For the Metrologic MX001
Page 11
CONFIGURING THE MX001 FOR 115 OR 230 VOLT OPERATION Before applying power to the MX001, it must first be configured for either 115 or 230 volt operation as required. This is accomplished by using the voltage selector switch and the installation of the proper fuses. Refer to one of the procedures on the following pages that apply to your voltage requirement to learn which fuses should be inserted into the F1 and F2 fuse holders. (Refer to Figure 3) If fuse replacement becomes necessary, replace with the same type of fuse originally supplied. Damage to the unit may result if the same type of fuse is not used. F2 Control
F1 TRIAC
230V
115V
Figure 3
USA: 115V OPERATION 1. Move the voltage selector to the right with a small screwdriver so that the 115V legend shows in the window. 2. Open the fuse kit and remove the following: • • •
(2) Gray Fuse Holder Caps (1) 10 Amp 250V Fast Acting ¼ x 1 ¼ Inch Fuse (1) 1/8 Amp 250V Slow Blow ¼ X 1 ¼ Inch Fuse
3. Press the end of the 10 Amp fuse into one of the gray fuse holder caps until it seats. 4. Insert the fuse and cap into the F1 TRIAC fuse holder with the screwdriver slot pointing toward the power transformer. 5. Using a small screw driver, press the cap down into the fuse holder body and turn the cap ¼ turn clockwise to lock the cap in place. This results in the cap slot pointing toward the top and bottom of the box. 5
Page 12
USA: 115V OPERATION (CONTINUED) 6. Press the end of the 1/8 Amp fuse into the other gray fuse holder cap unitl it seats. 7. Insert the fuse and cap into the F2 control fuse holder with the screwdriver slot pointing toward the power transformer. 8. Using a small screwdriver, press the cap down into the fuse holder body and turn the cap ¼ turn clockwise to the lock the cap in place. This results in the cap slot pointing toward the top and bottom of the box.
USA: 230V OPERATION 1. Move the voltage selector to the left with a small screwdriver so that the 230V legend shows in the window. 2. Open the fuse kit and remove the following: • (2) Gray Fuse Holder Caps • (1) 10 Amp 250V Fast Acting ¼ x 1 ¼ Inch Fuse • (1) 1/16 Amp 250V Slow Blow ¼ x 1 ¼ Inch Fuse 3. Press the end of the 10 Amp fuse into one of the gray fuse holder caps until seals. 4. Insert the fuse and cap into the F1 TRIAC fuse holder with the screwdriver slot pointing toward the power transformer. 5. Using a small screwdriver, press the cap down into the fuse holder body and turn the cap ¼ turn clockwise to lock the cap in place. This results in the cap slot pointing toward the top and bottom of the box. 6. Press the end of the 1/16 Amp fuse into the other gray fuse holder cap until it seats. 7. Insert the fuse and cap into the F2 control fuse holder with the screwdriver slot pointing toward the power transformer. 8. Using a small screwdriver, press the cap down into the fuse holder body and turn the cap ¼ turn clockwise to lock the cap in place. This results in the cap slot pointing toward the top and bottom of the box. 6
Page 13
EUROPE/ASIA: 230V OPERATION 1. Move the voltage selector to the left with a small screwdriver so that the 230V legend shows in the window. 2. Open the fuse kit and remove the following: • (2) Black Fuse Holder Caps • (1) 6.3 Amp 250V Fast Acting, High Interrupt 5 x 20 mm Fuse • (1) 50ma 250V Time Delay 5 x 20 mm Fuse 3. Press the end of the 6.3 Amp fuse into one of the black fuse holder caps until it seats. 4. Insert the fuse and cap into the F1 TRIAC fuse holder with the screwdriver slot pointing toward the power transformer. 5. Using a small screwdriver, press the cap down into the fuse holder body and turn the cap ¼ turn clockwise to lock the cap in place. This results in the cap slot pointing toward the top and bottom of the box. 6. Press the end of the 50mA fuse into the other black fuse holder cap until it seats. 7. Insert the fuse and cap into the F2 control fuse holder with the screwdriver slot pointing toward the power transformer. 8. Using a small screwdriver, press the cap down into the fuse holder body and turn the cap ¼ turn clockwise to lock the cap in place. This results in the cap slot pointing toward the top and bottom of the box.
