Introduction

Line Speed: The baud rate (bytes per second) at which the controller will communicate with, and expect communication from, the polled devices. The values of Line Speed for the controller and all the polled devices must be the same. The possible values are restricted to:

19200 9600 4800 2400

Address: Because the 9154 Controller is compatible with the INTERMEC 9161 02 Multi-Drop Concentrator, the single Multi-Drop port on the controller is given an address that corresponds to one of the addresses of the four Multi-Drop ports on the 9161 02 Multi-Drop Concentrator (n, m, 0, or p). The Multi-Drop port address is not used in the polling of devices by the controller; only the device address is used. However, the Multi-Drop port address is used in communication between the host computer and the polled devices. The address configured on the controller must correspond to the Multi-Drop port address used by the host. The possible values for the port address are restricted to:

wo 83

CRT Line Parameters

Seven CRT line parameters were configured on the controller so that it could communicate with the Supervisory CRT. These values are displayed for reference, even though it is not possible to change them from this screen. The CRT line parameters were configured using the Automatic Baud Rate sequence discussed in Section 5, “Configuring the Controller." If these parameters were not configured properly, the Supervisory CRT would not be able to communicate with the controller and display the Select Operating Parameters screen.

The CRT line parameters can have different values than the host line parameters.

© 1987 INTERMEC Corporation Page 8-17

Page 242 read from a scan by OCR; it may hold reading errors

CRT CONTROL OF 9154 COMMUNICATION

Line Speed: The baud rate (bytes per second) at which the controller communicates with the Supervisory CRT. The possible values are restricted to:

19200 9600 4800 2400 1200 600 300 110

Parity: The value of the parity bit in controller to Supervisory CRT communication. The values are restricted to:

Even Odd None

Data Bits: The number of data bits in a byte of communication between the controller and the Supervisory CRT. The values are restricted to:

7 8

Stop Bits: The number of stop bits in a byte of communication between the controller and the Supervisory CRT. The default value is two.

Clear Screen: Up to six ASCII characters that define the Supervisory CRT's clear screen sequence. A single ASCII control character is displayed in a three-character representation.

Page 8-18 © 1987 INTERMEC Corporation

Page 243 read from a scan by OCR; it may hold reading errors

Introduction

Terminal Type: To the right of the Clear Screen parameter, the screen displays the terminal type, if it is one of the six standard terminals. The standard terminals are:

IBM 3101 DEC VT100 ADM 3/5 Televideo ADM 31/32/42 Hazeltine

Row/Column Offsets: The first digit specifies the offset into the Cursor Address sequence which indicates the row. The second digit specifies the offset for the column. Values for each digit are restricted to 0-7. For entering offsets, 0 defines the first character, and 7 defines the eighth character.

Cursor Address: Up to eight ASCII characters that define the Cursor Address

Command sequence for the “home” position. A single ASCII control character is displayed in a three-character representation.

© 1987 INTERMEC Corporation Page 8-19

Page 244 read from a scan by OCR; it may hold reading errors

CRT CONTROL OF 9154 COMMUNICATION

SELECT TRANSMISSION PARAMETERS SCREEN

If "2" is entered for Task No. on the Master Menu, the Transmission Parameters screen shown in Figure 8-5 will be displayed on the Supervisory CRT. The Select Transmission Parameters screen allows the user to configure all the data communication parameters between the host and the controller.

Select Operating Parameters

HH:MM Host Line Parameters: Line Speed ...... 9600 (19200, 9600, 4800, 2400, 1200, 600, 300,110) Parity ......--6- E {E = even, O = odd, N = none) Data Bits ....... 7 (7 or 8) Stop Bits ....... 1 (1 or 2) Multi-Drop Parameters: Line Speed ...... 9600 (19200, 9600, 4800, 2400 Address ........- p (m, n, ©, Pp) CRT Line Parameters: Line Speed ...... 9600 (19200, 9600, 4800, 2400, 1200, 600,300,110) Parity ........-.. E (E = even, O = odd, N = none) Data Bits ....... 7 {7 or 8) Stop Bits ....... 2 (defaulted) Clear Screen .... { SUB) (ADM 3/5) Row/Column Offsets 2/3 Cursor Address .. {ESC} =<SP><SP>

Press CNTL-T Return to Task Options Press CNTL-X to Cancel Entry Press ESC to Update EEPROM

Figure 8-5 Select Transmission Parameters Screen

Page 8-20 © 1987 INTERMEC Corporation

Page 245 read from a scan by OCR; it may hold reading errors

Select Transmission Parameters Screen

Select Transmission Parameters Screen Layout

The time on the controller real time clock time is displayed in the upper right corner in the following format:

HH:MM

HH is hours in 24 hour format. MM is minutes.

