MX001 Industrial Control Interface Installation and User's Guide, pages 21 to 30

Pages 21 to 30 of 50

The original document is the PDF (455 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Metrologic MX001

Page 21

SENSORS POWERED INDEPENDENTLY WHICH PROVIDE EITHER 12V, 5V OR A 10MA DC OUTPUT SIGNAL 1.

Make sure power is not being applied to the unit.

2.

Open the terminals in the sensor terminal block by turning each screw counterclockwise until there is enough space to insert wires.

3.

Strip off 2 ¼ inches of the sensor cable’s outer jacket.

4.

Strip the insulation off each cable wire ¼ of an inch.

5.

Feed the sensor cable through the small strain relief.

6.

Insert the sensor’s DC common (or negative) output wire into the S IN- terminal block and secure the wire by turning the terminal’s screw clockwise.(Refer to the MX001 box or Figure 6 for the order of the terminals for the sensor wires)

7.

Insert and secure the sensor’s positive output wire to the S IN+ terminal.

8.

Secure the cable by turning the strain relief’s domed sealing nut clockwise until tight.

9.

Depending upon your sensor’s output, perform one of the following steps.

For a 5V DC output signal, position the jumper on pins 3 and 4 of the J1 (S SET UP) header. (Refer to Figure 7)

•

For a 10mA DC output signal, position the jumper on pins 4 and 5 of the J1 (S SET UP) header. (Refer to Figure 7)

+12V OUT

•

S IN+

For a 12V DC output signal, position the jumper on pins 1 and 2 of the J1 (S SET UP) header. (Refer to Figure 7)

S IN-

•

Figure 6

15

Page 22

Caution: When configured for a 10mA DC source input, the MX001 box expects a current limited 10 mA DC signal to be supplied by the sensor. Failure to limit this current to 10mA can damage the sensor input circuitry of the system. Current limiting can be accomplished by using an external limiting resistor of the appropriate value (which is dependent upon the sensor’s DC signal output voltage level). This resistor is connected between the S IN+ input of the MX001 box and the sensor. Sensor Output Voltage – 3V 10mA

Approximate Resistance =

J1

If the source is a 12V DC signal:

1

2

1

If the source is a 5V DC signal:

2

1

5

6 6

3

4

5

1

Figure 7

2

3

4

6

S SET UP

5

J1

6

S SET UP

1

16

4

S SET UP

1

If the source is a 10mA DC signal:

3

6 6

J1

Page 23

SENSORS THAT PROVIDE SWITCH CLOSURES OR RELAY TYPE OUTPUT:

3.

Strip off 2 ¼ inches of the sensor cable’s outer jacket

4.

Strip the insulation off each cable wire ¼ of an inch.

5.

Feed the sensor cable through the small strain relief.

6.

Insert one of the sensors signal output wires into the COMMON terminal and secure the wire by turning the terminal’s screw clockwise. (Refer to the MX001 box or to Figure 8 for the order of the terminals for the sensor wires.)

7.

Insert and secure the sensor’s other signal output wire into the S IN- terminal.

8.

Secure the cable by turning the strain relief’s domed sealing nut clockwise until tight.

9.

Position the jumper on pins 5 and 6 of the J1 (S SET UP) header. (Refer to Figure 9).

S IN+

S IN-

+12V OUT

Open the terminals in the sensor terminal block by turning each screw counterclockwise until there is enough space to insert wires.

A IN-

2.

COMMON

Make sure power is not being applied to the unit.

A IN+

1.

Figure 8 J1

1

1

2

3

4

S SET UP

5

6

6

Figure 9

17

Page 24

LOW VOLTAGE SELF-CONTAINED DC SENSORS WITH A CURRENT SINKING OUTPUT

Strip off 2 ¼ inches of the sensor cable’s outer jacket.

4.

Strip the insulation off each cable wire ¼ of an inch.

5.

Feed the sensor cable through the small strain relief.

6.

Inserts the sensor’s DC common wire into the COMMON terminal and secure the wire by turning the terminals’s screw clockwise. (Refer to the MX001 box or to Figure 10 for the order of the terminals for the sensor wires.)

7.

Insert and secure the sensor’s +DC power input wire into the +12V OUT terminal.

8.

Insert and secure the sensor’s signal output wire into the S INterminal.

9.

