Page 31
LOW VOLTAGE SELF-CONTIANED DC SENSORS WITH CURRENTSINKING OUTPUTS AND SENSOR ALARM
Open the terminals in the sensor terminal block by turning each screw counterclockwise until there is enough space to insert wires.
3.
Strip off 2 ¼ inches of the sensor cable’s outer jacket.
4.
Strip the insulation off each cable wire ¼ of an inch.
5.
Feed the sensor cable through the small strain relief.
6.
Insert the sensor’s DC common wire into the COMMON terminal and secure the wire by turning the terminal’s screw clockwise. (Refer to the MX001 box or to Figure 20 for the order of the terminals for the sensor wires.)
7.
Insert and secure the sensor’s +DC power input wire into the +12V OUT terminal.
8.
Insert and secure the sensor’s signal output wire into the S INterminal.
9.
Insert and secure the sensor’s alarm signal output wire into the A INterminal.
10.
Secure the cable by turning the strain relief’s domed sealing nut clockwise until tight.
11.
Position the jumpers on pins 5 and 6 of the J1 (S SET UP) and J2 (A SET UP) headers. (Refer to figure 21).
S IN-
A IN-
A IN+
+12V OUT
2.
S IN+
Make sure power is not being applied to the unit.
COMMON
1.
Figure 20 1
A SET UP 1
2
3
4
6 5
6 J2 J1
1 1
2
3
4
S SET UP
Figure 21
5
6 6
25
Page 32
LOW VOLTAGE SELF-CONTAINED DC SENSORS WITH CURRENT SOURCING OUTPUT AND SENSOR ALARM 1.
Make sure power is not being applied to the unit.
2.
Open the terminals in the sensor terminal block by turning each screw counterclockwise until there is enough space to insert wires.
3.
Strip off 2 ¼ inches of the sensor cable’s outer jacket.
4.
Strip the insulation off each cable wire ¼ of an inch.
5.
Feed the sensor cable through the small strain relief.
6.
Connect a small jumper wire between the COMMON and the S IN- terminals and secure the jumper in the S IN- terminal by turning the terminal’s screw clockwise. (Refer to the MX001 box or to Figure 22 for the order of the terminals for the sensor wires.)
7.
Connect a small jumper wire between the COMMON and the A IN- terminal and secure the jumper in the A IN- terminal.
8.
Connect the sensor’s DC common wire to the COMMON terminal and secure the jumpers and wire by turning the terminal’s screw clockwise.
9.
Insert and secure the sensor’s +DC power input wire into the +12V OUT terminal.
10. Insert and secure the sensor’s signal output wire into the S IN+ terminal. 11. Insert and secure the sensor’s alarm output wire into the A IN+ terminal. Secure the cable and turn the strain relief’s domed sealing nut clockwise until tight. 12. Position the jumpers on pins 1 and 2 of the J1 (S SET UP) and J2 (A SET UP) headers. (Refer to Figure 23)
26
Page 33
+12V OUT
S IN+
S IN-
COMMON
A IN-
A IN+
LOW VOLTAGE SELF-CONTAINED DC SENSORS WITH CURRENT SOURCING OUTPUT AND SENSOR ALARM (CONTINUED)
Figure 22
1
A SET UP 1
2
3
4
6 5
6 J2 J1
1 1
2
3
4
S SET UP
5
6 6
Figure 23
27
Page 34
“UNIVERSAL” SELF-CONTAINED SENSORS THAT PROVIDE SINGLE POLE/DOUBLE THROW (SPDT) RELAY OUTPUTS FOR BOTH OBJECT SENSING AND SENSOR ALARM 1.
Make sure the “universal” sensor can operate on +12 volts DC at 200ma or less. If so, then the MX001 box can supply the +12 volts necessary to power the “universal” sensor.
2.
Make sure power is not being applied to the unit.
3.
Open the terminals in the sensor terminal block by turning each screw counterclockwise until there is enough space to insert wires.
4.
Strip off 2 ¼ inches of the sensor cable’s outer jacket.
5.
Strip the insulation off each cable wire ¼ of an inch.
6.
Feed the sensor cable through the small strain relief.
7.
Insert the sensor’s +DC power input wire into the +12V OUT terminal and secure the wire by turning the terminal’s screw clockwise. (Refer to the MX001 box or to figure 24 for the order of the terminals for the sensor wires.)
