Flushing the Data Queues

FLUSHING THE DATA QUEUES

The following procedure is used to flush the controller data queues and write the EEPROM copy of the configuration parameters to RAM. This procedure should be used if the RAM copy of the configuration parameters becomes so inaccurate during configuration that it would be easier to start again with the EEPROM copy of the configuration parameters.

1.

Change at least one of the configuration parameters displayed on the following Supervisory CRT screens.

Select Operating Parameters Select Transmission Parameters Select Clock Parameters

Select Polled Devices

Enter [CR] to confirm the value, but do not enter [CNTL] [T] or [ESC] to re-initialize the controller.

Turn the controller power off by switching the Power pushbutton to the off position.

Turn the controller power on by pushing the Power pushbutton to the on position.

When you return to screens 1, 2, 3, and 6 the configuration values that will be displayed will be those that were in the EEPROM before the controller power was turned off in step 3.

© 1987 INTERMEC Corporation Page 8-7

Page 232 read from a scan by OCR; it may hold reading errors

CRT CONTROL OF 9154 COMMUNICATION

CONFIGURATION PARAMETERS

When the controller is on, three distinct copies of the configuration parameters exist at any given time. These three copies work together to provide the security of backup copies as well as configuration flexibility. During actual operation, the controller does not use any of the configuration copies themselves, but uses values for specific parameters stored in the firmware itself. Those values are obtained from the RAM copy of the configuration parameters during the controller initialization and re-initialization process.

An explanation of what each copy of the configuration parameters does and how itis obtained, follows. Figure 8-2 illustrates the relationship between the three copies of the configuration parameters and the controller program.

RAM

The configuration parameters are read from the RAM when the controller power is turned on or when you invoke [CNTL] [T]. Following re-initialization, the controller communicates with both the Multi-Drop connected devices and the host using the parameters values stored in RAM. When parameters are configured and saved with [CNTL] [T] they are not saved to EEPROM; changes are stored only in the RAM copy. Data in RAM is saved by a battery backup when the controller power is off. The battery backup circuit will hold RAM data for at least two weeks.

On power up, the controller creates a RAM copy from the EEPROM copy of the configuration parameters if a prolonged power interruption results in a loss of data in the battery backed up RAM.

When the host configures the controller, the changes in configuration parameters are written only in RAM, unless you invoke the specific write EEPROM command. Host configured parameters are not written to EEPROM to avoid exceeding the recommended number of writes to the EEPROM. For example, the host might configure the controller real time clock every day.

To flush data queues, and write the EEPROM values into the RAM copy of the configuration parameters refer to the preceding section, “Flushing the Data Queues.”

Page 8-8 © 1987 INTERMEC Corporation

Page 233 read from a scan by OCR; it may hold reading errors

Configuration Parameters

EEPROM

The EEPROM copy of the configuration parameters is a permanent copy. Interruption of the controller power will not cause a loss of data in EEPROM. After configuring the controller to communicate with its host, you will usually save the new configuration parameters to EEPROM. If user changes are not stored in EEPROM, the factory default settings will remain in EEPROM. The only way the EEPROM copy of the configuration parameters can be altered is by using the Supervisory CRT or the specific host command.

If a prolonged power interruption destroys the RAM copy, the EEPROM configuration parameters will be used to configure the controller when power is restored. After configuring the controller's communication parameters, you should write the values to EEPROM to avoid losing them in the event of a prolonged power interruption.

Factory Default Settings

No matter how the other two copies of the configuration parameters are altered using the host computer or the Supervisory CRT, the factory default settings always remain the same. For a list of the factory default settings stored in EEPROM, see Appendix B. When you initially receive the controller, the EEPROM and RAM copies of the configuration parameters contain the factory default values for these parameters.

If you ever need to restore the factory default settings to the EEPROM copy of the configuration parameters, enter [CNTL] [V] from the Master Menu on the Supervisory CRT. The [CNTL] [V] command also causes a destructive RAM test to be performed, which also updates the RAM copy of configuration parameters to the factory default settings. Thus, when [CNTL] [V] is invoked, all the copies of the configuration parameters will be returned to the factory default settings.

