Connecting the 9154 to Polled Devices

Multl-Drop Cables

Devices connected to the controller interchange data using 4-wire RS-485. INTERMEC cables for each part of the Multi-Drop system are described in this section. If you are making your own cables, they must satisfy the specific requirements which follow.

Cabling Requirements: The basis of the Multi-Drop system is a shielded, four-wire (two twisted pairs) cable. The cable used should be made up of two individually or fully shielded pairs. Cable specifications are listed below:

Cable Requirement: Specification:

Wire Size 24 gauge or larger

Nominal Impedance 100 ohms or less

Nominal Capacitance 12.5 pf/ft or less

Attenuation 6 dbv in 2100 ft or less

Heat Resistance Pass the VW-1 vertical flame test.

You may create custom Multi-Drop cabling for connecting polled devices. Table 4-3 provides a list of Belden cables that meet the above requirements for Multi- Drop cabling.

© 1987 INTERMEC Corporation Page 4-27

Page 102 read from a scan by OCR; it may hold reading errors

INSTALLING HARDWARE

Table 4-3 Belden Cable Meeting 9154 Controller Requirements

Belden VW-1 Nom Nom

Part No Test Gauge Imped Cap 6 dbv 9729 Yes 24 100 12.5 2100 8102 No 24 100 12.5 2100 8162 No 24 100 12.5 2100 89729 UL 24 100 12.5 2100

Belden cable #89729 has the additional feature of being UL listed for use in an air plenum without being in conduit (NEC Article725, UL classified, Class 2 Circuits).

Avallable INTERMEC Cables: To save the time and expense of locating a source for custom cabling components, cables and components designed specifically for use in Multi-Drop systems may be obtained from INTERMEC. See Table 4-4 for a list of cables and components. See Figure 4-11 for an example of how INTERMEC cables would be used in an installation.

Table 4-4 INTERMEC Cabling for Multi-Drop Systems

Purpose: INTERMEC Part No.: Main Trunk Cable 583262

Trunk Cable Test Segment 047661 Trunk Cable Connector Kit 047662 Drop Cable 047653

Page 4-28 © 1987 INTERMEC Corporation

Page 103 read from a scan by OCR; it may hold reading errors

Connecting the 9154 to Polled Devices

Note: It is recommended, even if no other INTERMEC cabies or connectors are purchased, that an INTERMEC Drop Cable, Part No. 047653, be purchased for each device to eliminate the time and expense of making the 9-Pin to 25-Pin connection at every drop site.

Note: By using INTERMEC Part No. 047653, a 30 foot drop may be made from the trunk cable. When wiring a cable yourself, INTERMEC recommends a 20 foot maximum drop. A description of each INTERMEC cable follows:

Main Trunk Cable, INTERMEC Part No. 583262: This cable is ordered by the foot. During installation, lengths of cable are cut off the cable roll and used with Trunk Cable Connector Kit, INTERMEC Part No. 047662, to make trunk cable segments.

Trunk Cable Test Segment, INTERMEC Part No. 047661: This cable is used in test situations. It is pre-wired to connect with a Drop Cable, INTERMEC Part No. 047653, and is six feet long. See Section 3, “Designing a 9154 System,” for information about test systems.

Trunk Cable Connector Kit, INTERMEC Part No. 047662: This kit is used to connect the main trunk cable to drop cables. The kit contains:

. 9-Pin Plug

*, 9-Pin Socket

. Wiring Accessories *, Wiring Diagram

Drop Cable, INTERMEC Part No. 047653: The drop cable is used to connect a device to the main trunk line. It comes equipped with a pre-wired, molded T-connector that connects to the trunk line, and a 25-Pin, "D" Style, sub-miniature plug that connects to the Multi-Drop device.

© 1987 INTERMEC Corporation Page 4-29

Page 104 read from a scan by OCR; it may hold reading errors

INSTALLING HARDWARE plug 4

Trunk Segment

Trunk Cable Connector Kit Part No. 583262 Part No. 047662 (2 ft. min.)