The working part of the Select Transmission Parameters screen is divided into two columns. The left-hand column lists the controller-to-host computer data transmission parameters that can be modified, and the right-hand column list the host computer to controller data transmission parameters that can be modified.

The Select Transmission Parameters Screen allows a full range of data communication parameters to be modified to fit any host requirements. See Section 4, “Host to 9154 Communication,” for information on possible configurations of this screen.

The Transmission parameters can be classified into two groups:

1. To Host Transmission Parameters 2. From Host Transmission Parameters

Where applicable, ASCII control characters are shown in standard three-character representations. For example, the Start of Message character (SOM) is STX.

© 1987 INTERMEC Corporation Page 8-21

Page 246 read from a scan by OCR; it may hold reading errors

CRT CONTROL OF 9154 COMMUNICATION

CAUTION

Two communication parameters can not be defined as the same value or communication will be impossible. For example, if the SOM and EOM characters are BOTH defined as ETX (03H), the host and the controller will be unable to communicate.

If the factory default values for the data communication parameters is satisfactory, you do not need to change this screen.

To Host Transmission Parameters

The left-hand column of parameters configures the way the controller communicates with the host. Configured values should match host computer data communication protocol.

No. of Records Per Block: Indicates the maximum number of individual polled device records that will be sent by the controller to the host in a given message block. The default is one. The default value may be changed to any number between 0 and 99.

Record Seperator: The To Host Record Separator is sent after every individual data record the controller transmits to the host. The default is the ASCII character CR (ODH).

Header: A header can be placed on the messages sent to the host by the computer. The header can be up to five ASCII characters in length. The default is header disabled, as shown by the blank field.

SOM: The Start of Message, SOM, is sent after the header, if used, and can be up to five ASCII characters long. The default SOM is the single ASCII character STX (02H).

EOM: The End Of Message, EOM, is sent after the data, and can be up to five ASCII characters. The default EOM is the single ASCII character ETX (03H).

Page 8-22 © 1987 INTERMEC Corporation

Page 247 read from a scan by OCR; it may hold reading errors

Select Transmission Parameters Screen

RES: When the host asks the controller for data by sending a POL, the controller will send an RES, indicating that it has no data. RES, thus, has the same meaning as NEG (Negative Acknowledgement), except that it is used in a different situation. The default setting for RES is the three ASCII characters STX ZCR.

AFF: If the host wants to transmit data to the controller, it will first send a SEL. The controller will respond to the computer with either AFF or NEG. If the controller responds with AFF, it indicates that itis acceptable to send data. AFF can be up to five ASCII characters. The default setting for AFF is the three ASCII characters STX Y CR.

NEG: If the host sends a SEL to the controller asking if it can send data, and the controller can not accept data, the controller will send a NEG. NEG can be up to five ASCII characters. The default setting for NEG is STX Z CR.

Error Message SOM: If the host transmits a message to an unconnected device address, or a device that has another message waiting to be transmitted to it, the controller will send the following message to the host:

“Error Message SOM” Reader Address BEL CR “Error Message EOM"

The Error Message Start Of Message indicates the start of an error message. The Error Message SOM can be up to five ASCII characters and be changed to a different value than the SOM. The default value for the Error Message SOM is the single ASCII character STX, just like the SOM.

Error Message EOM: The Error Message End Of Message indicates the end of an error message. The Error Message EOM can be up to five ASCII characters and can be set to a different value than the EOM. The default value for the Error Message EOM is the single ASCII character ETX, just like the EOM.

Transparency Check: The Transparency Check parameter allows the controller to send a control code used in the data communication protocol as part of the data stream. If the Transparency Check is enabled the defined DLE is placed directly in front of ASCII control characters contained in the data stream before they are transmitted. The default value for the Transparency Check is “N"” for disabled.

