Digi One and PortServer TS Family User's Guide: Configure Industrial Automation (IA), pages 71 to 79

Pages 71 to 79 of 140, from Digi One and PortServer TS Family User's Guide

The original document is the PDF (2.3 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Digi PortServer TS4

Page 71

Key Terms

Configure Industrial Automation (IA)

Chapter 4

The Digi Industrial Automation (IA) capabilities enable Digi products to identify and intelligently manage communications using several common Industrial Automation protocols. This chapter discusses using Digi products with Industrial Automation (IA) applications, including configurations that work for your for IA applications, and the configuration tasks required to use your Digi product in an IA environment. The content in this chapter assumes you are familiar with the basics of the industrial protocols you need to implement.

Key Terms Industrial Automation involves several key terms: Com Port Redirection A method of redirecting the serial data generated by a PC-based master to a slave connected to a port on a network-based device server. In this scheme, the master “thinks” that it is communicating with a device connected to a serial port on the PC system when, in fact, the data is encapsulated in network packets and transported across the network to a device connected to a serial port on the Digi device server. Many applications, written to support serial communication only, require this service in order to communicate over the Ethernet. IA

Abbreviation for industrial automation master (or protocol master) The host or IA device that initiates all communication with a protocol slave multi-master Any configuration in which more than one master simultaneously communicates with a slave protocol request A message generated by the master and sent to the slave that requests information or issues a command protocol response A message generated by the slave in response to a protocol request from the master slave (or protocol slave) The device that responds to requests from the master TCP socket (or TCP socket service) A type of network service that uses TCP to ensure reliability. When this manual discusses TCP sockets, it means that IA protocol messages are encapsulated in network packets and transported across the network using a standard network service. Many applications support connections to devices using TCP socket.

Chapter 4

Configure Industrial Automation (IA)

71

Page 72

Industrial Automation Configuration Wizard TCP tunnel A TCP socket connection in which a master is connected to the serial port of one device server and a slave to the serial port of another Digi device. UDP sockets (or UDP socket service) Similar to TCP socket service (discussed above) except that the UDP protocol is used instead of TCP, which means that the reliability service TCP performs is not provided. Advantages of UDP socket service are slightly less protocol overhead and support for multicasting. Some applications support connections to devices using TCP socket. UDP tunnel A UDP socket configuration in which a master is connected to the serial port of one device server and a slave to the serial port of another Digi device.

Industrial Automation Configuration Wizard To help you configure your Digi product for use in an IA application, a configuration wizard and several configuration profiles, or scenarios, are provided. To launch the wizard from the web interface, go to Applications > Industrial Automation and click the link in the text “For a guided installation, launch the Industrial Automation Wizard.”

Industrial Automation Configuration Profiles This chapter discusses several common configuration profiles for industrial automation: • "Serial Bridge Profile: Master and Slave Connected to Digi Ports" on page 73 • "Modbus Profile: Serial-Connected Slave" on page 74 • "Modbus Profile: Serial-Connected Master" on page 75 • "Omron Family Profile: Serial-Connected Slave" on page 78 • "Omron Family Profile: Serial-Connected Master" on page 79 • "Other Serial Port Protocol Profile: Serial-Connected Slave" on page 80 • "Other Serial Port Protocol Profile: Serial-Connected Master" on page 81

Industrial Automation Configuration Procedures This chapter presents procedures for configuring these common industrial automation configuration profiles: • "Configure a Serial-Connected Slave: Generic Procedure" on page 82 • "Configure a Serial-Connected Master: Generic Procedure" on page 82 • "Configure a Serial-Connected Master: TCP/UDP Sockets" on page 83 • "Configure a Serial-Connected Slave: Other IA Protocol" on page 83 • "Configure a Serial-Connected Master: Other IA Protocol" on page 84 • "Set Up COM Port Redirection" on page 85 72

Chapter 4 Configure Industrial Automation (IA)

Page 73

Serial Bridge Profile: Master and Slave Connected to Digi Ports

Serial Bridge Profile: Master and Slave Connected to Digi Ports When to Use Use this profile to connect a protocol master to the serial port of one device server and the protocol slave (or slaves) to the serial port of another device server. This profile, which is often called a serial bridge, is applicable to environments that use most IA serial port protocols and to multi-master environments as well. The network is completely transparent to the serial devices, which means they do not have to be reconfigured.

