Page 41
TROUBLESHOOTING (CONTINUED) TRIAC Output Active with Red TRIAC LED off: Tests for AC power output from the TRIAC should only be made when a device or load is connected between the TRIAC OUT and NEUTRAL terminals of the TRIAC terminal block. Attempting to measure output voltage with nothing connected to the TRIAC terminal block will result in a false output reading which may show partial or full line voltage present at all times. This is due to the TRIAC snubber circuit in the MX001 that protects the TRIAC from surge damage due to inductive loads. This circuit produces a small amount of AC output (5mA) at the TRIAC terminal block that can be measured when no load is connected there but is of no consequence otherwise. To test properly for AC power output from the TRIAC, temporarily connect a 60W light bulb in a wired test socket to the TRIAC output. This lamp will provide a proper load for the TRIAC. If the bulb lights when the red LED TRIAC indicator is OFF, then MX001 circuit damage is indicated as the problem. The unit can be damaged if the TRIAC output is accidentally shorted. No Sensor Input Indication (Red S in LED does not light): 1.
Review the documentation that came with your sensor to learn the type of output the sensor provides. Review the MX001 manual and find the set up procedure that applies to your sensor. Check for proper connection of the sensor to the MX001 sensor terminal block plus proper positioning of the S set up jumper J1. (Depends upon sensor type in use.)
2.
Check your sensor for output indication. Most sensors have a small indicator on them or their controller that lights when the sensor output is active. Make sure the sensor is active when expected.
3.
Check the positioning of the sensor making sure it is oriented correctly.
4. Check sensor gain/sensitivity adjustment for correctness. Most sensors provide this adjustment to adapt to various sensing conditions. Check to see if the gain/sensitivity is not set too low in diffuse proximity type sensors or not set too high in beam break type sensors. Review the documentation that came with your sensor to learn how to make this adjustment correctly.
5. Make sure the MX001 scanner link cable is connected to both the scanner and the MX001.
35
Page 42
TROUBLESHOOTING (CONTINUED) Reversed Sensor Input Indication (Red S in LED goes off when object is sensed): 1.
Some sensors provide the option of output activation when they sense or do not sense an object. Having the sensor set up to produce an output when it does not sense an object will result in reversed sensing conditions. The MX001 expects to receive an active output signal from the sensor (source voltage/current or switch closure) when the object to be scanned is being sensed. Review the documentation that came with your sensor to learn what type of output it provides and how to configure it.
2.
Some sensors that provide switch closure type output provide both normally open (NO) and normally closed (NC) switched outputs. If the sensor as connected is providing a reversed sensing condition (switch closure when no object is being sensed), disconnect the switched output used and connect the other switched output in its place.
3.
If the sensor in use provides an output only when an object is not being sensed and cannot be configured otherwise, contact Metrologic for special instructions on how to adapt to this type of sensor.
Erratic Sensor Operation:
36
1.
Check the sensor wiring for correct connection and security at the sensor terminal block. (wires must be stripped before insertion into the terminal block and terminal block screws must be tight, clamping the stripped wire firmly in the block.)
2.
Check the positioning of the sensor making sure it is oriented correctly and not dirty.
3.
Check sensor gain/sensitivity adjustments for correctness. Most sensors provide this adjustment to adapt to various sensing conditions. Review the documentation that came with your sensor to learn how to make this adjustment correctly. If this adjustment is made incorrectly, the sensor will act erratically.
Page 43
TROUBLESHOOTING (CONTINUED) Continuous Sensor Input Indication (Red S IN LED continuously on): 1.
Review the documentation that came with your sensor to learn the type of output the sensor provides. Review the MX001 manual and find the set up procedure that applies to your sensor. Check for proper connection of the sensor to the MX001 sensor terminal block plus proper positioning of the S set up jumper at J1. (Depends upon sensor type in use.)
2.
Check your sensor for output indication. Most sensors have a small indicator on them or their controller that lights when the sensor output is active. Make sure the sensor is not providing a continuous output.