8.
Insert the sensor’s -DC or common power input wire and both the object sense and alarm relay output common signal wires into the COMMON terminal and secure all three wires.
9.
Determine from the literature supplied with your sensor which sensor relay output makes contact with its common terminal when an object is sensed. If the output cannot be determined, go on to Step 10. Otherwise, skip to Step 11.
10. Temporarily apply power to the MX001 box to activate the sensor and then determine with a continuity tester or ohm meter which relay output (the normally closed [NC] or the normally open {NO] output) makes contact with the COMMON terminal when the sensor “sees" the object to be scanned.
11. Remove any power applied to the MX001 (in Step 100 and connect and secure the “sense” relay output wire previously determined to the S IN- terminal. (The other sense relay output wire may be cut off or connected to the MX001 COMMON terminal if desired).
28
Page 35
“UNIVERSAL” SELF-CONTAINED SENSORS THAT PROVIDE SINGLE POLE/DOUBLE THROW (SPDT) RELAY OUTPUTS FOR BOTH OBJECT SENSING AND SENSOR ALARM (CONTINUED) 12. Determine from the literature supplied with your sensor which sensor alarm relay output makes contact with its common terminal when sensing conditions become marginal. If the output cannot be determined, go on to Step 13. Otherwise, skip to Step 14.
13. Temporarily apply power to the MX001 box again to activate the sensor and try to make sensing conditions marginal by placing the object to be sensed at a greater than normal distance from the sensor or misalign the sensor to activate the sensor’s alarm output. (Most sensors have a small indicator that shows when the alarm output is active by being either on or off depending upon the type of sensor.) Determine with a continuity tester or ohm meter which relay output (the normally closed [NC or the normally open {NO] output) makes contact with the COMMON terminal when the sensor indicates that its alarm output is active.
14. Remove any power applied to the MX001 box (in Step 13) and connect and secure the “alarm” relay output wire previously determined to the A IN- terminal. (The other alarm relay output wire may be cut off or connected to the MX001 COMMON terminal if desired.)
15. Secure the cable by turning the strain relief’s domed sealing nut clockwise until tight.
16. Position the jumpers on pins 5 and 6 of the J1 (S SET UP) and J2 (A
+12V OUT
S IN+
S IN-
A IN+
A IN-
COMMON
SET UP) headers. (Refer to Figure 25)
Figure 24 1
A SET UP 1
2
3
4
6 5
6 J2 J1
1 1
2
3
4
S SET UP
5
6 6
Figure 25
29
Page 36
CLOSING THE MX001 INDUSTRIAL CONTROL BOX 1.
Close the lid of the MX001 box.
2.
While pushing down on the lid, rotate the clamp clockwise, then move the clamp to the right, positioning it over the ledge on the lid.
3.
Fasten the clamp in place by tightening its screw with a flat blade screwdriver.
CONNECTING THE MX001 TO THE SCANNER The supplied, scanner link cable is used to connect the MX001 box to a TECH series scanner. This one meter cable carries the MX001’s control signals and is terminated with an 8 and a 19 pin connector. (Other cable lengths are available, contact Metrologic for details.) 1.
Find the 8-pin male end of the scanner link cable and locate the wide connector key found above pins A and G. Align this key with the corresponding key on the MX001’s signal connector. Push in on the cable connector slightly and rotate its ring clockwise until the connector locks in place with a click.
2.
Likewise, the 19-pin female connector found on the other end of this cable is connected to the 19-pin male connector on the scanner case. This connector is the one closest to the scanner window.
