Manual · Microscan
DN120 DeviceNet Gateway User's Manual
Manual71 pagesPDF 1.4 MB
User's manual for the Microscan DN120 serial to DeviceNet gateway: installation, wiring, theory of operation and configuration.
Covers · 1 model
The models it covers
Summary
What is in it
The user's manual for the Microscan DN120, a gateway that connects an RS232 serial device to a DeviceNet industrial control network. It covers mounting and wiring the DeviceNet and DB9 serial connections, how the gateway passes serial messages to and from the DeviceNet master, configuring it with rotary switches or DeviceNet objects, the DeviceNet object specifications, an RSNetworx configuration example, further configuration examples and troubleshooting.
Its parts
- Overview
- Installation
- Theory of Operation
- Gateway Configuration
- DeviceNet Specifications
- RSNetworx Configuration Example
- Configuration Examples
- Troubleshooting
From the manual
Key facts from this manual
Each line names its page in the PDF.
Microscan's user manual (PN 83-210010 Rev B) for the DN120, a gateway that links an RS232 serial device such as a barcode scanner to a DeviceNet network. It covers mounting, wiring, the rotary switches and status LEDs, serial channel settings, RSNetworx setup, worked examples and troubleshooting.
- Device
- Serial to DeviceNet gateway; the DN120 has an RS232 full duplex serial channel p. 4
- Connectors
- Male 5-pin micro connector for DeviceNet; male DB9 for the serial device p. 6
- Power
- All from the DeviceNet network, up to 50mA from the 24VDC supply p. 6
- DeviceNet
- Slave with POLL and EXPLICIT messages; 125K, 250K or 500K baud; MAC ID 00 to 63, set by rotary switches p. 4, 18
- Serial rates
- 300, 600, 1200, 2400, 4800, 9600 or 19200 bps by rotary switch, or PRG to use the rate written over DeviceNet p. 19
- Serial channel
- 500V isolated; RTS/CTS and XON/XOFF flow control; configurable parity; 64 byte transmit and receive FIFO buffers p. 4
- Operating temperature
- 0°C to 70°C p. 5
- Heat
- Up to 1.4W p. 5
- Status LEDs
- NET and MOD for DeviceNet status; TX and RX for serial activity p. 19, 20
- Simple RS232 wiring
- DB9 pins 2 RXD, 3 TXD, 5 GND p. 7
- Mounting
- Horizontal or vertical surface, two screws (not provided) in the 0.19 inch mounting holes p. 5
- Construction
- Encapsulated circuit board in a compact industrial case p. 4
What this manual walks you through
- Mounting the gateway and wiring it to DeviceNet and a serial device p. 5, 6, 7
- Setting the DeviceNet baud rate and MAC ID with the rotary switches p. 18
- Setting the RS232 baud rate with the serial rotary switch p. 19
- Checking the status LEDs at power-up p. 19, 20
- Registering the gateway's EDS file in a configuration tool p. 20
- Configuring the serial channel through the Serial Stream Object p. 21
- Working out the poll sizes for the DeviceNet master scan list p. 26
- Example: reading UPC labels from a serial barcode scanner into a PLC p. 59
- Troubleshooting a gateway that is not recognized or shows red LEDs p. 68
Good to know
- The serial connector is not rated for NEMA4 / IP65 environments, so the gateway needs a suitable location or enclosure. p. 5
- Set the rotary switches before connecting to the DeviceNet network. p. 18
- A MAC ID setting above 63 makes the gateway use the MAC ID stored in its retentive memory. p. 18
- The gateway must be out of the master scanlist before its settings are changed. p. 21
- Disconnect the gateway from the network before changing its MAC ID. p. 68
Questions this manual answers
How is the Microscan DN120 powered?
Entirely from the DeviceNet network; it draws up to 50mA from the 24VDC supply. p. 6
What DeviceNet baud rates does the DN120 support?
125K, 250K or 500K, chosen on a rotary switch; the PGM position uses the rate stored in retentive memory. p. 18
What does a flashing red NET LED mean on the DN120?
The troubleshooting table says the gateway was removed from the DeviceNet master scanlist or network; power cycle it to reset. p. 68
What causes 1747-SDN error code 77 with a DN120?
The table points to the gateway's Poll Produce Size or Poll Consume Size not agreeing with the 1747-SDN Poll Rx/Tx settings. p. 68
The whole text · 8 parts
Read the manual here as text
Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.
The file