Festo Software Tools: Statement list and Ladder diagram for SF 3, FST 200 Manual, pages 361 to 370

Pages 361 to 370 of 496

The original document is the PDF (3.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

Filed in the catalog under the Festo FPC-202

Page 361

FST 200

7. Online mode

7.9.1 Set Stand alone operating mode

Fig. 7.31: Stand alone operating mode No settings may be made here other than selecting Automode.

9610a

7-49

Page 362

FST 200

7. Online mode

7.9.2 Set Master and Slave operating mode Master The system mode is set to "Field bus Master" using function key F1 for the Master operating mode. You may also select: • The field bus baud rate with F2 (31.25/62.5/187.5/375 kBaud) • Bus termination ON/OFF with F3*) • Automode ON/OFF with F7 *)

Note: If the terminal is at the start or end of a field bus line, a terminating resistor is required. This is already built into the SF 3 control block and is activated through F3 (switched on/off).

Fig. 7.32: Master operating mode

7-50

9610a

Page 363

FST 200

7. Online mode

Slave The system mode is set to "Field bus Slave" using function key F1 for the Slave operating mode. In addition to baud rate, bus termination and Automode, the following items can be set: • The field bus address with F4 • The input bytes for cyclical data transmission with F5 (0-12; default: 2 bytes IW 0.4 and 0.5) • The output bytes for cyclical data transmission with F6 (0-12; default: 2 bytes OW 0.4 and 0.5).

9610a

7-51

Page 364

FST 200

7. Online mode

7.10 Displaying the I/O configuration This function gives a summary display of the I/O components on the valve terminal.

Fig. 7.33: Display of I/O configuration The following I/O ranges can be highlighted in colour with functions F1 to F5 to make the display easier to understand: Function key F1 F2 F3 F4 F5

7-52

Display Digital inputs Digital outputs Analogue inputs Analogue outputs Display of the I/O configuration

9610a

Page 365

FST 200

8.

8. Field bus, AS-i master

Field bus, AS-i Master, CP interface These interfaces allow you to connect decentralized or remote I/O modules with your SF 3 to make an integrated system. Communication between the modules and the SF 3 control block is controlled by the appropriate interface. The field bus and the AS-i configuration module are the tools for design and monitoring in program generation. You use these to define the (set) configuration of the bus systems. You may then: • Print out the configuration data entered and connect the stations using this list. • Carry out a comparison between the actual and the As Specified configuration to rectify any connection errors. • Load the configuration data from the PC to the SF 3 control block. The CP interface is treated like the local I/Os and is described in the SF 3 Type 03 manual and in the CP system manual.

8.1.

FST field bus configuration module Before programming, set up the As Specified configuration for the field bus. The following information is required for this: • Types and addresses of the field bus stations. • Number of input and output units (operands) on the field bus station (bytewise or wordwise addressing).

9610a

8-1

Page 366

FST 200

8. Field bus, AS-i master

Type/address The model specifies the type of module and the address indicates the station number under which the module is connected to the field bus. Number of input/output units In some models, the number of I/O units varies and must therefore be entered separately here. Proceed as follows to call the field bus configuration module: • Select the "Configuration" function from the "Utility programs" menu. • Select function F6 "Field bus/AS-i" • Select function F1 "Field bus"

Fig. 8.1: Field bus configuration module

8-2

9610a

Page 367

FST 200

8. Field bus, AS-i master

The system configuration of the field bus configuration module constitutes the basis for the configuration of the field bus. The following functions are available for the preparation of the configuration file. Insert (F1) Use this function to insert a new station into the configuration file. The following window appears when you select this function.

Fig. 8.2: Inserting a field bus station Enter the station number and the station you wish to connect.

9610a

8-3

Page 368

FST 200

8. Field bus, AS-i master

The permitted input is shown in the following table: Abbreviation PN

Type

Meaning

Permitted input

Station (participant) number Type of station

1 to 31

IW

Number of input units

OW

Number of output units

The field bus stations stored in the types file are presented as a picklist in a window. Is only required for types for which the number of inputs can vary. Permitted: 0-12 for byte-structured stations 0-4 for word-structured stations Is only required for types for which the number of outputs can vary. Permitted: 0-12 for byte-structured stations 0-4 for word-structured stations

Complete your input with the ENTER key or the left mouse button. If your input is permitted, you are taken to the next input field. A list of all field bus stations that can be configured appears (see mask):

8-4

9610a

Page 369

FST 200

8. Field bus, AS-i master

Fig.8.3: Selecting a station type during configuration • Select your station from the list and press ENTER. • Only for type 03/05 field bus valve terminals: Enter the calculated input and output words (IW/OW) and press ENTER. • Accept the station into the configuration list by pressing F1. • Enter further field bus stations into the As Specified configuration list by pressing F1.

9610a

8-5

Page 370

FST 200

8. Field bus, AS-i master

All entries are checked. An error message will appear in the following cases: • Maximum number of I/Os on the field bus exceeded; • Field bus address not in the range of values 1...31 or has already been assigned; • Input and output words specified (IW/OW) invalid. Error messages can be acknowledged by pressing ESC. Modify (F2) Mark the comment for the field bus station you wish to modify and select the Modify function. A window appears, like the one for Insert. You can now overwrite the current entry.

The configuration module checks whether the maximum number of stations has been complied with both in Insert and in Modify.

8-6

9610a