Page 271
SECTION 9
POWER FAILURE AND RECOVERY
HANDLING POWER INTERRUPTION AND RECOVERY POWER INTERRUPTION
WHILE POWER IS INTERRUPTED
POWER RESTORATION
© 1987 INTERMEC Corporation Page 9-1
Page 272
POWER FAILURE AND RECOVERY
HANDLING POWER INTERRUPTION AND RECOVERY
Power for controller operation is supplied by an INTERMEC power supply connected to an AC power source. Power interruption is defined as the temporary or permanent loss of power to the controller. There are four common ways power may be interrupted:
1. The controller is deliberately turned off to flush the data queues. See Section 5, “Configuring the Controller,” or Section 8, "CRT Control of 9154 Communication.”
2. The controller is turned off at night when the system is not operating.
3. The controller is accidentally turned off without stopping system operation first.
4. The AC power source is interrupted. Regardless of the reason for the interruption, the 9154 Controller protects all data buffers in the controller. Data in transmission is re-transmitted after power is restored.
This section explains how the controller responds in each of the three phases of power interruption:
1. Power Interruption
2. While Power is Interrupted 3. Power Restoration
Page 9-2 © 1987 INTERMEC Corporation
Page 273
Power Interruption
POWER INTERRUPTION
When a power interruption occurs, all 9154 Controller communication functions instantly halt. Data will not be transmitted to or accepted from the host computer. The controller is unable to communicate with the polled devices. Unless readers can buffer their own data, they will be unable to read bar code labels.
All RAM data is battery-backed up, including the RAM copy of the configuration parameters. All firmware routines essential to maintaining data integrity are protected. The controller's internal battery supplies power for the backup operation.
When using the Supervisory CRT to configure parameters:
. If a power interrupt occurs while the first new parameter value on that screen is being typed in, but before a [CR] has been entered to move to the next parameter, the new value will be lost because it has not yet been entered into RAM.
+ {f a power interrupt occurs after one or more new values have been confirmed by a [CR], but before [CNTL] [T] or [ESC] has been entered to save them, the RAM configuration parameters test will fail when power is restored.
© 1987 INTERMEC Corporation Page 9-3
Page 274
POWER FAILURE AND RECOVERY
WHILE POWER IS INTERRUPTED
CAUTION
Do not interrupt power to the controller for more than two weeks, If the controller contains valuable data. A power interrupt exceeding two weeks may result in the loss of data as the NiCad battery runs down and becomes unable to protect data stored in RAM.
The controller's RAM data and real time clock operation are backed up for a minimum of two weeks by the internal NiCad battery. After two weeks, loss of data integrity may occur as the battery is unable to continue protecting RAM. AC power must be restored for operation to resume.
POWER RESTORATION When AC power is restored, a RAM status test is performed.
+ If RAMis still protected by the battery, the controller will then perform tests on ROM and the RAM copy of the configuration parameters.
. If the RAM configuration parameters test passes, the RAM copy of the parameters is fine and is left unchanged.
. If the RAM configuration parameters test fails, the EEPROM copy of the configuration parameters will be written to RAM.
After the RAM configuration parameters test, the controller initializes data communication with the host and polled devices using the RAM copy of the configuration parameters. Any essential controller operation that was being performed prior to the power interrupt is completed.
Page 9-4 © 1987 INTERMEC Corporation
Page 275
Power Restoration
With regard to data in transmission, if solicited protocol is being used, the controller reverts to waiting fora POL or SEL from the host computer. If the controller was transmitting a message when power was interrupted, the next POL from the host after power restoration causes re-transmission of the message. Conversely, if a power interrupt occurs while the controller is receiving a message from the host, the message must be re-transmitted by the host, starting with the SEL sequence.
Even if solicitation is disabled, the controller still knows if it was sending a message when a power interrupt occurred, so the message will be re-transmitted after power restoration.