3.
Some sensors provide the option of output activation when they sense or do not sense an object. Having the sensor set up to produce an output when it does NOT sense an object will result in continuous sensor output when the sensor is idle. Review the documentation that came with your sensor to learn what type of output it provides and how to configure it. The MX001 box expects to receive an active output signal from the sensor (source voltage/current or switch closure) when an object to be scanned is being sensed.
4.
Check sensor gain/sensitivity adjustment for correctness. Most sensors provide this adjustment to adapt to various sensing conditions. Check to see if the gain/sensitivity is not set too low in beam break type sensors or not set to high in diffuse proximity type sensors. Review the documentation that came with your sensor to learn how to make this adjustment correctly.
Continuous Sensor Alarm Indication (Red A IN LED continuously on): 1.
Review the documentation that came with your sensor to learn the type of alarm output the sensor provides. Review the MX001 manual and find the set up procedure that applies to your sensor. Check for proper connection of the sensor alarm output to the MX001 sensor terminal block plus proper positioning of the A Set Up jumper at J2. The MX001 expects to receive an active alarm output signal from the sensor (source voltage/current or switch closure) when sensing conditions have become marginal.
2.
If the sensor in use provides an alarm output only when sensor conditions are not marginal and cannot be configured otherwise, contact Metrologic for special instructions on how to adapt to this type of sensor.
37
Page 44
TROUBLESHOOTING (CONTINUED) Erratic Sensor Alarm Indication (Red A IN LED blinks): 1.
Check the positioning of the sensor to make sure it is oriented correctly.
2.
Check to see if the sensor is dirty and clean it if necessary.
3. Check sensor gain/sensitivity adjustment for correctness. Most sensors provide this adjustment to adapt to various sensing conditions. Review the documentation that came with your sensor to learn how to make this adjustment correctly. If this adjustment is made incorrectly, the sensor may produce an erratic alarm output. Scanner cannot be placed in program mode using HoloSet label: 1.
Disconnect then reconnect power to the scanner. Enter scanner program mode by choosing Enter Program Mode from the HoloSet Main Menu.
2.
If the scanner has been programmed for sensor support, the scanner will not scan any label including the HoloSet label unless a sensor is connected to the MX001 box and activated.
3.
If the scanner has been programmed to support DTR, the scanner will not scan any label including the HoloSet label unless the DTR input is active.
Scanner cannot be placed in program mode using HoloSet menu:
38
1.
Disconnect then reconnect power to the scanner. Retry entering program mode by choosing Enter Program Mode from the HoloSet Main Menu.
2.
Check to see if the HoloSet communication cable is plugged into your PC correctly.
3.
Make sure the correct COM option (COM 1 or 2 as required) is being used.
Page 45
TROUBLESHOOTING (CONTINUED) Operational Check Out Procedure for the MX001 Box: The following procedure provides a basic test of the MX001 hardware and confirms effective communication with the HoloSet program. This quick test should be preformed before the MX001 box has been configured by the HoloSet program for its final application. These steps are not required for proper installation and application programming of the MX001 box. 1.
Do not connect a sensor to the MX001 at this time. Tighten each sensor terminal block screw by turning each screw clockwise.
2.
Temporarily place both S and A SET UP jumpers (J1 and J2) at positions 5 and 6.
3.
Connect a standard 60W light bulb in a wired test socket to the TRIAC terminal block at the TRIAC OUT and NEUTRAL terminals. This lamp will act as a load for the TRIAC. (Do Not try to monitor TRIAC output without a load connected.)
4.
Connect the MX001 box to the scanner with the scanner link cable.
5.
Apply power to both the MX001 and the scanner. The green LED inside the MX001 should light.
6.
If a volt meter is available, measure the DC output voltage between the +12V OUT and COMMON terminals on the sensor terminal block. This voltage should be between 11.5 and 12.5 volts DC.
7.
