The text of a manual · part 13 of 33
9154 Line Controller System Manual, pages 121 to 130
Pages 121 to 130 of 330
The original document is the PDF (7.7 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Intermec 9154
Page 121
Master Menu
MASTER MENU
After the controller has been configured to communicate with the Supervisory CRT, the Master Menu screen should appear. However, several conditions can effect the Master Menu display.
If the controller detects a fault in its internal memory when the power is turned on, the Master Menu will not appear and a status condition indicating the fault will appear on the status lights.
If all power-up tests pass, the Master Menu will appear and will display "Running" next to the “System” heading. If the HALT ([CNTL] [K]) command is given, “Idle” will appear instead. If the polled device data storage capacity is full, “Buffer Full" will be displayed.
Enter [CTNL] [K], the Stop Polling command, to stop the polling of devices which starts automatically when the controller is turned on. It will be easier to configure the controller if you stop it from polling devices. After the controller has been configured, enter [CNTL] [R] to start polling.
INITIALIZING THE CONTROLLER
All screens are accessed from the Master Menu by entering the appropriate screen number and pressing [CR]. The four screens used to configure data communication between the host and controller and the host and polled devices follows:
Screen
Number: Screen Name:
1 Select Operating Parameters
2 Select Transmission Parameters 3 Select Clock Parameters
6 Select Polled Devices
Note: The Config LED comes on when screen 1, 2, 3, or 6 are displayed.
© 1987 INTERMEC Corporation Page 5-9
Page 122
CONFIGURING THE CONTROLLER
The initialization process is the same for each of the four screens. It requires these three steps.
1. Display the appropriate screen from the Master Menu screen by entering the screen number followed by [CR].
2. Change/Select/Insert the appropriate values for the parameters displayed on that screen.
3. Save the new values in RAM, or both RAM and EEPROM, re-initialize the controller, and return to the Master Menu screen.
As mentioned in Section 3, “Designing a System,” the initialization process can be streamlined by first making a list of the configuration parameters, particularly for the host to controller data link. Refer to "Configuration Preparation” in Section 3 for a list of configurable parameters.
Using the Supervisory CRT Screens to Configure
Each screen contains a series of fields where parameters can be entered or selected. Each field is preceded by the name of the parameter. Not all fields will accept input; some are used only for displaying information. The commands that can be executed from that screen are listed at the bottom of the screen. Use of each screen is similar and involves the following tasks and commands.
Cursor Movement: Press [CR] to move the cursor from one field to the next. Pressing [CR] after the parameter is entered moves the cursor to the next field. When the cursor is in the last field, pressing [CR] moves the cursor to the first field at the top of the screen.
Page 5-10 ©1987 INTERMEC Corporation
Page 123
initializing the Controller
Entering and Changing Parameters: To enter or change a parameter, position the cursor in the appropriate input field and type in the desired value and then press [CR]. Backspace to correct errors with [backspace] or [DEL/Rubout], or use [CNTL] [X] to clear the whole field. Disable a parameter by clearing the field and pressing [CR]. To enter a Supervisory CRT command as data, it must be preceded by [CNTL] [P]. When [CR] is pressed after a value is entered:
. If the parameter value is valid, the cursor moves to the next input field.
. If the parameter value is invalid, the Supervisory CRT beeps, and the cursor moves to the beginning of the input field. An acceptable value for the parameter must be entered before the cursor will move to the next field. Acceptable values are listed to the right of the input field for some parameters.
Note: A valid value does not mean that the value is appropriate for your particular data communication interface, only that it is an acceptable value for that specific parameter.
Saving Parameters Before saving the parameters, review the new values displayed on the screen. If any parameters need changing, follow these steps:
1. Move the cursor to the appropriate field by repeatedly pressing [CR].
2. Change the parameter, or enter [CNTL] [X] to erase the field and then enter a new parameter value.
© 1987 INTERMEC Corporation Page 5-11
Page 124
CONFIGURING THE CONTROLLER
Once all the parameters on a screen have been configured accurately, they must be saved to RAM or to EEPROM and RAM. The controller will operate with the old values of the configuration parameters until the new values are saved.
1. Enter [CNTL] [T] to save the configuration parameters on the screen on which it was invoked to RAM. This will not update the EEPROM. If the controller power is interrupted so long that battery-backed RAM fails to save the RAM configuration parameters, the EEPROM values will replace the RAM values.