Secure the cable by turning the strain relief’s domed sealing nut clockwise until tight.

10.

Position the jumper on pins 5 and 6 of the J1 (S SET UP) header. (Refer to Figure 11).

S IN-

+12V OUT

3.

S IN+

Open the terminals in the sensor terminal block by turning each screw counterclockwise until there is enough space to insert wires.

COMMON

2.

A IN-

Make sure power is not being applied to the unit.

A IN+

1.

Figure 10 J1

1

1

2

3

4

S SET UP Figure 11

18

5

6

6

Page 25

LOW VOLTAGE SELF-CONTAINED DC SENSORS WITH A CURRENT SOURCING OUTPUT 1.

Make sure power is not being applied to the unit.

2.

Open the terminals in the sensor terminal block by turning each screw counterclockwise until there is enough space to insert wires.

3.

Strip off 2 ¼ inches of the sensor cable’s outer jacket.

4.

Strip insulation off each cable wire ¼ of an inch.

5.

Feed the sensor cable through the small strain relief.

6.

Connect a small jumper wire between the COMMON and the S INterminals. Secure the jumper wire in the S IN- terminal by turning the terminal’s screw clockwise. (Refer to the MX001 box or to Figure 12 for the order of the terminals for the sensor wires.

7.

Connect the sensor’s DC common wire to the COMMON terminal and secure the sensor and jumper wire by turning the terminal’s screw clockwise.

8.

Insert and secure the sensor’s +DC power input wire into the +12V OUT terminal.

9.

Insert and secure the sensor’s sourcing output wire into the S IN+ terminal.

10.

Secure the cable by turning the strain relief’s domed sealing nut clockwise until tight.

11. Position the jumper on pins 1 and 2 of the J1 (S SET UP) header.

S IN+

+12V OUT

S IN-

COMMON

A IN-

A IN+

(Refer to Figure 13).

Figure 12 J1

1

1

2

3

4

S SET UP

5

6

6

Figure 13

19

Page 26

“UNIVERSAL” SELF-CONTAINED SENSORS THAT PROVIDE A SINGLE POLE/DOUBLE THROW (SPDT) RELAY OUTPUT 1.

Make sure the “universal” sensor can operate on +12 volts DC at 200mA or less. If so, then the MX001 box can supply the +12 volts necessary to power the “universal” sensor.

2.

Make sure power is not being applied to the unit.

3.

Open the terminals in the sensor terminal block by turning each screw counterclockwise until there is enough space to insert wires.

4.

Strip 2 ¼ inches of the sensor cable’s outer jacket

5.

Strip the insulation off each cable wire ¼ of an inch.

6.

Feed the sensor cable through the small strain relief.

7.

Insert the sensor’s +DC power input wire into the +12V OUT terminal and secure the wire by turning the terminal’s screw clockwise. (Refer to the MX001 box or to Figure 14 for the order of the terminals for the sensor wires.)

8.

Insert the sensor’s –DC or common power input wire and the relay output common signal wire into the COMMON terminal and secure both wires.

9.

Determine from the literature supplied with your sensor which sensor relay output makes contact with its common terminal when an object is sensed. If the output cannot be determined, go on to Step 10. Otherwise, skip to Step 11.

10. Temporarily apply power to the MX001 box to activate the sensor and then determine with a continuity tester or ohm meter which relay output (the normally closed [NC] or the normally open [NO] output) make contact with the COMMON terminal when the sensor “sees” the object to be scanned. 11. Remove any power applied to the MX001 (in Step 10) and connect and secure the relay output wire previously determined to the S IN- terminal. (The other relay output wire may be cut off or connected to the MX001 COMMON terminal if desired).

20

Page 27

“UNIVERSAL” SELF-CONTAINED SENSORS THAT PROVIDE A SINGLE POLE/DOUBLE THROW (SPDT) RELAY OUTPUT (CONTINUED) 12. Secure the cable by turning the strain relief’s domed sealing nut clockwise until tight.

+12V OUT

S IN+

S IN-

COMMON

A IN-

A IN+

13. Position the jumper on pins 5 and 6 of the J1 (S SET UP) header. (Refer to Figure 15).

Figure 14

J1

1

1

2

3

4

S SET UP

5

6

6

Figure 15

21

Page 28

SENSORS POWERED INDEPENDENTLY WHICH PROVIDE EITHER 12V, 5V OR A 10MA DC OUTPUT SIGNAL WITH A SENSOR ALARM 1.

