The text of a manual · part 36 of 50
Festo Software Tools: Statement list and Ladder diagram for SF 3, FST 200 Manual, pages 351 to 360
Pages 351 to 360 of 496
The original document is the PDF (3.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
Filed in the catalog under the Festo FPC-202
Page 351
FST 200
7.5
7. Online mode
Dynamic display All information that can be displayed under Display SF3 information regarding the operands for the controller, the error display and the system status can be displayed dynamically. This mode is reached by selecting function F3 from the appropriate menus.
Fig. 7.25: Selecting the dynamic display
9610a
7-39
Page 352
FST 200
7. Online mode
The states of the operands are scanned cyclically, their value being displayed on the screen and continuously updated. You may vary the scanning rate using functions F1 and F2.
Be aware that a high scanning rate can significantly slow down the speed of program processing in the controller.
7-40
9610a
Page 353
FST 200
7.6
7. Online mode
Mini-Terminal You may open a window in all the static and dynamic display menus using function F4 Mini Terminal, this provides you with direct access to the commando interpreter. The capabilities of this menu correspond to those of Terminal Mode (see section 7.8: Terminal Mode).
Fig. 7.26: Mini Terminal
9610a
7-41
Page 354
FST 200
7.7
7. Online mode
Using macros If you find it necessary to use frequently certain repeated command sequences from the command interpreter, it is best to record these commands in what is known as a macro. Access macro handling from the Online Mode opening menu by selecting function F2 Macro mode. You may define three macros, i.e. enter a maximum of 16 commands per macro. The content of this macro is retained until it is redefined.
Fig. 7.27: Macro handling
7-42
9610a
Page 355
FST 200
7. Online mode
The instructions you may enter in the macros are shown in the following list: • D (Display) • R (Run) • F (Function) • S (Stop) • M (Modify) A detailed description of the various commands is found in the "Command interpreter" section of the SF-3 description "Electronics".
9610a
7-43
Page 356
FST 200
7. Online mode
7.7.1 Defining macros The commands the macro is intended to execute must be entered in the macro before the macro can be run. Retrieve macro 1, 2 or 3 to define it using function keys F1, F3 or F5. You may enter a maximum of 16 command interpreter commands in each macro. Each line may contain exactly one command. Therefore, it makes sense only to use such commands which return with one response line only. See the System or User Manual for the controller concerned (table at the end of this section) for instructions regarding entering the individual commands.
Fig. 7.28: Defining macros
7-44
9610a
Page 357
FST 200
7. Online mode
7.7.2 Running macros All the commands in a macro are executed sequentially. Macros 1, 2 or 3 are run by selecting functions F2, F4 or F6. When one of these functions is selected, the relevant operands, memory areas or system states are modified or displayed.
Fig. 7.29: Running macros
9610a
7-45
Page 358
FST 200
7. Online mode
Selecting the Execute macro 1, 2 or 3 functions causes the commands entered in the macro to be executed once. The macro commands can be made to execute continuously by selecting function F7 Dynamic display. Execution is repeated cyclically until you quit dynamic display mode again. The repetition cycle can be slowed down or accelerated through functions F1 or F2 respectively.
7-46
9610a
Page 359
FST 200
7.8
7. Online mode
Terminal Mode
Terminal Mode is accessed from the Online Mode opening menu through function F3.
Fig. 7.30: Terminal Mode This menu sets your personal computer up as a simple terminal which you can use to work directly in the command interpreter. See the "Command Interpreter" section of SF-3 description "Electronics" for further information on the function and operation of the command interpreter.
9610a
7-47
Page 360
FST 200
7.9
7. Online mode
System configuration (set operating mode) Use function key F5 in the Online Mode to carry out system configuration (field bus settings, automode) for the controller. The SF 3 has three operating modes (system modes) which can be set using function key F1 (FB Mode): – Operating mode without field bus system mode (stand alone), (see section 7.9.1) – Field bus Master operating mode system mode (see section 7.9.2) – Field bus Slave operating mode system mode (see section 7.9.2)
The controller operating mode can only be changed in the STOP condition. Any modifications made will become effective when function key F8 is pressed. Function F7 Automode defines whether the controller goes into the STOP condition when the operating voltage is switched on (Automode OFF), or whether the controller begins program processing automatically (Automode ON). The program with the lowest number is started (generally program 0). The controller is then in the RUN status (RUN LED lights up).
7-48
9610a