Connecting the Host Computer to the 9154

RS-232

The controller can be connected to the host using a standard RS- 232 communications interface. Observe the following pin assignment requirements and other relevant wiring guidelines.

1/O Signal Levels:

CAUTION

The signal levels between the controller and both the host computer and Supervisory CRT must be as specified with supported EIA standard. If other signal levels are used, the controller, Supervisory CRT, and host computer could be damaged.

To avoid damaging any equipment, the signal levels of your Supervisory CRT and host should conform to EIA RS-232. RS-232 specifies the following I/O signal levels for serial transmission:

Outbound Lines: RS-232 I/O Signal Levels +12V -12V

Control Lines True (1)

Data Lines Space (0) Mark (1)

Inbound Lines: +3V Min. -8V Min. +25V Max. -25V Max.

Control Lines True (1) False (0)

Data Lines Space (0) Mark (1)

© 1987 INTERMEC Corporation Page 4-17

Page 92 read from a scan by OCR; it may hold reading errors

INSTALLING HARDWARE

Connecting the Controller to an RS-232 Host: The controller is wired as a DTE (Data Terminal Equipment) and must have the following minimum connections to operate properly with RS-232:

Pin

No.: Function: Direction: 2 Transmit Data Outgoing 3 Receive Data Incoming 7 Signal Ground (required)

If the controller is to be connected directly to a host computer port, use a modem bypass (null modem) cable with appropriate crossovers. If you are building a custom cable, one end must have a connector compatible with the host computer and the other end must have a 25-Pin, “D" Style, sub-miniature plug connector to connect with the controller. Figure 4-8 shows the crossover connections for this configuration.

25-Pin 25-Pin Controller Host Computer Connector Connector Pin # Pin # Transmit Transmit Data Data Receive Receive Data Data Signat Signal Ground 7 7 Ground DTE DTE NULL MODEM Figure 4-8

Controller to RS-232 Host Wiring Diagram

Page 4-18 © 1987 INTERMEC Corporation

Page 93 read from a scan by OCR; it may hold reading errors

Connecting the Host Computer to the 9154

Figure 4-9 displays a typical connection of the controller to a host computer. To connect the controller and host computer, follow this procedure:

1. Obtain a cable with an RS-232 crossover, a 25-Pin, “D" Style, sub-miniature plug on one end, and whatever connector is required for the host computer on the other end.

2. Plug the 25-Pin plug into the 25-Pin host socket on the rear of the controller.

3. Plug the other end of the cable into the host computer.

Host Computer Controller 2 Host Connector

U

Va a,c

Cc

\ i)

Figure 4-9 Connecting the Controller to a Host Computer

If the host computer requires more than these three connections, see the following descriptions of additional RS-232 signals the controller supports.

© 1987 INTERMEC Corporation Page 4-19

Page 94 read from a scan by OCR; it may hold reading errors

INSTALLING HARDWARE

The controller host port is wired as a DTE (Data Terminal Equipment) device. For an RS-232 interface, the pin assignments are:

EIA Direction Pin Circuit (from No.: Symbol: Signal: controller): 1 AA Chassis Ground (optional) 2 BA Transmitted Data Outgoing 3 BB Received Data Incoming 4 CA Request-to-Send Outgoing 5 CB Clear-to-Send Incoming 6 cc Data Set Ready Incoming 7 AB Signal Ground (required) 8 CF Receive Line

Signal Detector Incoming

20 cD Data Terminal Outgoing

Ready

Request-to-Send (Pin No. 4): When the controller has data to transmit, this line is made true and the controller tests the CTS and DSR lines. When both control lines are true, it transmits the data and changes the Request-to-Send to a false condition.

Clear-to-Send (Pin No. 5): This line is made true by the modem when it is ready to receive data. The controller will not transmit data until this line is made true. The default condition of this line (no connection) is a constant true.

Data Set Ready (Pin No. 6): This line is made true when the modem is ready to receive data. The default condition of this line (no connection) is constant true.

Receive Line Signal Detector (Pin No. 8): This line is made true by the modem when a carrier is detected. The default condition (no connection) of this line is constant true.

Data Terminal Ready (Pin No. 20): This line is constant true when the controller's power is on. DTR must be true before the controller will transmit data.

Page 4-20 © 1987 INTERMEC Corporation

Page 95 read from a scan by OCR; it may hold reading errors

Connecting the Host Computer to the 9154

RS-422/485

The host RS-422/485 communication interface is generally intended for use at high baud rates; however, RS-422/485 may also be required under any of the following three conditions:

1. The interconnecting cable is too long for effective unbalanced operation (RS-232).

2. The interconnecting cable is exposed to noise sources that could induce unwanted voltage, in excess of plus or minus one volt, into an unbalanced line.

3. It is necessary to minimize interference with other signals.

See your host computer manual to determine if your host computer supports RS- 422 and for information on how to connect RS-422 to your computer.

For RS-422/485 communication, there are two wires for receive data and two wires for transmit data. The two wires for each circuit are labeled A and B. Fora mark (binary 1, or OFF), the A wire is negative with respect to the B wire. Fora space (binary 0, or ON), wire A is positive with respect to wire B.

The transmitter must generate greater than 2 volts with 100 ohms between wire A and wire B. The receiver must detect signals greater than 200 mV. Cable lengths up to 4000 feet are allowed by the standard.

