Display Error Messages Screen

Device (Device Address): Buffer Overflow

The controller is receiving too much information from the devices. The devices are sending information too fast, or too much information at one time (more than 254 bytes).

Device (Device Address): Framing Stop and start bits were not found where they should have been found.

Device (Device Address): Illegal data The data link worked, but the format of the data was in error.

Device (Device Address): LRC The controller is receiving the wrong LRC from the device for the transmitted message block.

Device (Device Address): Overrun The controller receive buffer is full. The controller is receiving information from the devices at a faster rate than it can process it.

Device (Device Address): Parity The parity bit was the wrong one for the message to match the even parity required by Multi-Drop Protocol.

Device (Device Address): SOM not received No Start of Message character was received.

Device (Device Address): Timeout

The device did not send data or respond before the timeout limit was reached after the controller sent a message to the device. For example, if the controller timeout limit is 5 seconds, after the controller sends a message to a device, the device has 5 seconds to respond. If after 5 seconds the device has not responded, the controller logs this error.

Device (Device Address): Xmit problem NEG received by controller, device did not receive transmission.

Host Receive Error: Buffer Overflow

The controller is receiving too much information from the host. The host is sending information too fast, or too much information (more than 512 bytes) at one time.

© 1987 INTERMEC Corporation Page 8-37

Page 262 read from a scan by OCR; it may hold reading errors

CRT CONTROL OF 9154 COMMUNICATION

Host Receive Error: Framing or Host Transmit Error: Framing A stop bit or start bit was not found where it should be.

Host Receive Error: Illegal data Data link worked, but format of data is in error. Data was either not a valid command or the device address was invalid.

Host Receive Error: LRC The LRC is not set correctly, or the controller is receiving the wrong LRC from the the host for the message block.

Host Transmit Error: NEG received

NEG was received by controller, indicating the host did not receive the transmission.

Host Receive Error: Overrun or Host Transmit Error: Overrun

The controller receive buffer has received too much information from the host. The controller is receiving information from the host faster than it can process the information. Host Transmit Error: Overrun is unlikely to happen, but is a potential problem.

Host Receive Error: Parity or Host Transmit Error: Parity The parity bit was the wrong one for the message to match the choice of Even, Odd, or No parity shown on the Select Operating Parameters screen.

Host Receive Error: SOM not received No Start of Message character was received; meaning depends upon whether protocol is solicited, or unsolicited.

Host Receive Error: Timeout or Host Transmit Error: Timeout The host did not send data or respond before the timeout limit was reached after the controller sent a message to the host.

Polled Device Buffer Full Controller polled device buffer has reached its limit for receiving information.

Power Interrupt

An interruption of power has caused the NMI circuit to be invoked to protect essential firmware routines and ensure the routine is completed on power up.

Page 8-38 © 1987 INTERMEC Corporation

Page 263 read from a scan by OCR; it may hold reading errors

Display Buffer Review Screen

DISPLAY BUFFER REVIEW SCREEN

If “5" is entered for Task No. on the Master Menu, the Display Buffer Review screen shown in Figure 8-8 will be displayed on the Supervisory CRT. This screen lets you view any records stored in the Multi-Drop buffer that are ready to be transmitted to the host.

{ Display Buffer Review HH: MM

41234567 SDATA1 234567890

>01:00:09 3DATA343533242234234-98

301:00:10

CNTL-Q to Start Review CNTL-S to Stop Review Press CNTL-T For Listing of Task Options

\.

Figure 8-8 Display Buffer Review Screen

© 1987 INTERMEC Corporation Page 8-39

Page 264 read from a scan by OCR; it may hold reading errors

CRT CONTROL OF 9154 COMMUNICATION

Display Buffer Review Screen Operation

Data records are displayed first at the top of the screen. Each data record received from a device starts on its own line. If one line does not have enough room to hold the entire record, the end of the record is wrapped around to the next line if CRT auto wrap is enabled. The data displayed at the top of the screen will be the next data record to be transmitted by the controller to the host.