7
Page 14
EUROPE/ASIA: 115V OPERATION 1. Move the voltage selector to the right with a small screwdriver so that the 115V legend shows in the window. 2. Open the fuse kit and remove the following: • • •
(2) Black Fuse Holder Caps (1) 6.3 Amp 250V Fast Acting, High Interrupt 5 x 20mm Fuse (1) 125mA 250V Time Delay 5 x 20mm Fuse
3. Press the end of the 6.3 Amp fuse into one of the black fuse holder caps until it seats. 4. Insert the fuse and cap into the F1 TRIAC fuse holder with the screwdriver slot pointing toward the power transformer. 5. Using a small screwdriver, press the cap down into the fuse holder body and turn the cap ¼ turn clockwise to lock the cap in place. This results in the cap slot pointing toward the top and bottom of the box. 6. Press the end of the 125mA fuse into the other black fuse holder cap until it seats. 7. Insert the fuse and cap into the F2 control fuse holder with the screw driver slot pointing toward the power transformer. 8. Using a small screwdriver, press the cap down into the fuse holder body and turn the cap ¼ turn clockwise to lock the cap in place. This results in the cap slot pointing toward the top and bottom of the box.
8
Page 15
LOCATING THE THREE STRAIN RELIEFS AND THE SIGNAL CONNECTOR There are three strain reliefs and one 8-pin signal connector located on the bottom of the MX001 box. The two large strain reliefs on the left side allow the use of flexible cordage for MX001 power input and controlled power (TRIAC) output in that order. If your application requires the use of conduit for power wiring, these two strain reliefs can be easily removed and standard conduit fittings can be used in their place. The smaller strain relief is used to secure the signal/ power cable from the object sensor that is a user supplied part. The 8-pin signal connector is used to connect the MX001 box to the scanner through the scanner link cable.
CONNECTING EXTERNAL WIRING TO THE MX001 External wiring is connected to the MX001 by means of “lift clamp” terminal blocks. These blocks have an opening in their base that will accept a wire with ¼ inch of insulation removed. Connections are made by first turning the terminal’s binding screw counterclockwise with a small screwdriver which “opens” the terminal allowing it to accept the wire. The stripped wire is then inserted into the opening in the terminal and then clamped in place by turning the associated terminal screw clockwise until tight. There are two sets of terminal blocks inside the MX001. The larger set of 6 terminals on the left of the voltage selector switch handle the AC power wiring while the smaller set of 6 terminals on the right handle the sensor wiring. Two terminals mounted on the MX001 enclosure near the protective earthing symbol are intended to be used for ground connection of the AC power input cable and TRIAC controlled power output cable.
MX001 POWER REQUIREMENT The MX001 control box neither supplies nor draws operating power from the scanner to which it is connected. It contains an independent, regulated and totally isolated 12 volt DC power supply that is used to drive the (optocoupled) sensor and TRIAC signal circuit links to the scanner. Therefore, the MX001 must be powered from the AC line at all times to allow it to communicate with the scanner. 9
Page 16
CONNECTING THE AC POWER INPUT CABLE 1. Make sure power is not being applied to the power cable that is to be connected to the unit.
2. Open the terminals in the power terminal block by turning each screw counterclockwise until there is enough space to insert wires.
3. Strip off 1 ¾ inches of the power cable’s outer jacket. 4. Strip the insulation off each cable wire ¼ of an inch. 5. Feed the power cable through the first, large strain relief on the left. 6. Connect each wire to the appropriate locations noted in the table below and secure the wires in the terminal block and protective earthing terminal by turning each screw clockwise. (Refer to the MX001 box or to Figure 4 for the order of the terminals for the power wires.)
7. Secure the cable by turning the strain relief’s domed sealing nut
NEUTRAL
TRIAC OUT
LINE IN
Protective Earthing Terminals
NEUTRAL clockwise until tight.
Figure 4 NOTE: Do not connect any wires to the first terminal.
