Page 371
FST 200
8. Field bus, AS-i master
Delete (F3) You may delete the field bus station for which you have highlighted the comment. Mark the comment using the cursor keys or the mouse. When you select the Delete function, a window appears showing the current station address and the query:
Do you wish to remove the station? (Y/N) As Specified/Actual comparison (F4)
CAUTION: The field bus will be reconfigured during an As Specified/Actual comparison. All field bus outputs are switched off for approximately 2 seconds. This procedure reads the actual configuration from the SF 3 control block and compares it with the configuration created on the PC. The following items are checked for compliance with the As Specified configuration: • Name (model) of station. • Setting of the field bus address. • Correct configuration of the input and output words.
9610a
8-7
Page 372
FST 200
8. Field bus, AS-i master
You will see a message in the message line if the configurations are identical. If inconsistencies are found during the comparison, a message window will appear listing the deviations. As Specified/Actual comparison without As Specified configuration The downloaded Actual configuration will be used as the As Specified configuration if there is no As Specified configuration file in the project directory. The file is not, however, commented, and must therefore have this information added to it. An As Specified/Actual comparison is carried out as follows: • Start the As Specified/Actual comparison by pressing F4. The following screen will appear in the event of any deviations (example):
8-8
9610a
Page 373
FST 200
8. Field bus, AS-i master
Fig. 8.4: Example of an As Specified/Actual comparison with deviations In this example, the station on the field bus with field bus address 1 has been incorrectly entered. Correct this deviation as follows: • Modify the entry in the configuration list. Note: The field bus station detected by the controller (or an "empty" entry) can be included in the As Specified list using function F4. or • Modify the field bus address of the field bus station. If the As Specified/Actual comparison has been completed without error, the As Specified configuration must be loaded into the controller.
9610a
8-9
Page 374
FST 200
8. Field bus, AS-i master
Load configuration (F5) The As Specified configuration prepared with the field bus configuration module will be loaded. An As Specified/Actual comparison will then be carried out (see above). The controller automatically carries out a comparison between the Actual and the As Specified configurations when you switch it on. The result is stored in system flag FU 0 and can be analysed by the user program. Here: FU 0 = 2
Actual list = As Specified list
FU 0 = 3
Actual list <> As Specified list
FU 0 = 4
Only the Actual list is available.
Print configuration (F6) A printout of the field bus configuration can be obtained by pressing function key (F6).
8-10
9610a
Page 375
FST 200
8. Field bus, AS-i master
File commands (F8) Use this function to quit the field bus configuration module. The File commands window will appear when you select this function.
Fig. 8.5: File commands Save and exit editor The configuration data required for the controller are stored in the current project directory under filename 3C.CFG. You are then returned to the FST configuration module function. Save in baffer The configuration file is simply saved. You may then continue with data input. Use this function to avoid possible data loss. Abort editing This function returns you to FST configuration without saving the configuration file.
9610a
8-11
Page 376
FST 200 8. Field bus, AS-i master FESTO
8-12 9610a
Page 377
FST 200
8.2
8. Field bus, AS-i master
AS-i configuration module The AS-i bus configuration module provides an easy way to design the AS-i bus system and put it into service. The following facilities are available: – Design and storing onto the PC of the configured AS-i bus system – Assign/reassign AS-i addresses to the slaves – Execution of an As Specified/Actual comparison – Loading the configuration data from the PC to the SF 3 control block. Once you have properly created a project in FST 200, you can call the AS-i bus configuration module and configure an AS-i bus system. Proceed as follows to call the AS-i bus configuration module: • Select the "Configuration" function from the "Utility programs" menu. • Select function F6 "Field bus/AS-i" • Select function F2 "AS-i Bus" (see Fig. 8.6).
9610a
8-13
Page 378
FST 200
8. Field bus, AS-i master
Fig. 8.6: Project planning ASI-slaves
This menu is used for planning the AS-i-slaves (i.e. specifying AS-i-slave address, ID code and IO code). You can complete the project planning work before the AS-i hardware is installed. The fully designed AS-i network is then loaded into the SF 3 control block for commissioning. At the same time, you need this AS-i-slave list to determine any errors in the AS-i network in an As Specified/Actual comparison.
PLEASE NOTE: Before you press F2 "Edit" or F3 "Delete": Select the slave to be modified by its AS-i address.
8-14
9610a
Page 379
FST 200
8. Field bus, AS-i master
The "Project planning AS-i slaves " screen offers the following functions. Further information may be found in the SF 3 Description Folder 6, Section 6.4. Process (F2) This key opens a window in which you can edit the slave data for the slave selected. The following slave data must be specified: – ID code for the AS-i-slave (specified in hexadecimal) – IO code for the AS-i-slave (specified in hexadecimal) – I/O/B entry for the four AS-i databits I = Input O = Output B = Bi-directional
You will find the specifications you require for your AS-i slaves in the appropriate descriptive material. Pressing F1 enters each new or modified slave in the As Specified list. Delete (F3) Function key F3 deletes a selected slave from the project planning list.
9610a
8-15
Page 380
FST 200
8. Field bus, AS-i master
Compare (F4) (As Specified/Actual comparison)
CAUTION The field bus will be reconfigured during an As Specified/Actual comparison. The controller goes over to the Stop status. All AS-i outputs are switched off. An AS-i bus system must be installed and the AS-iMaster must be connected via the SF3 to the PC for the "As Specified/Actual comparison" function. The ASi-slaves installed are read (Actual) and this is compared with the planned slaves (As Specified). The following screen will appear, see Fig. 8.7. As Specified/Actual comparison without As Specified configuration The uploaded Actual configuration will be used as the As Specified configuration if there is no As Specified configuration file in the project directory. The file is not, however, commented, and must therefore have this information added to it.
8-16
9610a