For the Intermec DCS-300
Page 151
Connecting to the 9180 and the Intermec CrossBar Network
7
To configure the server to work with an Intermec controller 1. From the main menu, choose the type of communication you are using to connect the server to the host. 2. Choose Downline Network. Two buttons, Connection Points and Downline Devices, appear. 3. Choose Connection Points. The Connection Point List dialog box appears.
4. Choose Add, Edit, or Delete. If you choose Add, the Add a Downline Connection Point dialog box appears.
5. Choose the controller that you want to add and then choose Add. The setup dialog box for the controller appears. 6. Configure the controller. For help, see “About the Controller Parameters” in the next section and then see the appropriate section for your controller. 7. Set any time parameters for the controller. For help, see “Setting the Time Parameters” later in this chapter.
7-5
Page 152
DCS 300 User’s Manual
8. (9180 v2.0 only) Define a default host for each type of host that the 9180 devices will communicate with through the 9180 controller. For help, see “Defining Default Hosts” later in this chapter. 9. Choose OK to save your changes and return to the Connection Point List dialog box. Choose Close to return to the main menu.
About the Controller Parameters When you configure an Intermec controller, you may need to configure the communication parameters, set the hot standby timeout, define the integrity mode, set time parameters, and enable the correct Multi-Drop port. You must make sure that any communication parameters that you define for the serial port on the server are the same as the parameters set for the serial port on the Intermec controller. Time Parameters These optional parameters let you set time broadcast and time append parameters for the Intermec controller. These time parameters synchronize the Intermec controllers with their devices. In the System Parameters dialog box, you can set a time synchronization parameter that synchronizes the time on the server with its Intermec controllers. For more help, see “Setting the Time Parameters” later in this chapter.
Adding a 9154 Controller •
7-6
From the Add a Downline Connection Point dialog box, choose 9154 and then choose Add. The Configure Controller: 9154 dialog box appears.
Page 153
Connecting to the 9180 and the Intermec CrossBar Network
Field
Description
Value
Default
Serial port
The communications port to which the 9154 controller is connected.
COM1, COM2
COM1
Baud rate
The baud rate at which the serial port communicates.
Predefined
9600
LRC enabled
This check box determines if the longitudinal redundancy check character is appended to data transmitted by a device.
Check, Clear
Clear
Parity
The type of self-checking you want to use when sending data.
Even, Odd, None
Even
Data bits
The number of bits to use for setting communications protocol.
7, 8
7
Stop bits
The number of bits to use for setting communications protocol.
1, 2
1
Hot Standby Timeout
The number of seconds the server waits after delivering a transaction to the 9154 controller to receive an acknowledgment for the transaction.
1 to 9999
40
Faster, Safer
Faster
7
If it does not receive an acknowledgment, the server writes all transactions for the 9154 to a Hot Standby file. The 9154 receives its transactions from this file either when it sends an acknowledgment to the most recently delivered transaction or when it sends a system transaction. Before the 9154 becomes interactive again, it receives all the transactions, from oldest to newest, that are in its Hot Standby file. Integrity mode
This mode determines the amount of transaction verification that the server performs. In Faster mode, the server acknowledges the transaction as soon as it receives the transaction from 9154 controller. In Safer mode, the server acknowledges the transaction only after it is stored in a Hot Standby file. Transaction throughput is slower because the server cannot accept another transaction from the 9154 until it verifies the previous one.
7-7
Page 154
DCS 300 User’s Manual
Field
Description
Value
Default
Transactions held in volatile memory
The number of transactions the server keeps in volatile RAM before it begins to write them to a Hot Standby file.
None, Unlimited, Maximum
Maximum 50 m, n, o, p p
Choose None if you want the transaction always written to the file. Choose Unlimited if you do not want the transaction written to the file unless the time you set for the Hot Standby timeout expires. Choose Maximum and enter a maximum number of transactions. When the server has this number of transactions in RAM, it writes them to a file. Multi-Drop Enabled
7-8
The Multi-Drop line that the 9154 controller uses.
Page 155
Connecting to the 9180 and the Intermec CrossBar Network
7
Adding a 9161 Controller •
From the Add a Downline Connection Point dialog box, choose 9161-01 or 9161-02 and then choose Add. The Configure Controller: 9161 dialog box appears.
Field
Description
Value
Default
Serial port
The communications port to which the 9161 controller is connected.
COM1, COM2
COM1
Baud rate
The baud rate at which the serial port communicates.
Predefined
9600
LRC enabled
This check box determines if the longitudinal redundancy check character is appended to data transmitted by a device.
Check, Clear
Clear
Parity
The type of self-checking to use when sending data.
Even, Odd, None
Even
Data bits
The number of bits to use for setting communications protocol.
7, 8
7
Stop bits
The number of bits to use for setting communications protocol.
1, 2
1
7-9
Page 156
DCS 300 User’s Manual
Field
Description
Value
Default
Hot Standby Timeout
The number of seconds the server waits after delivering a transaction to the 9161 controller to receive an acknowledgment for the transaction.