Temporarily program the TECH options of the scanner using HoloSet for the following: • • • • •
Support Line Sensor Support Line Sensor Alarm Support TRIAC TRIAC Normally On Activate on No Read
8.
After programming, the MX001’s red TRIAC LED should light and the test light bulb should be on.
9.
Short the S IN- terminal screw to the COMMON terminal screw with a short piece of wire. The red S IN LED should light and the test light bulb connected to the TRIAC output should flash off then back on.
39
Page 46
TROUBLESHOOTING (CONTINUED) 10. Short the A IN- terminal screw to the COMMON terminal screw with a short piece of wire. The red A IN LED should light and the scanner should emit a repetitive warning tone as long as this connection is maintained. 11. Disconnect then reconnect power to the scanner. Enter scanner program mode by choosing Enter Program Mode from the HoloSet Main Menu. (Do not try to use the HoloSet bar code label at this time) DISABLE all TECH options then re-program the scanner. This neutralizes the test program disabling the unconnected sensor inputs and turns the TRIAC output off. 12. If needed, the scanner can now be programmed for your particular application.
40
Page 47
LIMITED WARRANTY & DISCLAIMER The MX001 interface is manufactured by Metrologic at its Blackwood, New Jersey, USA facility. The MX001 interface has a two (2) year limited warranty from the date of manufacture. Metrologic warrants and represents that all MX001 interface is free of all defects in material, workmanship and design, and have been produced and labeled in compliance with all applicable US Federal, state and local laws, regulations and ordinances pertaining to their production and labeling. This warranty is limited to repair, replacement of Product or refund of Product price at the sole discretion of Metrologic. Faulty equipment must be returned to the Metrologic facility in Blackwood, New Jersey, USA or Puchheim, Germany. To do this, contact Metrologic’s Customer Service/Repair Department to obtain a Returned Material Authorization (RMA) number. In the event that it is determined that the equipment failure is covered under the warranty, Metrologic shall, as its sole option, repair the Product or replace the Product with a functionally equivalent unit and return such repaired or replaced Product without charge for service or return freight, whether distributor, dealer/reseller, or retail consumer, or refund an amount equal to the original purchase price. This limited warranty does not extend to any Product which, in the sole judgement of Metrologic, has been subjected to abuse, misuse, neglect improper installation, or accident, nor any damage due to use or misuse produced from integration of the Product into any mechanical, electrical or computer system. The warranty is void if the case of Product is opened by anyone other than Metrologic’s repair department or authorized repair centers. THIS LIMITED WARRANTY, EXCEPT AS TO TITLE, IS IN LIEU OF ALL OTHER WARRANTIES OR GUARANTEES, EITHER EXPRESS OR IMPLIED, AND SPECIFICALLY EXCLUDES, WITHOUT LIMITATION, WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE UNDER THE UNIFORM COMMERCIAL CODE, OR ARISING OUT OF CUSTOM OR CONDUCT. THE RIGHTS AND REMEDIES PROVIDED HEREIN ARE EXCLUSIVE AND IN LIEU OF ANY OTHER RIGHTS OR REMEDIES. IN NO EVENT SHALL METROLOGIC BE LIABLE FOR ANY INDIRECT OR CONSEQUENTIAL DAMAGES, INCIDENTAL DAMAGE, DAMAGES TO PERSON OR PROPERTY, OR EFFECT ON BUSINESS OR PROPERTY, OR OTHER DAMAGES OR EXPENSES DUE DIRECTLY OR INDIRECTLY TO THE PRODUCT, EXCEPT AS STATED IN THIS WARRANTY. IN NO EVENT SHALL ANY LIABILITY OF METROLOGIC EXCEED THE ACTUAL AMOUNT PAID TO METROLOGIC FOR THE PRODUCT. METROLOGIC RESERVES THE RIGHT TO MAKE ANY CHANGES TO THE PRODUCT DESCRIBED HEREIN. Corporate Headquarters Metrologic Instruments, Inc. 90 Coles Road Blackwood, NJ 08012-4683 Germany Metrologic Instruments GmbH Dornierstrasse 2 82178 Puchheim b. Munich, Germany
Customer Service: 1-800-ID-METRO Tel: 856-228-8100 Fax: 856-228-6673 Email: info@metrologic.com Website: www.metrologic.com Tel: 49-89-89019-0 Fax: 49-89-89019-200 Email: info@europe.metrologic.com
41
Page 48
NOTICES Notice This equipment has been tested and found to comply with limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference, in which case the user will be required to correct the interference at his own expense. Any unauthorized changes or modifications to this equipment could void the users authority to operate this device. Notice This Class A digital apparatus complies with Canadian ICES-003. Remarque Cet appareil numérique de la classe A est conformé a la norme NMB-003 du Canada.
