Page 111
Verifying System Installation
9. Check the layout of the Multi-Drop cabling to ensure that: + The single main trunk cable is no longer than 2000 feet. « The main trunk cable has no cable termination.
* The distance between drop sites on the main trunk line is at least two feet.
* No customer-manufactured drop cable is longer than 20 feet. No drop using INTERMEC Part No. 047653 is longer than 30 feet.
10. Check that all cable plugs are firmly inserted into the sockets, and the connections are secured where applicable.
11. Inspect that the following pin assignments are properly made: + The controller to Supervisory CRT(9-Pin to 25- Pin) « Drop cables (9-Pin to 25-Pin) * Main trunk cable connection (9-Pin to 9-Pin)
* Serial interface to the host (RS-232, RS-422/485, 20 mA Current Loop, and modem)
Section 5, “Configuring the Controller,” and Section 6, “Configuring Polled Devices," explain how to configure the controller and the polled devices. The host computer must also be configured, but that information is outside the scope of this manual. See your host system reference manual for host configuration information.
© 1987 INTERMEC Corporation Page 4-37
Page 112
Page 113
SECTION 5
CONFIGURING THE CONTROLLER
CONFIGURATION OVERVIEW APPLYING POWER TO THE 9154
CONFIGURING THE 9154 TO COMMUNICATE WITH THE SUPERVISORY CRT
MASTER MENU
INITIALIZING THE CONTROLLER
SELECT OPERATING PARAMETERS SELECT TRANSMISSION PARAMETERS SELECT CLOCK PARAMETERS
SELECT POLLED DEVICES
VERIFYING CONTROLLER CONFIGURATION
SETTING DEVICE ADDRESSES
© 1987 INTERMEC Corporation
Page 5-1
Page 114
CONFIGURING THE CONTROLLER
CONFIGURATION OVERVIEW
This section explains how to customize the controller firmware to communicate with the host computer and the polled devices. All the controller system hardware should be connected before performing the step-by-step procedures outlined in this section. See Section 4, "Installing Hardware" for step-by-step instructions on installing system hardware.
After the Supervisory CRT is configured to communicate with the controller, as explained in the next section, "Configuring the 9154 to Communicate with the Supervisory CRT," you will use the Supervisory CRT to configure the controller. The Supervisory CRT has four screens for configuring controller parameters, all of which are accessed from the Master Menu. Those four screens are:
* Select Operating Parameters
* Select Transmission Parameters . Select Clock Parameters
«, Select Polled Devices
Some of the procedures in this section may be skipped if the factory default values for those parameters are satisfactory. If ail the default values are satisfactory for establishing data communication, no configuration is necessary.
Once the values which come from the unit from the factory have been changed, the new settings must be saved before they can be used by the controller. They may be saved to RAM, or to both RAM and EEPROM. The RAM copy of the configuration parameters will be lost if a prolonged power interrupt (over two weeks) occurs. If the configuration parameters are saved to EEPROM, they are permanent until changed by the Supervisory CRT or host, and will not be lost during a prolonged power interrupt.
Page 5-2 ©1987 INTERMEC Corporation
Page 115
Applying Power to the 9154
APPLYING POWER TO THE 9154
Turn on the controller by pushing in the Power pushbutton on the front of the controller.
When the controller is powered up, it will perform a series of self tests. Once the tests are complete, the controller will immediately begin polling the Multi-Drop port and initializing communication with the host computer using the factory settings for the operating, transmission, real time clock, and polled device parameters stored in RAM. For a listing of factory default settings for all parameters, see Appendix B.
The controller will continue using the default values until it receives other instructions from the host or Supervisory CRT.
CONFIGURING THE 9154 TO COMMUNICATE WITH THE SUPERVISORY CRT
Before the Supervisory CRT can be used to configure the controller for communication with the host computer or the polled devices, the controller must be able to communicate with the Supervisory CRT.
When the power is turned on, the controller sends the Master Menu screen out the CRT port to the Supervisory CRT screen. If the Master Menu that appears is formatted incorrectly or displays garbled characters, you must configure the Supervisory CRT line parameters using the Automatic Baud Rate Detection sequence. If no screen appears, check the hardware connection between the controller and the CRT. If no screen appears, and the hardware connection is satisfactory, there may be a large difference between the controller and CRT baud rate, and the Automatic Baud Rate Detection sequence must be used.
© 1987 INTERMEC Corporation Page 5-3
Page 116
CONFIGURING THE CONTROLLER
Automatic Baud Rate Detection Sequence To start the Automatic Baud Rate Detection sequence, follow these steps. Ensure that the controller power is turned on before starting.
1. Press the [Break] key on the Supervisory CRT keyboard.
Note: Once the [Break] key is pressed, the rest of the sequence must be entered within 10 seconds or the Automatic Baud Rate Detection sequence must be started again by repeating step 1. If the 10 second timeout occurs, the operating system will attempt to display the same screen shown when the [Break] key was pressed.
2. Enter [Shift] [U] (capital letter “U") until U or any other character is displayed on the screen OR until you have pressed [Shift] [U] eight times.
3. Once acharacter appears, enter a single [Shift] [I] (capital letter "I"). HW) ey Is He broek sepierce Sor Selecting Supervisory CRT Terminal Type /20
After entering "I", you will be prompted to select a terminal type.