© 1987 INTERMEC Corporation Page 8-9

Page 234 read from a scan by OCR; it may hold reading errors

CRT CONTROL OF 9154 COMMUNICATION

Supervisory CRT Command (CNTL] (T}

Supervisory CRT Command {ESC]

Supervisory CRT Command (CNTL] [V)

!

!

!

Use Factory Default Values of Configuration

Parameters

Use Supervisory CRT Values of Configuration Parameters

Use Supervisory CRT Values of Configuration Parameters

Y

Y

Update EEPROM Copy of Configuration Parameters

Update EEPROM Copy of Configuration Parameters

!

y

Page 8-10

Y

Update RAM Copy of Configuration Parameters

!

Initialize Hardware/ Firmware

Figure 8-2

Three Copies of the Configuration Parameters

© 1987 INTERMEC Corporation

Page 235 read from a scan by OCR; it may hold reading errors

Master Menu Screen

MASTER MENU SCREEN

The Master Menu is the first screen displayed. Its primary purpose is to control access to the other screens, and to allow the implementation of commands for writing the configuration parameters to EEPROM. Figure 8-3 shows the Master Menu screen.

Master Menu HH:MM 9154 Multi-Drop Controller Program 048418.- Copyright 1987 INTERMEC Corporation

- Select Operating Parameters

~ Select Transmission Parameters - Select Clock Parameters

Display Error Messages

- Display Data Review

- Select Polled Devices

~ Send Messages to Polled Devices

SHUR WH ,

Task No: - Free bytes: XXXXX (XXX%)

System: Idle / Running / Buffer Fuli

Press CNTL-R to Start Polling

Press CNTL-K to Stop Polling

Press CNTL-X to Cancel] Line

Press ESC to Write to EEPROM

Press CNTL-V to Enter Default Parameters in EEPROM

Figure 8-3 Master Menu Screen

© 1987 INTERMEC Corporation Page 8-11

Page 236 read from a scan by OCR; it may hold reading errors

CRT CONTROL OF 9154 COMMUNICATION

Master Menu Screen Layout

The top part of the screen lists the screen title and the program number. The revision number after the program number should be the most recent revision of the program. !f not, you can obtain the most recent program revision from your local INTERMEC representative.

The time on the controller real time clock is displayed in the upper right corner in the following format:

HH:MM

HH is hours in 24 hour format. MM is minutes.

Task Options: The Task Options section of the screen lists the seven screens that can be reached from the Master Menu, and describes the main function of each screen. In general, the first three and the sixth are used to configure the controller. The fourth, fifth, and seventh screens are used to troubleshoot and monitor system operation.

Configuration Screens:

Select Operating Parameters Select Transmission Parameters Select Clock Parameters

Select Polled Devices

Troubleshooting and Monitoring of Operation:

Display Error Message Display Buffer Review Send Messages to Polled Devices

The screens may be, and often are, used for other purposes than those they were primarily intended to perform. For example, if a system problem develops, you could review the configuration screens to ensure that the configuration parameters are set to acceptable values. When the system is first set up, the Display Buffer Review screen can be used to ensure time messages are being appended correctly.

Page 8-12 © 1987 INTERMEC Corporation

Page 237 read from a scan by OCR; it may hold reading errors

Master Menu Screen

Task No: The cursor will be located in the data field next to the heading “Task No". To display a screen, enter the screen number and then press [CR].

System: This field indicates the status of the controller.

if, "Running" is displayed, the controller passed all power-up tests, and the system is operating normally.

If "Idle" is displayed, the “HALT” command has been received, and there are problems with the controller operation.

If "Buffer Full" is displayed, the polled devices buffer is full, and no more data can be received from polled devices.