Unless a time message is being appended to every record, time messages are displayed in the buffer like data records.

You can move forward through the buffer beyond the records initially displayed by using the [CNTL] [Q] command to start the display of records, and the [CNTL] [S] command to stop scrolling. If the CRT has a scrolling or roll mode, the selection of this mode will facilitate the review of data records. When all the data in the buffer has been displayed, the controller will wait ifor more data to display. As new records are received, they will scroll onto the bottom of the screen as the old records scroll off the top.

To return to the top of the data queue, you must exit to the Master Menu, and then return to the Display Buffer Review screen. Data Format

Data records displayed on the screen have the following format.

Time Message Format: Each time message is displayed in a format like the following example from Figure 8-8.

01:00:09

> Indicates that a time message follows.

01 Days, two digits, (01-31)

: Delimiter used between days and hours.

00 Hours, two digits (00-23), 12-hour or 24-hour format depends on configuration of real time clock. : Delimiter used between hours and minutes. 09 Minutes, two digits (00-59).

Data Message Format: Each data message is displayed in a format like the following example from Figure 8-8 above.

Page 8-40 © 1987 INTERMEC Corporation

Page 265 read from a scan by OCR; it may hold reading errors

Display Buffer Review Screen

41234567

4 Device address, one character, A-Z or 0-5.

1234567 The data record.

Notice that the data record does not contain any of the Multi- Drop communication protocol; the SOM, EOM, and LRC have all been stripped out by the controller before inserting the data in the buffer. The data record also does not contain any of the data communication protocol necessary to communicate with the host. This protocol will be added when the message is transmitted from the controller.

The frequency with which time messages are appended to data records received from polled devices depends on the time interval specified with the Select Clock Parameters screen.

No two time messages will ever appear back-to-back. The controller will only append time to the data buffer when a data record has been received from a polled device. For example, if five minutes had passed between the transmission of data to the controller, the buffer would look like this:

>01:12:00 A19844234-12 >01:17:00 119844237-10

© 1987 INTERMEC Corporation Page 8-41

Page 266 read from a scan by OCR; it may hold reading errors

CRT CONTROL OF 9154 COMMUNICATION

SELECT POLLED DEVICES SCREEN

If "6" is entered for Task No. on the Master Menu, the Select Polled Devices screen shown in Figure 8-9 will be displayed on the Supervisory CRT. The Select Polled Devices screen lets you specify which Multi-Drop addresses will be enabled or disabled and check which addresses are being used by devices. The controller will only poll or select enabled addresses.

Select Polled Devices HH :MM

Device Status (E=Enabled,D=Disabled) Device Status (E=Enabled,D=Disabled)

Connected

Connected

VPOSEKAGH TOANMNMOAD?D' oR R Eh ECR ECR E nC am Eon) OUpwnronxxeccHnupmoal

AAM MMM AM AMAA MM

Press CNTL-T For Listing of Task Options Press ESC to Update EEPROM

~

Figure 8-9 Select Polled Devices Screen

Page 8-42 © 1987 INTERMEC Corporation

Page 267 read from a scan by OCR; it may hold reading errors

Select Polled Devices Screen

Select Polled Devices Screen Layout The time on the controller real time clock time is displayed in the upper right corner in the following format:

HH:MM

HH is hours in 24 hour format. MM is minutes.

The main part of the screen is a two column list of device addresses: A-P in the first column, and Q-5 in the second column. To the right of the addresses, there are spaces for displaying address and device status. At the bottom of the screen are the two commands for saving changes.

Select Polled Devices Screen Operation

Enabling or Disabling Addresses: The controller will only poll or select those addresses which are enabled. To enable or disable device addresses, move the cursor to the appropriate addresses by pressing [CR] as many times as is necessary, and then enter [D] for disable polling to that address, or [E] for enable polling to that address. A [CR] after entering the status will confirm the value and move the cursor to the next address.