30
Page 37
CABLE PIN OUTS FOR THE 8-PIN AND 19-PIN CONNECTORS The standard scanner link cable length is 3 feet – 1 meter. Other scanner link cable lengths are available upon request. (Contact Metrologic Customer Service for details.) If there is a need to lengthen the scanner link cable, use a cable with #26 wire. The scanner link cable can be easily extended to 100 feet without signal difficulty. The following are listings of the cable pin outs for the 19-pin female and the 8-pin male ends of the link cable. (Refer to Figures 26 and 27) 19-Pin Female Mil Spec Connector Pin
Function
A B C-L M N P R S-V
TRIAC1+ TRIAC1RESERVED SENSOR+ SENSORSENSE ALARM+ SENSE ALARMRESERVED
A
B C
P V
R
D
M L
N
S
J
T
E F
K
U
H
G
Figure 26
8-Pin Male Mil Spec Connector Pin
Function
A B C D E F G H
TRIAC+ TRIACSENSOR+ SENSORSENSE ALARM/AUX+ SENSE ALARM/AUXRESERVED RESERVED
G
A
F E
H
B C
D
Figure 27
31
Page 38
SPECIFICATIONS Application: Orientation: Dimensions: Weight: Case Material: Electrical: System Interfaces: Status Indicators: UL, CSA and IEC:
Industrial Control Interface L-bracket with TECH scanner or independently mounted 152mm L x 102mm W x 76mm D (6” x 4” x 3”) 1.36 Kg 93 lbs.) Oil Tight J1C box 12 V at 200mA for low voltage DC type object sensor 6 Amp TRIAC output (5 Amp in Europe) 12V, 5V, 10mA or switch closure object sensor input Four LED’s for: 12V Power supply, TRIAC, sensor and sensor alarm UL and CUL listed, CE
Specifications subject to change without notice
32
Page 39
TROUBLESHOOTING No Operation – Green LED off: 1.
Check power input wiring for correct connection and security at power terminal block. (Wires must be stripped before insertion into the terminal block and terminal block screws must be tight, clamping the stripped wire firmly in the block.)
2.
Check for AC power input between LINE IN and NEUTRAL terminals of the power terminal block.
3.
Check F2 Control fuse.
F2 Control Fuse Open: 1.
Review the MX001 manual detailing the fuse installation procedure and check the F2 Control fuse for correct rating. (Depends upon line voltage in use.)
2.
If a low voltage DC type sensor is connected to the MX001 and is using the MX001 as its power source (+12V OUT in use), make sure this sensor does not draw more than 200mA of current from the MX001 or that the sensor is incorrectly connected or shorted.
No Operation Sensor & TRIAC with Green LED on (other LED’s do not light): 1.
Check that the scanner link cable is connected to the MX001 and scanner.
2.
Check the connection of the MX001 internal link cable to the printed circuit board at J3 (Lower right corner).
3.
Check for proper connection of the sensor (if used) plus proper positioning of the S and A set up jumpers at J1 and J2. (Depends upon sensor type.)
4.
Check for proper HoloSet programming of the TRIAC. (To check TRIAC output, temporarily program the scanner via HoloSet to support only the TRIAC with TRIAC Normally On. This will activate the red TRIAC LED and the TRIAC output continuously.)
33
Page 40
TROUBLESHOOTING (CONTINUED) No TRIAC Output with Red TRIAC LED On: 1.
Check that the TRIAC load is properly connected to the TRIAC terminal block. (Wires must be stripped before insertion into the terminal block and terminal block screws must be tight, clamping the stripped wire firmly in the block.)
2.
Check for AC power output between the TRIAC OUT and NEUTRAL terminals of the TRIAC terminal block when the TRIAC LED is on.
3.
Check the fuse in the F1 TRIAC fuse holder.
F1 TRIAC Fuse Open: 1.
Review the section detailing the fuse installation procedure and check the F1 TRIAC fuse for correct rating (10 or 6.3 Amps). Make sure one of the F2 CONTROL fuses have not been installed in place of the correct TRIAC fuse.
2.
Check that the TRIAC load has been properly connected to the TRIAC terminal block and does not draw current greater than the rating of the F1 TRIAC fuse installed (10 Amp in USA or 6.3 Amp in Europe/Asia).
3.
Check that the TRIAC load does not draw an excessively large surge or start up current that is beyond the capabilities of the MX001 fuse rating.
4.
Check to make sure the TRIAC load is not or has not been accidentally shorted. If a short is found, remove the short and check for proper TRIAC operation after installing a new F1 TRIAC fuse. (See item 5.)
5.
Disconnect the normal TRIAC load and temporarily connect a 60W light bulb in a wired test socket to the TRIAC output. If the bulb does not light when the red LED TRIAC indicator is on after a new fuse has been installed or if the bulb lights continuously with the red LED TRIAC indicator off, then MX001 TRIAC circuit damage is indicated. The Mx001 can be damaged if the TRIAC output is accidentally shorted.
NOTE: TRIAC load refers to the device that is connected by the MX001 TRIAC.