Polled Device Queue Status

To the right of the Task No. prompt, the number of free bytes in the polled device queue the screen displays. Free bytes is also shown as a percentage of total bytes. When the percentage is 0, the polled device data queue is full.

Master Menu Screen Operation

When the Master Menu screen is displayed, the cursor will be positioned in the Task No. field, and remain there during the entire time this screen is displayed. To display one of the seven listed screens, enter the screen number (1, 2, 3, 4, 5, 6, or 7) and then press [CR]. The screen corresponding to the number entered will be displayed. !f a wrong number is entered, use either backspace or the {CNTL] [X] command to clear the field so that another screen number can be entered. For a complete description of screen commands, see the “Supervisory CRT Command Summary” in this section.

© 1987 INTERMEC Corporation Page 8-13

Page 238 read from a scan by OCR; it may hold reading errors

CRT CONTROL OF 9154 COMMUNICATION

SELECT OPERATING PARAMETERS SCREEN

If "1" is entered for Task No. on the Master Menu, the Operating Parameters screen shown in Figure 8-4 will be displayed on the Supervisory CRT. This screen allows the user to configure the data-link layer of data communication with the host, and specify Multi-Drop parameters.

Select Operating Parameters

HH: MM Host Line Parameters: Line Speed ...... 9600 (19200, 9600, 4800, 2400,1200, 600,300,110) Parity ........45 E {E - even, O = odd, N = none) Data Bits ....... 7 (7 or 8) Stop Bits ......- 1 {1 or 2) Multi-Drop Parameters: Line Speed ...... 9600 (19200, 9600, 4800, 2400) Address ......... p (m, 1, Oo, Pp) CRT Line Parameters: Line Speed ...... 9600 (19200, 9600, 4800, 2400, 1200, 600,300,110) Parity ....+.-eee E {E = even, O = odd, N = none) Data Bits ....... 7 {7 or 8) Stop Bits ....... 2 (defaulted) Clear Screen .... (SUB) (ADM 3/5) Row/Column Offset 2/3 Cursor Address .. {ESC}=<SP><SP>

Press CNTL-T Return to Task Options Press CNTL~X to Cancel Entry Press ESC to Update EEPROM

Figure 8-4 Select Operating Parameters Screen

Page 8-14 © 1987 INTERMEC Corporation

Page 239 read from a scan by OCR; it may hold reading errors

Introduction

Select Operating Parameters Screen Layout The time on the controller real time clock time is displayed in the upper right corner in the following format:

HH:MM

HH is hours in 24 hour format. MM is minutes.

The working part of the Select Operating Parameters screen is divided into three sections:

. Host Line Parameters . Multi-Drop Port Parameters . CRT Line Parameters

Each section is made up of three columns. The parameter name is given in the first column. The second column contains data fields for entering and displaying values for the parameter. The third column, if it exists, lists the possible values that can be entered for the parameter.

Commands that can be invoked from the Select Operating Parameters screen are listed at the bottom of the screen.

Host Line Operating Parameters

Four Host Line parameters must be configured on the controller so that it will communicate with the host. The host and controller values for these parameters must be the same.

© 1987 INTERMEC Corporation Page 8-15

Page 240 read from a scan by OCR; it may hold reading errors

CRT CONTROL OF 9154 COMMUNICATION

Line Speed: The baud rate (bytes per second) at which the controller will communicate with, and expect communication from, the host. The possible values are restricted to:

19200 9600 4800 2400 1200 600 300 110

Parity: The value for the parity bit in host-to-controller communication. See Section 5, "Configuring the Controller,” for information about implementing mark or space parity. The values are restricted to:

Even Odd None

Data Bits: The number of data bits in a byte of communication. The values are restricted to:

Stop Bits: The number of stop bits in a byte of communication between the controller and the host computer. The values are restricted to:

Multi-Drop Line Parameters Two Multi-Drop line parameters must be configured on the controller to determine how the controller communicates with the polled devices.

Page 8-16 © 1987 INTERMEC Corporation