Connected Devices: To the right of the status column is a column which displays "Connected" if a device is actually operating at that address. The address must be enabled, even if a device is configured to operate at that address. If itis not enabled, “Connected” will not appear on this screen. In Figure 8-9, addresses Q and W are enabled and connected.

© 1987 INTERMEC Corporation Page 8-43

Page 268 read from a scan by OCR; it may hold reading errors

CRT CONTROL OF 9154 COMMUNICATION

SEND MESSAGES TO POLLED DEVICES SCREEN

If "7" is entered for Task No. on the Master Menu, the Send Messages to Polled Devices screen shown in Figure 8-10 will be displayed on the Supervisory CRT. The Send Messages to Polled Devices screen lets you send a message to specified device addresses.

Send Messages to Polled Devices HH :MM

MOZEePRGHITOMNMOONO WY USWNRPONKX BEMCHHM DO

Addresses:

Text (Press CNTL-Y to Send):

Press CNTL-T For Listing of Task Options

Figure 8-10 Send Messages to Polled Devices Screen

Page 8-44 © 1987 INTERMEC Corporation

Page 269 read from a scan by OCR; it may hold reading errors

Send Messages to Polled Devices Screen

Send Messages to Polled Devices Screen Layout The time on the controller real time clock time is displayed in the upper right corner in the following format:

HH:MM

HH is hours in 24 hour format. MM is minutes.

The main part of the screen is divided in half with each half displaying a list of device addresses, A-P on the left and Q-5 on the right. To the right of each address is space for displaying the first 35 characters of messages being sent to that address.

At the bottom of the screen are prompts for entering addresses and messages to be sent to the polled devices.

Send Messages to Polled Devices Screen Operation Addresses: When the screen is first displayed, the cursor should be positioned in the “Addresses:* field. Enter the address for the devices to which you want to send messages in this field. A message may be sent to any or all of the addresses.

To Send To: Do This: One address Enter that address, for example, "A." Two or more addresses Enter the addresses, without any delimiters and in any order, for example, “abez125y."

All addresses Leave the address field blank.

© 1987 INTERMEC Corporation Page 8-45

Page 270 read from a scan by OCR; it may hold reading errors

CRT CONTROL OF 9154 COMMUNICATION

Once an address has been entered, press [CR] to acknowledge the address and move the cursor to the "Text" data field.

If invalid addresses are entered, the CRT will beep, ignore them and not display them on the screen. If there are no valid addresses, the CRT will treat the field as if it were empty, and send the message to all addresses.

Text: This field is used for entering a message to be sent to the devices specified in the “Addresses” field. The message can be up to 79 ASCII characters in length. If the text entered is longer than 79 characters, the Supervisory CRT will beep, and the message will be truncated to the first 79 characters.

To enter a Supervisory CRT command as a character, first enter [CNTL] [P] and then the control character. For example, you may want to enter DC4 (HEX 14) which is [CNTL] [T], the return to Master Menu command. To avoid invoking the command, enter [CNTL] [P], then press {CNTL] [7].

Once the message text has been typed, enter [CNTL] [Y] to send the message. The first 35 characters of the message will be displayed, sometimes only for a brief moment, on the screen next to each address that has been specified. As soon as the device receives the message, it will be removed from the screen. If the Multi-Drop communication link between the controller and polled devices is working properly, the message should be received and cleared from the screen almost simultaneously.

if the message is displayed on the screen for an extended pericd of time, the device address next to the message has more than likely been disconnected.

Itis not possible to send a second message to a device while the first message is still displayed on the screen. To remove the old message, enter the address in the address field, and enter i[CNTL] [X] in the text field to clear it. Then enter {CNTL] [Y] to send the blank text to the address, thereby clearing the message. Then enter a new message.

The messages displayed on the Send Messages to Polled Devices screen are not the messages sent to the polled devices by the host. Those messages can not be reviewed from the Supervisory CRT.

Page 8-46 © 1987 INTERMEC Corporation