The text of a manual · part 6 of 8
DN120 DeviceNet Gateway User's Manual, pages 46 to 54
Pages 46 to 54 of 71
The original document is the PDF (1.4 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Microscan DN-120
Page 46
DN120 DeviceNet Gateway User’s Manual
3) RSNetworx displays the following text box while it uploads the network configuration.
4) The following screen displays the online nodes.
Microscan Systems, Inc.
46
Page 47
DN120 DeviceNet Gateway User’s Manual 5) Left-click on the DN120 icon to select it. Right-click and select Properties from the pop-up menu. You can also double-click on the DN120 icon to open its properties box.
6) RSNetworx displaces the following text box while is reads DN120 EDS file.
Microscan Systems, Inc.
47
Page 48
DN120 DeviceNet Gateway User’s Manual
7) The DN120 Properties Box is displayed.
8) Select the Parameters tab. You will be prompted for the parameters source. Select the Upload button to upload DN120 parameters from the actual device. All the DN120 parameters are now shown in the Properties window.
Microscan Systems, Inc.
48
Page 49
DN120 DeviceNet Gateway User’s Manual
9) You may now edit the Serial Stream Object attributes in this window Note that the Idle String and Fault String attributes are not listed. These attributes use Short_String data type, which is not supported by RSNetworx EDS File interface. 10) Use the Class Instance Editor to configure Short_String attributes.
Microscan Systems, Inc.
49
Page 50
DN120 DeviceNet Gateway User’s Manual 11) Select the Set_Attribute_Single service code to write an attribute value, and the Get_Attribute_Single service code to read an attribute value. Check Values in decimal box to enter class, instance, attribute, and data values in decimal. The Idle String address is Class 64, Instance 1, Attribute Number 19. The Fault String address is Class 64, Instance 1, Attribute Number 20. Enter the Short_String data as length byte, then data bytes. Example is [0x01 0x02] for a single byte string 0x02 (ASCII STX).
12) Enter the remaining Serial Stream Object attributes in the Parameters Box window. Status – Click on … to open selection box. Shows current status and error information. Click on any errors to clear check. Press OK to continue.
Baud Rate – Click on arrow to the right of the current value to select from pull-down menu. Parity – Click on arrow to the right of the current value to select from pull-down menu.
Microscan Systems, Inc.
50
Page 51
DN120 DeviceNet Gateway User’s Manual Data Size – Read-only value, set to 8 if no parity selected and 7 if party selected. Stop Bit – Read-only value, always set to 1. Flow Control – Click on arrow to the right of the current value to select from pull-down menu. Receive Count – Read-only value. Transmit Count – Read-only value. Maximum Receive Size – Click on current value and enter desired number in decimal. Maximum Transmit – Click on current value and enter desired number in decimal. Data Format – Click on … to open selection box. Click on check box to select the desired option. The Delimiter Mode uses bits 0, 1, 2, 3 of the byte. Ignore bits 4 through 7.
Block Mode – Click on … to open up selection box. Click on check box to set or clear the desired bit. The Serial Status byte uses bits 0 through 6. Ignore bit 7.
Receive Delimiter – Click on current value and enter number in decimal. Pad Char – Click on current value and enter number in decimal.
Microscan Systems, Inc.
51
Page 52
DN120 DeviceNet Gateway User’s Manual
Configure DeviceNet Master Scan list After all the object instances have been configured, the DeviceNet master can be configured to poll the gateway. 1) Before using the RSNetworx to map the gateway’s Polled I/O connection to 1747-SDN DeviceNet master scanner, you must calculate the Poll Produce Size & Poll Consume Size. Chapter 4 describes how to calculate these values. 2) Double click on the 1747-SDN icon to open its Properties box. You can also left click on the icon to select it, right click for the pop-up menu, and select Properties.
3) Select the Scan list tab. RSNetworx prompts you for the Scanner Configuration. Click Upload to upload current 1747-SDN configuration from the node. RSNetworx displays the upload progress.
Microscan Systems, Inc.
52
Page 53
DN120 DeviceNet Gateway User’s Manual
4) The next window shows the Available Devices: that can be added to the 1747-SDN Scanlist.
5) Select the Automap on Add checkbox if you want RSNetworx to automatically map the DN120 input and output bytes into the 1747-SDN memory. Microscan Systems, Inc.
53
Page 54
DN120 DeviceNet Gateway User’s Manual 6) Select the DN120 under Available Devices: and click the > button to transfer to Scanlist.
7) RSNetworx warns that the DN120 does not contain any I/O data. Click OK to continue.
Microscan Systems, Inc.
54