. If RAM has lost its integrity, a destructive RAM test is performed that will destroy all RAM data, including the RAM copy of the configuration parameters. The controller will configure itself to operate with the parameter values stored in EEPROM, and resume normal operation.
CAUTION
If the controller's battery is depleted to the extent it is unable to back up RAM, charge the battery before interrupting AC power. If you do not allow the battery to recharge, data stored In RAM could be lost during an extended power interrupt.
After a prolonged power interrupt, the battery should be recharged before interrupting power. A depleted battery charges whenever there is AC power and the controller Power pushbutton is in the on position. For example, the battery charges when the controller is transmitting data or any other time during normal operation.
For short power interrupts, like cycling the power on and off, the battery should be sufficiently charged after a few minutes. However, fully recharging the battery may take up to four hours. The battery will be unable to back up RAM for an extended period of time until it has fully recharged.
© 1987 INTERMEC Corporation Page 9-5
Page 276
Page 277
SECTION 10
TROUBLESHOOTING
CONTROLLER TROUBLESHOOTING
TROUBLESHOOTING WITH THE SUPERVISORY CRT tsolate Data Communication and Protocol Errors Determine if the Polled Devices Are Communicating with the Controller Determine Which Device Addresses are Being Used
© 1987 INTERMEC Corporation Page 10-1
Page 278
TROUBLESHOOTING
CONTROLLER TROUBLESHOOTING
Table 10-1 lists problems that might occur in controller operation and their possible cause. To use the table, first identify the symptom, then isolate the cause, and finally try the corrective measure listed.
Table 10-1
Troubleshooting System Problems
Symptom: Possible Problem: Try This: Controller will Not using proper power Check that the AC power not operate. supply. source matches the configuration on the power supply label. Switch to appropriate power supply if necessary. Power supply Check power supply; replace defective. if defective. The power The controller does See “Controller will not LED doesn't not receive at least operate” above. light. 5V of power.
The Config LED blinks every
1/2 second while the controller is operating.
The Fault LED blinks every 1/2 second while the controller is operating.
The EEPROM, where the configuration parameters are written, is defective.
RAM, which provides workspace and stores the active copy of the configuration parameters, is defective.
Contact your local INTERMEC service representative.
Contact your local INTERMEC service representative.
Page 10-2
© 1987 INTERMEC Corporation
Page 279
Controller Troubleshooting
Table 10-1 (cont.) Troubleshooting System Problems
Symptom: Possible Problem: Try This:
All four status ROM test failed. ROM, Contact your local INTERMEC LEDs blink every where program resides, service representative.
1/2 second when __ is defective.
controller power is turned on.
The Fault LED Repeated communica- Check the controller often blinks tion errors are occur- configuration using during ting in either the host Supervisory CRT; change operation of or device data links. parameters if necessary. the Section 5 provides controller. information on the configuration of operating parameters. Review information in the next section, “Troubleshooting with a Supervisory CRT."
Check the device addresses. Ensure that only one device is assigned to any given address. Section 6 explains how to select device addresses.
Check the cable and cable connections for any source of electrical noise.
See the information in the next section, “Troubleshooting with a Supervisory CRT."
© 1987 INTERMEC Corporation Page 10-3
Page 280
TROUBLESHOOTING
Table 10-1 (cont.) Troubleshooting System Problems
Symptom:
Possible Problem:
Try This:
The controller does not communicate with the host.
The controller is not configured properly; baud rate, parity, stop bits, or LRC are not set correctly.
Transmission parameters are not set correctly.
Cabling is incorrectly installed.
Check the controller configuration using the Supervisory CRT; change parameters if necessary. Section 5 provides instructions for checking the configuration parameters.
Check the controller transmission parameters using the Supervisory CRT; change parameters if necessary. See Section 5 for instructions.
Check that the cable was made properly. Look for opens, shorts, and miswires.
Check that the cable meets system requirements. Refer to Section 4 for specifications.
Check that the cable ends are securely fastened to components connections.
Page 10-4