/

Ne

25-pin D Sub Connector (Compatible with any

INTERMEC Multi-Drop Device) Drop Cable

Part No. 047653 (30 ft. fong)

socket mb

Maximum allowed plug length of Drop Segment is 30 ft. w Trunk Cable \ Part No. 583262 (2 ft min.) Trunk Segment o 7

Connector Kit Part No, 047662 Minimum allowed length of Trunk Segment between drops is 2 ft.

™ socket

Drop Cable Part No. 047653 i

.) (30 ft. long) plug (Maximum allowed length of Trunk Cable is 2000 ft.) Figure 4-11

Multi-Drop Cable Installation

Page 4-30 © 1987 INTERMEC Corporation

Page 105 read from a scan by OCR; it may hold reading errors

Connecting the 9154 to Polled Devices

Installing the Multi-Drop Cabling System There are two ways to install a Multi-Drop Cabling system:

. Build the main trunk cable segment-by-segment as the drop cables are installed.

. Lay the entire main trunk cable, then go back and insert drop cables.

Choose the method you are going to use and see the appropriate guidelines in the sections that follow. Regardless of which method is used, observe the following two guidelines.

Ending the Main Trunk Cable: The main trunk cable may be ended either ata drop site where the T-connector is the termination, or by leaving a section of unterminated main trunk line.

No special termination should be installed because it will reduce the signal amplitude in the rest of the line.

Splices: Splices between cable sections can be made open (with heat shrink or other applied protection), but keep the unshielded section shorter than two inches. The splice can also be made in a shielded box, but this is not required. The shields are connected to each other at all cable section ends and to the controller through pin 1.

Segment-By-Segment Main Trunk Cable Installation The main trunk cable may be built as the bar code readers and printers are installed. Instructions for building a system this way follow:

1. Measure and cut a length of Multi-Drop cable (INTERMEC Part No. 583262)

a little longer than the distance from the controller to the first device drop site. The distance must be at least two feet as shown in see Figure 4-11.

© 1987 INTERMEC Corporation Page 4-31

Page 106 read from a scan by OCR; it may hold reading errors

INSTALLING HARDWARE

2. Wire a9-Pin, "D” style, sub-miniature plug to the controller end of the cable length and wire a 9-Pin, "D* Style, sub-miniature socket to the drop cable end of the cable. The cable ends must be wired as illustrated in Figure 4- 12.

INTERMEC Part No. 047662 supplies the required connectors. Figure 4-10 illustrates the completed connection of the main trunk cable between the controller and the polled device.

3. Attach a drop cable from the main trunk cable to the device location using one of the two following methods:

* Use INTERMEC Part No. 047653; plug the T-connector into the main trunk cable and plug the 25-Pin,"D" style, sub-miniature connector into the device.

¢, Construct the connection using wiring information from Figure 4-12. Check that the length of the drop cable is sufficient to reach from the main trunk cable to the device, but not longer than 20 ft. Any excess cable length between the main trunk and the device should be bundled and tied.

4. Repeat steps 1 through 3 as many times as necessary until the last drop cable have been added.

Page 4-32 © 1987 INTERMEC Corporation

Page 107 read from a scan by OCR; it may hold reading errors

Connecting the 9154 to Polled Devices

9- Pin 14689 Socket

9- Pin Plug

25 - Pin Drop Cable Socket INTERMEC Part No. 047653 e (Compatible with any INTERMEC 1 4 6 8 g| Multi- Drop device)

I | | | | | _ | | i414] Transmit Driver A | | ¢ 119] Transmit Driver B | ¢ fn L146] Receive Driver A ! I ¢, 13] Receive Driver B | i ‘f o - e - | 1 | Shieid l | 14 689 Device ! ie Plug Pint | bo LL a

14 6 8 9/2 tin FE aia 2 5 14689 Fela,

Figure 4-12

Multi-Drop Wiring Diagram

© 1987 INTERMEC Corporation Page 4-33

Page 108 read from a scan by OCR; it may hold reading errors

INSTALLING HARDWARE

Laying the Main Trunk First

An alternative to creating Multi-Drop cabling segment-by-segment is to lay the main trunk cable out along its entire path. Then add drop cables after the main trunk cable has been installed.