42
Page 49
NOTICES (CONTINUED) European Standard EN 55022 Warning This is a class A product. In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures.
Funkstöreigenschaften nach EN 55022` Warnung! Dies ist eine Einrichtung der Klasse A. Diese Einrichtung kann im Wohnbereich Funkstörungen verursachen; in diesem fall kann vom Betrieber verlangt werden, angemessene Maßnahmen durchführen.
Standard Europeo EN 55022 Attenzione Questo e’ un prodotto di classe A. Se usato in vicinanza di residenze private potrebbe causare interferenze radio che potrebbero richiedere all’utilizzatore opportune misure.
Attention Ce produit est de classe “A”. Dans un environnement domestique, ce produit peut être la cause d’interférences radio. Dans ce cas l’utiliseteur peut être amené à predre les mesures adéquates.
43
Page 50
INDEX C Cable pin outs Link cable...................................3 Connector 19-pin ................................30, 31 8-pin ..................................30, 31 D Dimensions ...................................32 F Fuse Holder F1 TRIAC ...............3, 5-8, 31, 34 F2 control .....................3, 6-8, 34 H HoloSet....................1, 11, 13, 38, 39 I Indicator green +12V (D1) ..................4, 37 LED .................................3, 4, 37 red TRIAC (D2) ..................4, 37, red S IN (D3) .................4, 36, 37 red A IN (D4) .................4, 37, 38 status ........................................4 J Jumper disable sensor/sensor alarm ....14 J1 3 J1 and J2 positions 1and2 .23,26 J1 and J2 positions 2 and 3 ....14 J1 and J2 positions 3 and 4 .....23 J1 and J2 positions 4 and 5 ....23 J1 and J2 positions 5 and 6 ......... ...........................................24, 25 J1 position 1 and 2 ............16, 19 J1 position 2 and 3 ..................14 J1 position 3 and 4 ..................16 J1 position 4 and 5 ..................16 J1 positions 5 and 6 ....17, 18, 21 J2 ..............................................3 O Operational Check ........................39
P Power controlled output ............. 3, 11 line input ......................... 3, 10 Power Cable inserting .............................. 10 S Scanner link cable ............................ 38 Sensor 10mA .......................13, 16, 23 12V ..........................13, 16, 23 5V ............................13, 16, 23 current sinking output .... 13,18 current sourcing output . 19, 26 disable .......................... 12, 14 relay type output ................. 13 supported types .................. 13 switch closure ......1, 13, 17, 24 universal ....................... 28, 29 Sensor Alarm disable .................................. 3 Sensor Cable inserting ......15, 17, 18, 19, 20, ...................................... 22, 24 Specifications ........................... 32 Strain relief ..... 9-11, 15, 17-20, 22 T Terminal block power .................................... 3 sensor ................................... 3 TRIAC ................................... 3 Transformer power .................................... 3 TRIAC disable ............................... 14 TRIAC Cable inserting .............................. 11 Troubleshooting .................. 33-40 V Voltage 115V ................................. 5, 8 230V ................................. 6, 7 W Weight ...................................... 32