4 >
Terminal Types: 1 IBM 3101 4 TELEVIDEO, ADM 31/32/42 2 DEC VT100 5 HAZELTINE 3 ADM 3/5 6 OTHER
Enter Terminal Type: -
Ne yy,
Page 5-4 ©1987 INTERMEC Corporation
Page 117
Configuring to Communicate with the Supervisory CRT
The six terminal choices are: five standard types of terminals and "OTHER." “OTHER?” allows the controller to be configured for the specific clear screen and cursor position commands used by the terminal.
If the Supervisory CRT being used is one of the five types listed or has been configured to emulate one of these types, enter the number corresponding to that terminal type and press [CR].
Terminal
Type Number: Terminal:
1 IBM 3101
2 DEC VT100
3 ADM 3/5
4 Televideo, ADM 31/32/42 5 Hazeltine
For example, to configure the controller to communicate with a generic terminal or PC terminal emulator that is configured as a DEC VT100, enter [2] and press [CR]. The new default terminal will be stored in RAM. If you want to store the terminal type number in EEPROM, you must invoke the store EEPROM command (ESC) from the Master Menu or from one of the other Configuration screens.
If the CRT being used is not one of the five standard types, continue to the next section, "Configuring for a Non-Standard CRT.” Otherwise, skip to the section called "Master Menu."
© 1987 INTERMEC Corporation Page 5-5
Page 118
CONFIGURING THE CONTROLLER
Configuring for a Non-Standard CRT
If the Supervisory CRT being used is not one of the five types listed, use "OTHER’ to set the specific clear screen and cursor address command for the "home" position. You must have a reference manual or specific knowledge of the CRT being used for configuration. The Supervisory CRT will prompt you to enter the following three parameters:
* Clear Screen Sequence * Cursor Row & Column Position * Cursor Address Command Sequence for the Home Position
Follow these steps to configure the controller for a Non-Standard CRT:
1. Enter [6] then press [CR] to start the "OTHER" sequence, the following clear screen prompt will appear:
Enter Clear Screen Sequence:
2. Enter the Clear Screen sequence and press [CR]. The Clear Screen sequence can be up to six ASCIl characters. If more than six are entered, only the first six characters will be displayed and the CRT will beep. Press [CR] to accept. If you want to enter [CR] or any other active CRT command as part of the Clear Screen Sequence, it must be preceded by [CNTL] [P]. CRT commands that must be preceded by [CNTL] [P] include: [CNTL] [T], [Backspace], [DEL/Rubout], (CNTL) [X], [CNTL] [R] and [CNTL] [kK]. To enter DLE, [CNTL] [P] must be entered twice.
See Table 5-1 for directions on entering ASCIl control characters with the use of the (CNTL] key.
After you enter the Clear Screen sequence, the following cursor row and column prompt will appear:
Enter Cursor Row & Column Positions:
Page 5-6 ©1987 INTERMEC Corporation
Page 119
Configuring to Communicate with the Supervisory CRT
3. Enter the Cursor Row and Column positions and press [C].
You must enter two numeric digits ("0" to "7") so that the controller will know where to look for the cursor home coordinates. The first digit specifies the offset for the row. The second digit specifies the offset for the column position.
When entering offsets, 0 defines an offset of one character and 7 defines an offset of eight characters. The offsets are measured from the first character of the command sequence. In the example that follows, <ESC> is the first character of the cursor home command sequence. Counting to the right, the cursor row position is the third character of the sequence and the cursor column position is the fourth. The offsets from the start of the cursor home command sequence is 2 and 3 respectively. The correct entry would be "23."
1 234 Command Sequence character position 0 123 Offsets <ESC>=RC
R is the cursor row position (actual value of 1) which is offset 2 from the start of the cursor home command sequence.
Cis the cursor column position (actual value of 5) which is offset 3 from the start of the cursor home command sequence.
After entering the offsets, the final prompts will appear as follows:
Enter Cursor Address Command Sequence for the Home Position:
© 1987 INTERMEC Corporation Page 5-7
Page 120
CONFIGURING THE CONTROLLER
4. Enter the cursor address command sequence and press [CR]. The cursor home position must be defined when entering this sequence.
The Cursor Address sequence can be up to eight ASCil characters long. If more than eight are entered, only the first eight characters will be displayed and the CRT will beep. Press [CR] to accept.
If you want to enter [CR] or any other active CRT command as part of the Clear Screen Sequence, it must be preceded by [CNTL] [P]. CRT commands that must be preceded by [CNTL] [P] include: (CNTL] [7], [Backspace], [DEL/Rubout], (CNTL] [X], [CNTL] [R] and [CNTL] [K]. To enter DLE, {CNTL] [P] must be entered twice.
See Table 5-1 for directions on entering other ASCII control characters.
When the final CRT parameter, the Cursor Address command, has been entered, all the CRT parameters are initialized and automatically stored in RAM as the new default values for the controller's CRT interface. The Master Menu will be displayed, as shown in the section, “Master Menu.” if you want to store the CRT parameters to EEPROM, you must invoke the store to EEPROM command ([ESC)}) from the Master Menu or from one of the Configuration screens.
If you remove the Supervisory CRT after configuring the controller, it will be easy to re-connect a CRT which is compatible with the original Supervisory CRT if CRT parameters are stored in EEPROM.
Page 5-8 ©1987 INTERMEC Corporation