4. Install the main trunk line along its entire path ensuring that there is slack in the cable so that connections can easily be inserted and corrected during installation.

2. Attach a9-Pin, "D" style, sub-miniature plug to the end of the main trunk cable nearest the controller. Insert the plug into the host connector on the rear of the controller.

3. Cutthe main trunk line near the drop site. Ensure that the cut is at least two feet from any other drop sites or the controller.

4, Attach a9-Pin, “D" Style, sub-miniature socket to the end of the main trunk cable nearest the controller. Attach a 9-Pin, "D" style, sub-miniature plug to the end of the main trunk cable away from the controller.

5. Attach a drop cable from the main trunk cable to the device location using one of the two following methods:

¢ Use INTERMEC Part No. 047653 plug the T-connector into the main trunk cable and the 25-Pin, “D" style, sub-miniature connector into the device.

*, Construct the connection using wiring information from Figure 4-12. Check that the length of the drop cable is sufficient to reach from the main trunk cable to the device, but not longer than 20 ft. See Figure 4- 11 for maximum and minimums lengths. Any excess cable length between the main trunk and the device should be bundied and tied.

6. Repeat steps 3 through 5 at each drop site.

Note: The method explained in steps 3 through 5 may be used to insert new drop sites in an already existing main trunk cable.

Page 4-34 © 1987 INTERMEC Corporation

Page 109 read from a scan by OCR; it may hold reading errors

Connecting the 9154 to Polled Devices

Connection to Specific Readers

All the devices supporting Multi-Drop protocol connect to the Multi-Drop cable using a 25-Pin, “D" Style, sub-miniature socket. The maximum length allowed between the device and the main trunk cable is 30 feet. The transmit and receive drivers are at all times. Figure 4-12 illustrates the pins used by this interface.

The 9-Pin to 25-Pin connection necessary to connect the devices to the Multi- Drop main trunk cable is described in “Segment-By-Segment Cable Installation" earlier in this section. If you used INTERMEC Part No. 047653, no cable connection is required when connecting the polled device to the trunk cable.

See your reader manual for information about connecting input devices like slot scanners, wands, satellite wand stations, and laser scanners to the reader.

© 1987 INTERMEC Corporation Page 4-35

Page 110 read from a scan by OCR; it may hold reading errors

INSTALLING HARDWARE

VERIFYING SYSTEM INSTALLATION

At this point the controller system should be fully installed. Except for removing the Supervisory CRT after the controller has been configured in Section 5, "Configuring the Controller," no more hardware handling should be necessary.

Before applying power to the controller or any connected equipment, review the following checklist to verify the system installation:

1. Check the controller location and mounting:

Type of Mounting: Check: Flat surface Controller is positioned away from edges. Screws Firmly attached.

2. Ensure that the AC power source is noise-free and at the proper voltage and frequency.

3. Check that the controller power supply rating is the proper one for the AC power source.

4. Check that a grounding wire is connected both to the grounding stud on the rear of the controller and a good earth ground.

5. Check that the Supervisory CRT is plugged into the 9-Pin socket on the front of the controller, located next to the Power pushbutton.

6. Check that the host computer line is plugged into the 25-Pin socket on the rear of the controller.

7. €nsure that the controller to host computer interface is a reasonable choice for the work environment. In particular, check the interface if the distance is longer than 250 feet for RS-232 or longer than 4000 feet for RS-422/485. Section 3, “Designing a 9154 System,” discusses the choice of interface.

8. Check that the Multi-Drop main trunk cable is plugged into the 9-Pin socket on the rear of the controller.

Page 4-36 © 1987 INTERMEC Corporation