© 1987 INTERMEC Corporation Page 8-23

Page 248 read from a scan by OCR; it may hold reading errors

CRT CONTROL OF 9154 COMMUNICATION

Data Walt Mode: When Data Wait Mode is disabled, the controller will wait until itis polled by the host before sending data. When Data Wait Mode is enabled, if the host has polled the controller, the controller will transmit data to the host as soon as it becomes available. Once data is transmitted, the controller will wait for another POL from the host before it will transmit more data.

From Host Transmission Parameters Host transmission parameters, in the right-hand column on the screen, specify what the controller will look for when it expects control characters from the host.

Two parameters are of particular importance: POL and SEL. These parameters configure solicited or unsolicited protocol. Section 7, “Host to 9154 Communication,” discusses both solicited and unsolicited protocol.

POL: The POL is used by the the host to ask if the controller has any data to transmit. POL can be up to two ASCII characters. The default value for POL is the single ASCII character ENQ.

SEL: The SEL is used by the the host to ask if the controller will accept a message. SEL can be up to two ASCII characters. The default value for SEL is the single ASCII character BEL.

AFF: AFF is the host response to a controller message and indicates that the data was good. AFF can be up to two ASCII characters long. The default value of AFF is the single ASCII character ACK.

NEG: NEG is the host response to a controller message and indicates that the data was bad and needs to be re- transmitted. NEG can be up to two ASCII characters. The default value of NEG is the single ASCII character NAK.

DLE: DLE is the character that precedes the contro! codes in host-to-controller communication to tell the controller that the character immediately after the defined DLE is to be interpreted as data and not as a command. The host DLE can be any single ASCII character. The default for the host DLE is DLE (10H).

Page 8-24 © 1987 INTERMEC Corporation

Page 249 read from a scan by OCR; it may hold reading errors

Select Transmission Parameters Screen

SOM: The Host to Controller Start of Message is sent at the beginning of data messages to the controller. The host SOM can be any one or two ASCIl characters. With certain protocols, it is ignored and may be left blank. The default for the host SOM is STX (02H).

EOM: The Host to Controller End of Message is sent at the end of data messages to the controller. The host EOM can be any one or two ASCII characters. With certain protocols, it is ignored and may be left blank. The default for the host EOM is ETX (03H).

Record Separator: The host Record Separator is sent after every individual data record that the host sends to the controller. The host record separator may be any one or two ASCII characters. The default for the host Record Separator is CR (ODH).

Delay Timer: If the host sends an ENQ request for data to the controller, the controller will respond to that ENQ in the time specified by the Delay Timer. The numeric value in the Delay data field is multiplied by 10 msec to give the amount of time in which the controiler will respond. The Delay Timer can be any one to four digit number (0-99). For example, if the Delay value was two, the controller would respond in 20 msec. The default for the Delay Timer is 0 msec.

Timeout: The Timeout parameter selects the amount of time the controller will wait after sending a message to the host computer before it expects a response. The numeric value for this parameter is multiplied by one second to obtain the length of the timeout period. For example, if the timeout is "5" and the controller has transmitted an AFF in response to a host POL, the controller will transmit AFF again after waiting five seconds. The default for the Timeout is 60 seconds. It can be any value between 0-60.

The Timeout is also used when receiving data from the host. The next character must be received before the Timeout specified.

© 1987 INTERMEC Corporation Page 8-25

Page 250 read from a scan by OCR; it may hold reading errors

CRT CONTROL OF 9154 COMMUNICATION

XON/XOFF Enable: The XON/XOFF Handshake allows the controller and host to limit data transmissions if their receive buffers are full. The XON/XOFF handshake is especially useful if an unsolicited communication protocol is being used.

When the receiving unit's receive buffer is full, it will send XOFF (ASCII DC3) to the transmitter, telling it not to send anymore data. After the receiving unit's receive buffer has room for more data, the receiving device will send XON (ASCII DC1) to tell the transmitting unit that it is acceptable to send data again. The default for the XON/XOFF is "N", for disabled.

LRC: The LRC is a message error check sent after the EOM character. The LRC is calculated as the exclusive OR of all the applicable characters in the message block. If a SOM is used, all characters are applicable to the LRC calculation except the first character of the SOM. If a SOM is not used, all the characters are applicable to the LRC calculation, starting at the first character of data. The default for the LRC is "N*, for disabled. If the header is enabled, all characters are applicable to the LRC calculation except the first character of the header.

Page 8-26 © 1987 INTERMEC Corporation