Make sure power is not being applied to the unit.

2.

Open the terminals in the sensor terminal block by turning each screw counterclockwise until there is enough space to insert wires.

3.

Strip off 2 ¼ inches of the sensors cable’s outer jacket.

4.

Strip the insulation off each cable wire ¼ of an inch.

5.

Feed the sensor cable through the small strain relief.

6.

Insert the sensor’s DC common (or negative) output wire into the S IN- terminal block and secure the wire by turning the terminal’s screw clockwise. (Refer to the MX001 box or to Figure 16 for the order of the terminals for the sensor wires.)

7.

Insert and secure the sensor’s positive output wire into the S IN+ terminal.

8.

Insert and secure the sensor’s alarm DC common (or negative) output wire into the A IN- terminal and the sensor’s alarm positive output wire into the A IN+ terminal.

9.

Secure the cable by turning the strain relief’s domed sealing nut clockwise until tight.

Figure 16

22

+12V OUT

S IN+

S IN-

COMMON

A IN-

A IN+

10. Depending upon your sensor’s output, perform one of the of the following steps:

Page 29

SENSORS POWERED INDEPENDENTLY WHICH PROVIDE EITHER 12V, 5V OR A 10MA DC OUTPUT SIGNAL WITH A SENSOR ALARM (CONTINUED) •

For 12V DC output signals, position the jumpers on pins 1 and 2 of the J1 (S SET UP) and J2 (A SET UP) headers. (Refer to Figure 17)

•

For 5V DC output signals, position the jumpers on pins 3 and 4 of the J1 (S SET UP) and J2 (A SET UP) headers. Refer to Figure 17)

•

For 10mA DC output signals, position the jumpers on pins 4 and 5 of the J1 (S SET UP) and J2 (A SET UP) headers. (Refer to Figure 17)

Caution:

When configured for a 10mA DC source input, the MX001 box expects a current limited 10 mA DC signal to be supplied by the sensor. Failure to limit this current to 10 mA can damage the sensor input circuitry of the system.

Current limiting can be accomplished by using external limiting resistors of an appropriate value (which are dependent upon the sensor’s DC signal output voltage level). One resistor is connected between the S IN+ input of the MX001 box and the sensor. The other resistor is connected between the A IN+ input of the MX001 box and the sensor (for the sensor alarm circuit). Sensor Output Voltage – 3V 10 mA

Approximate Resistance =

If the source is a 12 V DC Signal: 1

A SET UP 1

2

3

4

5

1

6 J2

1

A SET UP 1

2

3

4

J1

6

1

5

2

3

4

4

5

6

S SET UP

6 J1

1

6

A SET UP 1

3

6

J2 1

2

2

1

3

4

5

6

S SET UP

6

6 5

J1 1

6 J2

1

2

3

4

S SET UP

5

6 6

Figure 17

23

Page 30

SENSORS THAT PROVIDE SWITCH CLOSURES OR RELAY TYPE OUTPUT WITH A SENSOR ALARM 1.

Make sure power is not being applied to the unit.

2.

Open the terminals in the sensor terminal block by turning each screw counterclockwise until there is enough space to insert wires.

3.

Strip off 2 ¼ inches of the sensor cable’s outer jacket.

4.

Strip the insulation off each cable wire ¼ of an inch.

5.

Feed the sensor cable through the small strain relief.

6.

Insert one of the sensor’s signal output wires and one of the sensor’s alarm output wires into the COMMON terminal and secure the wires by turning the terminal’s screw clockwise. (Refer to the MX001 box or to Figure 18 for the order of the terminals for the sensor wires.)

7.

Insert and secure the sensor’s remaining signal output wire into the S IN- terminal.

8.

Insert and secure the sensor’s remaining alarm output wire into the A IN- terminal.

9.

Secure the cable by turning the strain relief’s domed sealing nut clockwise until tight.

+12V OUT

S IN+

S IN-

COMMON

A IN-

A IN+

10. Position the jumpers on pins 5 and 6 of the J1 (S SET UP) and J2 (A SET UP) headers. (Refer to Figure 19)

Figure 18 1

A SET UP 1

2

3

4

6 5

6 J1 J2

1 1

2

3

4

S SET UP

Figure 19

24

5

6 6