1 to 9999
40
Faster, Safer
Faster
None, Unlimited, Maximum
Maximum 50 m, n, o, p p
If it does not receive an acknowledgment, the server writes all transactions for the 9161 to a Hot Standby file. The 9161 receives its transactions from this file either when it sends an acknowledgment to the most recently delivered transaction or when it sends a system transaction. Before the 9161 becomes interactive again, it receives all the transactions, from oldest to newest, that are in its Hot Standby file. Integrity mode
This mode determines the amount of transaction verification the server performs. In Faster mode, the server acknowledges the transaction as soon as it receives the transaction from 9161 controller. In Safer mode, the server acknowledges the transaction only after it is stored in a Hot Standby file. Transaction throughput is slower because the server cannot accept another transaction from the 9161 until it verifies the previous one.
Transactions held in volatile memory
The number of transactions the server keeps in volatile RAM before it begins to write them to a Hot Standby file. Choose None if you want the transaction always written to the file. Choose Unlimited if you do not want the transaction written to the file unless the time you set for the Hot Standby timeout expires. Choose Maximum and enter a maximum number of transactions. When the server has this number of transactions in RAM, it writes them to a file.
Multi-Drop Enabled
7-10
The Multi-Drop lines (up to four) that the 9161-02 controller supports. The 9161-01 controller does not support this feature.
Page 157
Connecting to the 9180 and the Intermec CrossBar Network
7
Adding a 9180 v1.x Controller •
From the Add a Downline Connection Point dialog box, choose 9180 v1.x and then choose Add. The Configure Controller: 9180 v1.x dialog box appears.
Field
Description
Value
Default
Serial port
The communications port to which the 9180 controller is connected.
COM1, COM2
COM1
Baud rate
The baud rate at which the serial port communicates.
Predefined
9600
LRC enabled
This check box determines if the longitudinal redundancy check character is appended to data transmitted by a device.
Check, Clear
Clear
Parity
The type of self-checking you want to use when sending data.
Even, Odd, None
Even
Data bits
The number of bits to use for setting communications protocol.
7, 8
7
Stop bits
The number of bits to use for setting communications protocol.
1, 2
1
7-11
Page 158
DCS 300 User’s Manual
Field
Description
Value
Default
Hot Standby Timeout
The number of seconds the server waits after delivering a transaction to the 9180 controller to receive an acknowledgment for the transaction.
1 to 9999
40
Faster, Safer
Faster
None, Unlimited, Maximum
Maximum 50
If it does not receive an acknowledgment, the server writes all transactions for the 9180 to a Hot Standby file. The 9180 receives its transactions from this file either when it sends an acknowledgment to the most recently delivered transaction or when it sends a system transaction. Before the 9180 becomes interactive again, it receives all the transactions, from oldest to newest, that are in its Hot Standby file. Integrity mode
This mode determines the amount of transaction verification the server performs. In Faster mode, the server acknowledges the transaction as soon as it receives the transaction from 9180 controller. In Safer mode, the server acknowledges the transaction only after it is stored in a Hot Standby file. Transaction throughput is slower because the server cannot accept another transaction from the 9180 until it verifies the previous one.
Transactions held in volatile memory
The number of transactions the server keeps in volatile RAM before it begins to write them to a Hot Standby file. Choose None if you want the transaction always written to the file. Choose Unlimited if you do not want the transaction written to the file unless the time you set for the Hot Standby timeout expires. Choose Maximum and enter a maximum number of transactions. When the server has this number of transactions in RAM, it writes them to a file.
7-12
Page 159
Connecting to the 9180 and the Intermec CrossBar Network
7
Adding a 9180 v2.0 Controller •
From the Add a Downline Connection Point dialog box, choose 9180 v2.0 and then choose Add. The Configure Controller: 9180 v2.0 dialog box appears.
Field
Description
Value
Default
Serial port
The communications port to which the 9180 controller is connected.
COM1, COM2
COM1
Baud rate
The baud rate at which the serial port communicates.
Predefined
9600
LRC enabled
This check box determines if the longitudinal redundancy check character is appended to data transmitted by a device.
Check, Clear
Clear
Parity
The type of self-checking you want to use when sending data.
Even, Odd, None
Even
Data bits
The number of bits to use for setting communications protocol.
7, 8
7
Stop bits
The number of bits to use for setting communications protocol.
1, 2
1
7-13
Page 160
DCS 300 User’s Manual
Field
Description
Value
Default
Hot Standby Timeout
The number of seconds the server waits after delivering a transaction to the 9180 controller to receive an acknowledgment for the transaction.
1 to 9999
40
Faster, Safer
Faster
None, Unlimited, Maximum
Maximum 50
If it does not receive an acknowledgment, the server writes all transactions for the 9180 to a Hot Standby file. The 9180 receives its transactions from this file either when it sends an acknowledgment to the most recently delivered transaction or when it sends a system transaction. Before the 9180 becomes interactive again, it receives all the transactions, from oldest to newest, that are in its Hot Standby file. Integrity mode
This mode determines the amount of transaction verification the server performs. In Faster mode, the server acknowledges the transaction as soon as it receives the transaction from 9180 controller. In Safer mode, the server acknowledges the transaction only after it is stored in a Hot Standby file. Transaction throughput is slower because the server cannot accept another transaction from the 9180 until it verifies the previous one.
Transactions held in volatile memory
The number of transactions the server keeps in volatile RAM before it begins to write them to a Hot Standby file. Choose None if you want the transaction always written to the file. Choose Unlimited if you do not want the transaction written to the file unless the time you set for the Hot Standby timeout expires. Choose Maximum and enter a maximum number of transactions. When the server has this number of transactions in RAM, it writes them to a file.
7-14