2. Enter [ESC] to save the configuration parameters on all the screens to EEPROM. This also updates the RAM copy of the configuration parameters.
Regardless of which command is used, the Master Menu is displayed on the Supervisory CRT screen and the controller is re-initialized to operate with the new configuration parameter values.
Writing EEPROM Configuration Parameters to RAM: If you want to exit a screen without saving any changes, use the following procedure to restore the original values. This procedure will change all the configuration parameters on screens 1, 2, 3, and 6 to the EEPROM values.
Note: This procedure will also erase all data in the polled device buffer and host mailboxes.
1. Change atleast one configuration parameter value and press [CR] to confirm, but do not enter [CNTL] [T] to save it.
2. Turn the controller off by switching the Power pushbutton to the off position. 3. Turn the controller on by pushing the Power pushbutton to the on position.
The configuration parameters displayed on screens 1,2,3, and 6 will have the EEPROM values.
Page 5-12 ©1987 INTERMEC Corporation
Page 125
Initializing the Controller
Screen Commands
The commands listed below can be given from the initialization screens and are used in the initialization process. For a complete description of all Supervisory CRT commands, see the “Supervisory CRT Command Summary” in Section 8.
{CNTL] [X]
[CNTL} [7]
Cancels line. Erases the value in the input field where the cursor is positioned and repositions the cursor at the beginning of the field. Can be used to disable a parameter.
Returns to Master Menu. Removes the current screen from the CRT and returns to the Master Menu. Screen parameter values are saved to the RAM copy of the configuration parameters. The controller is re-initialized to operate with the new RAM copy of the configuration parameters.
The controller always calculates a checksum of the RAM copy of the configuration parameters when [CNTL] [T] is invoked.
When the controller is turned on, the controller always checks for a correct checksum. If the RAM checksum is correct, the controller is initialized to operate with the RAM copy of the configuration parameters.
If the RAM checksum is incorrect, the controller is initialized to operate with the EEPROM copy of the configuration parameters, and the polled device data queue and the host mailbox are cleared of all existing data. The RAM checksum will fail after a prolonged power interrupt or if a power interrupt occurs before changed parameter values are saved.
© 1987 INTERMEC Corporation Page 5-13
Page 126
CONFIGURING THE CONTROLLER
[ESC]
[CTRL] [V]
[CNTL] [Y]
[CNTL] [RF]
[CNTL] {K]
[CNTL] [P]
Page 5-14
Updates EEPROM. Writes all the parameter values currently displayed on the screens to RAM and EEPROM and then returns to the Master Menu. The controller is re-initialized to operate with the new EEPROM copy of the configuration parameters.
Write Factory Default. This command is available from the Master Menu screen only. It asks if you want to “Write Default Configuration Parameters To EEPROM? (Y/N)..". If you enter "Y", the factory default parameters will be written to EEPROM and then RAM. The controller will be re-initialized with the factory default values, including the screens displayed on the Supervisory CRT. “N" or any other entry will cause the Master Menu screen to be redisplayed.
Update Clock. This command is used on the Select Clock Parameters screen to update the controller's real time clock to the time and date parameters displayed on that screen.
Starts Polling. This command instructs the controller to start polling the devices on the Multi-Drop line using the current configuration parameters.
Stop Polling. This command stops the controller from polling the devices on the Multi-Drop line.
Next Entry Data Only. After using this command, the next keyed input is received by the controller as data. This allows the ASCII control codes associated with the above Supervisory CRT commands to be entered as data. Enter [CNTL] [P] twice to enter DLE as data.
©1987 INTERMEC Corporation
Page 127
Select Operating Parameters
SELECT OPERATING PARAMETERS
The operating parameters are set using the Select Operating Parameters screen. To display this screen, enter [1] and then [CR] from the Master Menu. The cursor will be positioned in the first input field, Line Speed, under the Host Line Parameters heading.