Connecting the Controller to an RS-422/485 Host: The cable connected to the controller must have the following pin assignments to operate properly under RS-422/485:

Pin No. Signal: Direction: 1 Chassis Ground (optional) 13 Received Data B Incoming 14 Transmitted Data A Outgoing 16 Received Data A Incoming 19 Transmitted Data B Outgoing

© 1987 INTERMEC Corporation Page 4-21

Page 96 read from a scan by OCR; it may hold reading errors

INSTALLING HARDWARE

The receive driver is enabled by the controller at all times. However, the transmit driver can be enabled or disabled by the firmware. It is enabled in the default state.

Figure 4-9 illustrates the connection of the host computer to the controller. To connect the controller to the host computer with an RS-422/485 interface follow these steps:

1. Make an interface cable with a 25-Pin, "D" style, sub-miniature plug on one end and whatever connector is needed for the host computer on the other end.

2. Plug the 25-Pin plug into the 25-Pin host connector on the rear of the controller.

3. Plug the other end of the cable into the host computer.

Modem

Modems allow communication across longer distances than direct connection with a given interface. If the host computer is located farther than several thousand feet from the controller, modems should be used for communication.

To connect the controller to a host with a modem, follow this procedure:

1. Connect the controller host port socket to a modem using a 25-Pin to 25- Pin, modem cable assembly such as INTERMEC Part No. 043237S which supports an RS-232 interface.

2. Connect the two modems together using an appropriate interface, such as an acoustic coupler or direct connection to telephone communication lines.

3. Connect a second modem to the host computer using the appropriate cable assembly for the host and modem.

Page 4-22 © 1987 INTERMEC Corporation

Page 97 read from a scan by OCR; it may hold reading errors

Connecting the 9154 to Polled Devices

Current Loop

A 20 mA Current Loop interface offers clearer transmission and noise immunity in environments prone to electrical interference or where data transmission over long distances is required. Current Loop can only be used with asynchronous communication, which is the data communication method supported by the controller.

Current Loop is available as a controller option. Consult your local INTERMEC representative for Current Loop adapters that will work with the controller. To use Current Loop, the controller must use an RS-232 interface with a Current Loop adapter connected.

CONNECTING THE 9154 TO POLLED DEVICES

The controller has one polling port with a 9-Pin,"D” Style, sub-miniature socket. Multi-Drop cabling connected to this port can support up to 32 devices. This section explains how to connect the controller to the polled devices with a Multi- Drop cabling system. Figure 4-10 illustrates the connection of a Multi-Drop cable to the controller.

The tasks required to install a Multi-Drop cabling system are:

1. Design the layout of the Multi-Drop cabling system.

2. Select Multi-Drop cables for installation.

3. Choose the method for installing the Multi-Drop cabling.

4. Install the Multi-Drop cabling.

5. Connect the devices to the cabling.

Each of these steps are described in this section, "Connecting the 9154 to Polled Devices.”

© 1987 INTERMEC Corporation Page 4-23

Page 98 read from a scan by OCR; it may hold reading errors

INSTALLING HARDWARE

Controller Polled Device Connector

Wand [ _

| D> Main Trunk ~~ Cable

Ga,, #4 !

Figure 4-10 Connecting a Multi-Drop Cable to the Controller

Reader

Page 4-24 © 1987 INTERMEC Corporation

Page 99 read from a scan by OCR; it may hold reading errors

Connecting the 9154 to Polied Devices

Compatible Readers and Printers

INTERMEC Multi-Drop Protocol is the only polling protocol supported by the 9154 Controller. The following INTERMEC devices can be configured to operate with Multi-Drop protocol and thus can be used with the controller on its Multi-Drop line.

Table 4-2 Readers and Printers Compatible with the 9154

Model Number: Comments: Readers

INTERMEC 9440 (Requires 9440 Communication Dock) INTERMEC 9510 All units INTERMEC 9511 All units INTERMEC 9512 All units INTERMEC 9540 All units INTERMEC 9550 All units Printers

INTERMEC 863X-Series All units INTERMEC 864X-Series All units

© 1987 INTERMEC Corporation Page 4-25

Page 100 read from a scan by OCR; it may hold reading errors

INSTALLING HARDWARE

Designing a Multl-Drop Cable Layout The following terminology is helpful when discussing Multi-Drop cabling.

Term: What itis:

Main trunk cable The Multi-Drop cable extending from the 9-Pin polled device connector on the rear of the controller.

Main trunk segment A section of main trunk cable, usually from one drop site to the next drop site.

Drop site The location on the main trunk cable where a drop cable is connected.

Drop cable The cable that extends from the main trunk cable to the polled device. This cable makes the 9-Pin to 25- Pin connection.

The allowed Multi-Drop layout consists of one main trunk cable with a maximum of 32 drop sites where drop cables are attached. Follow these guidelines for creating a cable layout:

* The one main trunk cable may be a maximum length of 2000 feet. *, On the main trunk cable the minimum distance allowed between drop sites is two feet of main trunk cable. This means the minimum length of a main trunk cable is two feet.

+ The drop cable, from the main trunk cable to the device port, may be a maximum of 30 feet long.

No other layout is guaranteed to work properly. See Section 3, "Designing a 9154 System,” for specific instructions on system design.

Page 4-26 © 1987 INTERMEC Corporation