Terminal Block Neutral Line In Protective Earthing Terminals Ground
10
Cable Color in USA and Canada White Black Cable Color in USA and Canada Green
Cable Color in in Europe Blue Brown Cable Color in in Europe Yellow-Green
Page 17
CONNECTING THE TRIAC CONTROLLED POWER OUTPUT CABLE The MX001 box contains a power line TRIAC that acts as an electronic power output switch operated by the scanner and capable of controlling a current load of 6 amps in the USA. In Europe, the maximum current load supported is 5 Amps. The TRIAC controlled output voltage equals the line input voltage when the scanner activates the TRIAC. How the TRIAC will operate is defined by the HoloSet Program.
3.
Strip off 1 ¾ inches of the power output cable’s outer jacket.
4.
Strip the insulation off each cable wire ¼ of an inch.
5.
Feed the power output cable through the second large strain relief.
6.
Connect each wire to the appropriate locations noted in the table below and secure the wires in the terminal block and protective earthing terminal by turning each screw clockwise. (Refer to the MX001 box or to figure 5 for the order of the terminals for the TRIAC wires.) Protective Earthing Terminals
TRIAC OUT
Open the terminals in the TRIAC terminal block by turning each screw counterclockwise until there is enough space to insert wires.
NEUTRAL
2.
LINE IN
Make sure power is not being applied to the unit.
NEUTRAL
1.
Figure 5
Note: Do not connect any wires to the fourth terminal. Terminal Block Neutral Line In Protective Earthing Terminals Ground Caution:
Cable Color in USA and Canada White Black Cable Color in USA and Canada Green
Cable Color in in Europe Blue Brown Cable Color in in Europe Yellow-Green
Damage will occur to the unit if the TRIAC output is shorted.
11
Page 18
TEMPORARILY DISABLING THE TRIAC OUTPUT If, during set up or maintenance, there is a need to disable the TRIAC output of the MX001, simply remove the F1 TRIAC fuse. This disconnects the AC line voltage from the TRIAC circuitry and output terminal block, but leaves the TRIAC LED indicator active allowing checks to be made for TRIAC circuit activity without activating the TRIAC controlled device.
12
Page 19
SENSOR SUPPORT There are many different types of sensors available that will work with the MX001 control box. Common types: 1.
Sensors powered independently which provide either 12V, 5V or a 10mA DC output signal (sourcing type output).
2.
Sensors that provide switch closures or relay type outputs.
3.
Low voltage, self-contained DC sensors that provide current sourcing and/or sinking type outputs.
4.
“Universal” self-contained sensors that provide a single pole, double throw (SPDT) relay output.
In all cases, the sensor’s output signal or switch closure is expected to become active when an object has been sensed. The easiest sensor to use with the MX001 is a low voltage (a 10-30 volt) DC, self contained, sensor. The industrial control box can power this type of sensor with 12V DC at 200 mA maximum and will interface to either a (PNP) current sourcing, or (NPN) current sinking output. (Current sourced or sunk = 10 mA.) A switch closure (relay) type output is also supported. All output types are expected to become active when an object has been sensed. Additionally, some sensors also provide an “alarm” output that warns the user when sensing conditions are becoming marginal. This optional output is also supported through the MX001 and forces the scanner to emit a repetitive warning tone when the sensor’s alarm output becomes active. How the sensor interacts with the scanner depends upon which sensor options were chosen in the HoloSet program. Refer to that manual for further details.
13
Page 20
CONNECTING THE SENSOR Reference the documentation that came with your sensor to determine the function of each sensor wire. Then, refer to one of the procedures on the following pages that apply to your sensor for information on how to hook up the appropriate wires and position the configuration jumper on the appropriate pins of its header. If your sensor supports the alarm function, begin looking for the procedure for your sensor on page 22.
TEMPORARILY DISABLING THE SENSOR AND/OR SENSOR ALARM If, during set up or maintenance, there is a need to disable the sensor and/or sensor alarm inputs of the MX001, proceed as follows: •
To disable the sensor, position the J1 (S SET UP) jumper on pins 2 and 3 of its header.
•
To disable the sensor alarm, position the J2 (A SETUP) jumper on pins 2 and 3 of its header.
These procedures disconnect the sensor’s output signals from the MX001’s input circuitry without physically disconnecting any sensor wiring.