mA max., 200 mV p-p max. allowed ripple

Operating Environment Measurements in inches (millimeters)

1.0" (25.4)

Appendices

Appendix A, MS-5000 Specifications

Operating Temperature: 32° to 113°F (0° to 45°C) Storage Temperature: –58° to 158°F (-50° to 70°C) Humidity: 0% to 95% (non-condensing)

Status Lights Three LEDs (light emitting diodes) on the front panel of the concentrator serve as visual indicators to verify that it is operating correctly. IND 1: Flashes green each time data is sent to the host. IND 2: Illuminates red whenever the concentrator is in a ready state or is polling the connected devices. When this light goes off, a data-buffer-full condition exists and the concentrator is no longer polling the devices. PWR: Illuminates red when the power switch is in the ON position.

MS-5000 Multidrop Concentrator User’s Manual

Page 79

Quick Reference Tables Appendices

Appendix B, Quick Reference Tables Table A-1 ASCII Table with Control Characters

Dec

Hex

Mne

Ctrl

Dec

Hex

Ch

Dec

Hex

Ch

Dec

Hex

Ch

00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31

00 01 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 0F 10 11 12 13 14 15 16 17 18 19 1A 1B 1C 1D 1E 1F

NUL SOH STX ETX EOT ENQ ACK BEL BS HT LF VT FF CR SO SI DLE DC1 DC2 DC3 DC4 NAK SYN ETB CAN EM SUB ESC FS GS RS US

^@ ^A ^B ^C ^D ^E ^F ^G ^H ^I ^J ^K ^L ^M ^N ^O ^P ^Q ^R ^S ^T ^U ^V ^W ^X ^Y ^Z ^[ ^\ ^] ^^ ^_

32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63

20 21 22 23 24 25 26 27 28 29 2A 2B 2C 2D 2E 2F 30 31 32 33 34 35 36 37 38 39 3A 3B 3C 3D 3E 3F

SP ! " # $ % & ' ( ) * + , . / 0 1 2 3 4 5 6 7 8 9 : ; < = > ?

64 65

40 41 42 43 44 45 46 47 48 49 4A 4B 4C 4D 4E 4F 50 51 52 53 54 55 56 57 58 59 5A 5B 5C 5D 5E 5F

@ A B C D E F G H I J K L M N O P Q R S T U V W X Y Z [ \ ] ^ _

96 97 98

60 61 62 63 64 65 66 67 68 69 6A 6B 6C 6D 6E 6F 70 71 72 73 74 75 76 77 78 79 7A 7B 7C 7D 7E 7F

` a b c d e f g h i j k l m n o p q r s t u v w x y z { | } ~ ý

66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95

MS-5000 Multidrop Concentrator User’s Manual

99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127

A-3

Page 80

Appendices

Table A-2 Summary of Serial Configuration Commands

Command

Effect

51<Kadata>CR 51<Kbdata>CR

Host Port Baud, Parity, Stop Bits, and Data Bits Host Port RS-422

51<Kcdata>CR 51<Kddata>CR 51<Kedata>CR 51<Kfdata>CR 51<Kgdata>CR 51<Khdata>CR 51<Kidata>CR 51<Kjdata>CR 51<Kkdata>CR 51<Kldata>CR 51<Kmdata>CR 51<Kndata>CR 51<Kodata>CR 51<Kpdata>CR 51<Kqdata>CR 51<Krdata>CR 51<Ksdata>CR 51<KIdata>CR 51<KJdata>CR

LRC Preamble Postamble Host Protocol Blocking Factor Host Port Turnaround Timeout Host Port Intercharacter Timeout RTS/CTS XON/XOFF LAN Port Baud, Parity, Stop Bits, and Data Bits LAN Port RS-422 LAN Port Turnaround Timeout, Number of Devices Auxiliary Mode Aux Port Baud, Parity, Stop Bits, and Data Bits Full Screens Battery-backed RAM (optional) Poll Response Timeout Time and Date Setting Time and Date Output

Table A-3 Summary of MS-5000 Operational Commands

Command 51<A>CR 51<B>CR 51<C>CR 51<D>CR 51<Z>CR 51<&>CR 51<#>CR

Effect Software reset, but preserve data in buffers Reset, including data in buffers Partial buffer to host Launch Configuration Program Save current configuration for power up Upload to Current Date and Time Upload to Software Part Number

Less than < and greater than > symbols are included as part of the commands. There are no spaces between any fields, but commas are used to separate data fields. Configuration commands are shown here with one data field; however, the actual number of data fields varies by command.

A-4