( ™ Select Operating Parameters HH: MM
Host Line Parameters: Line Speed ...... 9600 (19200, 9600, 4800, 2400, 1200, 600, 300,110) Parity .......... E (E = even, O = odd, N = none) Data Bits ....... 7 (7 or 8) Stop Bits ....... 1 (1 or 2)
Multi-Drop Parameters: Line Speed ...... 9600 (19200, 9600, 4800, 2400) AddresS ......... p (m, n, 0, Dp)
CRT Line Parameters: Line Speed ...... 9600 (19200, 3600, 4800, 2400,1200, 600, 300,110) Parity .......... E (E = even, O = odd, N = none) Data Bits ....... 7 (7 or 8) Stop Bits ....... 2 (defaulted) Clear Screen .... {SUB} (ADM 3/5 Row/Column Offsets 2/3 Cursor Address .. {ESC} =<SP><SP>
Press CNTL-T Return to Task Options
Press CNTL-X to Cancel Entry
Press ESC to Update EEPROM
\. S
© 1987 INTERMEC Corporation Page 5-15
Page 128
CONFIGURING THE CONTROLLER
Two types of operating parameters can be modified with this screen:
1. Host line parameters set the line parameters between the controller and the host.
2. Multi-Drop parameters set the configurable parameters between the polled * devices and the controller.
The CRT line parameters display the current values of the line parameters between the Supervisory CRT and the controller. These parameters are displayed but can not be changed from this screen; CRT Line Parameters are configured by the Automatic Baud Rate Detection sequence.
Line Parameters for Host Port
Four parameters can be configured for the Host Port Line: Line Speed, Parity, Data Bits, and Stop Bits. Check the default settings against the values required by the host, because these values must match.
Line Speed: Data is interchanged between the host and the controller at one of eight selectable baud rates. The eight available settings are listed below:
19200 9600 4800 2400 1200 600 300 110
The default setting is 9600. If the default setting is satisfactory, press [CR]. The cursor will move to the next field, Parity. If you need change the value, type the new value, and then press [CR]. If the entered value is acceptable for that parameter, the cursor will move to the next field, Parity.
Page 5-16 ©1987 INTERMEC Corporation
Page 129
Select Operating Parameters
If the typed value is not one of the eight values listed to the right of the field, the Supervisory CRT will beep, and the cursor will move to the beginning of the Line Speed field. Either retype an appropriate value over the old line speed, or press [CNTL] [X] to cancel the entry and then type in a new value. Before pressing [CR], you can use the backspace or DEL/Rubout keys to change entries.
Parity: The following three options are available for Host line parity. Even Odd
None
To implement mark or space parity use the following values:
Data Stop Data format: bits: Parity: bits: 7 bits, mark 7 None 2 7 bits, space 8 None 2 8 bits, mark 8 None 2 8 bits, space NA NA NA
NA_ Not applicable The table assumes that stop bits are set to one.
The default setting is even. If even is a satisfactory value for Parity, press [CR]. The cursor will move to the next parameter field, Data Bits.
To change the parity to Odd or None, enter the first letter of the parity type followed by [CR]. The cursor will move to the next field, Data Bits.
© 1987 INTERMEC Corporation Page 5-17
Page 130
CONFIGURING THE CONTROLLER
Data Bits: Host Line Data Bits is the number of bits in a transmitted or received character. Two options are available:
7 8
The default number of data bits in a character is seven. If this is satisfactory, press [CR]. The cursor will move to the next parameter field, Stop Bits.
If the host computer operates at eight, enter [8], then press [CR]. The cursor will move to the next parameter field, Stop Bits.
Stop Bits: The Host Line has two options for the number of stop bits per byte:
1 2
The default number of stop bits is one. If one is satisfactory, press [CR]. The cursor will move to the next parameter field, Multi-Drop Line Speed.
If the host computer operates with two stop bits, enter [2], then press [CR]. The cursor will move to the next parameter field, Multi-Drop Line Speed.
Multi-Drop Parameters
The two Multi-Drop parameters, Line Speed and Address, are related to communication between the polled devices and the controller, and the controller's subsequent transmission of the data to the host computer.
Line Speed: Multi-Drop Line Speed is the baud rate at which communication occurs between the controller and the polled devices. All the polled devices must be set at the same line speed as the controller. Four options are available for line speed:
19200 9600 4800 2400
The default value for Multi-Drop Line Speed is 9600. If this is satisfactory, press [CR]. The cursor will move to the next parameter field, Address.
Page 5-18 ©1987 INTERMEC Corporation