The text of a manual · part 35 of 50
Festo Software Tools: Statement list and Ladder diagram for SF 3, FST 200 Manual, pages 341 to 350
Pages 341 to 350 of 496
The original document is the PDF (3.1 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
Filed in the catalog under the Festo FPC-202
Page 341
FST 200
7. Online mode
CP digital input/outputs When you select function F1 the instantaneous values of the connected local digital inputs and outputs are displayed on the screen for you. The operands I/O8.x - 15.x are given a fixed assignment to the CP system if you have installed a CP interface. Browsing with the F1 and F2 keys will bring up the display of the CP outputs. • The inputs and outputs are arranged in full on one screen page. • CP components not present are greyed out.
Fig. 7.17: Display of the CP inputs and outputs
9610a
7-29
Page 342
FST 200
7. Online mode
7.4.2 Static display of flags Selecting function F2 will bring up a display of the instantaneous values of all flags and flag words on the screen.
Fig. 7.18: Flags Display operand The flags are shown both individually and as flag words. F <v>.<t> =
7-30
5-digit decimal = 16-digit binary or 5-digit decimal +/- = 16-digit binary or $ 4-digit hexadecimal = 16-digit binary
9610a
Page 343
FST 200
7. Online mode
7.4.3 Static display of the timers Selecting function F3 brings up a display for all the timers of their instantaneous values, time attributes, timer words and the timer defaults.
Fig. 7.19: Timers Display operand Timer
T Attr.
TW [s]
TP [s]
Timer number
Timer status
Timer word
Timer preselection
Modify operand - Selection of a timer with the cursor keys; - Modification of the timer status (0 or 1) or - Modification of the timer preselection (0 to 65535 s); - Execution of the modification with the ENTER key. 9610a
7-31
Page 344
FST 200
7. Online mode
7.4.4 Static display of the counters When you select the function F4, the instantaneous values for the counter attributes, the counter words and the counter defaults for all the counters are displayed on the screen.
Fig. 7.20: Counters Display operand Counter
C
Counter number Counter status
CW [Num]
CP [Num]
Counter word
Counter preselection
Modify operand - Selection of a counter with the cursor keys; - Modification of the counter status (0 or 1) or - Modification of the counter preselection (0 to 65535 events) - Execution of the modification with the ENTER key. 7-32
9610a
Page 345
FST 200
7. Online mode
7.4.5 Static display of the registers Selecting function key F5 will bring up a display of the contents of all registers in your controller to the screen.
Fig. 7.21: Registers
9610a
7-33
Page 346
FST 200
7. Online mode
Display operand 16 registers are displayed per screen. Further registers may be displayed by pressing function keys F1 and F2. Modify operand - Selection of a register with the cursor keys; - Modification of the register content (0 to 65535) - Execution of the modification with the ENTER key.
7-34
9610a
Page 347
FST 200
7. Online mode
7.4.6 Static display of error diagnostics Selecting function F6 brings up a display to the screen of any errors which may occur in your system.
Fig. 7.22: Error display
9610a
7-35
Page 348
FST 200
7. Online mode
In the event of an error, the error number and a brief description of the error will appear. The SF 3 control block can store up to four error records. The most recent entry is displayed. Where there is more than one entry, the most recent is identified with an asterisk. If you select function F6 again, you will get a prompt asking whether the error message should be deleted. Be aware that this action only deletes the error message, but does not always rectify the cause of the error. See SF-3 description "Electronics" in respect of error messages and how to handle them.
7-36
9610a
Page 349
FST 200
7. Online mode
Local input/output and field bus diagnostics Further diagnostics information relating to the local I/Os (e.g. short circuit, supply voltage outside tolerance) and relating to the field bus stations (e.g. bus interruption, station failed/error) are displayed in Online Mode "Display SF 3 Information" (see also sections 7.4 und 7.4.1). The precise meaning of the diagnostic bytes is listed in SF-3 description "Electronics".
Fig. 7.23: Local I/O and field bus diagnostics
9610a
7-37
Page 350
FST 200
7. Online mode
7.4.7 Static display of the system status Selecting function F7 brings to the screen a listing of all the user programs stored in your controller.
Fig. 7.24: System status The listing shows the current program status and program step and any activated program module and its current step at the time the function is called for each program. Up to 16 programs can be displayed simultaneously. You may obtain information regarding further programs through functions F1 and F2.
7-38
9610a