Configuration Options The serial port connections must be configured to meet the requirements of the attached device, which can be Modbus ASCII, Modbus RTU, DF1 FullDuplex, DF1 Half-Duplex, Omron Hostlink, Omron FINS, and Omron CompoWay/F. It can also be a serial port protocol that meets Digi’s definition of a “user defined” protocol, that is, one that has fixed header and trailer strings that bound all message packets and where each protocol request is followed by a single response. For the network connection, Digi recommends TCP sockets, which works regardless of the serial port protocol specified and provides an efficient and reliable network service. Another option is UDP sockets, which also works with all the serial port protocols, although it lacks TCP socket reliability. For Modbus devices, Modbus/TCP is an option, and for DF1 Full-Duplex devices, Allen Bradley Ethernet and Ethernet/IP are options. Setup Information: Slave Side See "Configure a Serial-Connected Slave: Generic Procedure" on page 82. Setup Information: Master Side To configure TCP socket or UDP socket communication, see "Configure a Serial-Connected Master: TCP/UDP Sockets" on page 83. To configure any of the other network communication protocols, see "Configure a SerialConnected Master: Generic Procedure" on page 82. Chapter 4

Configure Industrial Automation (IA)

73

Page 74

Modbus Profile: Serial-Connected Slave

Modbus Profile: Serial-Connected Slave When to Use Use this profile to connect a slave device (or devices) using Modbus RTU or Modbus ASCII. This profile is applicable to environments in which multiple masters will control the slave or slaves.

Configuration Options The serial port connection must be configured for the protocol required by the slave, in this case Modbus RTU or Modbus ASCII. The network connection usually does not require configuration. The only exception is if the master requires COM port redirection. In this case, the master is an application that resides on a PC, such as a Microsoft Windows system, and communicates only with devices on COM ports. Setup Information • •

74

To configure the serial port for Modbus ASCII or Modbus RTU, see "Configure a Serial-Connected Slave: Generic Procedure" on page 82. To setup a PC and the device server for COM port redirection using RealPort, see "Set Up COM Port Redirection" on page 85.

Chapter 4 Configure Industrial Automation (IA)

Page 75

Modbus Profile: Serial-Connected Master

Modbus Profile: Serial-Connected Master When to Use Use this profile to connect a master device using Modbus RTU or Modbus ASCII to the serial port of the device server.

Configuration Options The serial port connection must be configured for the protocol required by the master, in this case Modbus RTU or Modbus ASCII. If the remote slave supports TCP socket communication, which is the case if the remote slave is connected to another device server, Digi recommends this option. Modbus/TCP is the other supported network option. This master can be configured to control up to 8 slaves. Setup Information •

•

Chapter 4

To configure the port for Modbus ASCII or Modbus RTU and the network for TCP socket communication, see "Configure a SerialConnected Master: TCP/UDP Sockets" on page 83. To configure the port for Modbus ASCII or Modbus RTU and the network for Modbus/TCP, see "Configure a Serial-Connected Master: Generic Procedure" on page 82.

Configure Industrial Automation (IA)

75

Page 76

DF1 Profile: Serial-Connected Slave

DF1 Profile: Serial-Connected Slave When to Use Use this profile to connect a slave device (or devices if multiple slaves are connected) using DF1 Full-Duplex and DF1 Half-Duplex protocols.

Configuration Options The serial port connection must be configured for the protocol required by the slave, in this case DF1 Full-Duplex or DF1 Half-Duplex. The network connection usually does not require configuration. The only exception is if the master requires COM port redirection. In this case, the master is an application that resides on a PC, such as a Microsoft Windows system, and communicates only with devices on COM ports. Setup Information •

•

76

To configure the serial port of the device server for DF1 Full-Duplex or DF1 Half-Duplex, see "Configure a Serial-Connected Slave: Generic Procedure" on page 82. To set up a PC and the device server for COM port redirection using RealPort, see "Set Up COM Port Redirection" on page 85.

Chapter 4 Configure Industrial Automation (IA)

Page 77

DF1 Profile: Serial-Connected Master

DF1 Profile: Serial-Connected Master When to Use Use this profile to connect a master device using DF1 Full-Duplex and DF1 Half-Duplex protocols to the serial port.

Configuration Options The serial port connection must be configured for the protocol required by the master, in this case DF1 Full-Duplex or DF1 Half-Duplex. If the remote slave supports TCP socket communication, which is the case if the remote slave is connected to another device server, Digi recommends this option. For DF1 Full-Duplex users, Allen Bradley Ethernet and Ethernet/IP are other supported network options. Setup Information •

•

Chapter 4

To configure the port for DF1 Full-Duplex or DF1 Half-Duplex and the network for TCP socket communication, see "Configure a SerialConnected Master: TCP/UDP Sockets" on page 83. To configure the port for DF1 Full-Duplex and the network for Allen Bradley Ethernet or Ethernet IP, see "Configure a Serial-Connected Master: Generic Procedure" on page 82.

Configure Industrial Automation (IA)

77

Page 78

Omron Family Profile: Serial-Connected Slave

Omron Family Profile: Serial-Connected Slave When to Use Use this profile to connect a slave device (or devices) using one of the Omron serial port protocols, Hostlink, FINS, or CompoWay/F.

Configuration Options The serial port connection must be configured for the protocol required by the slave, Hostlink, FINS, or CompoWay/F. The network connection usually does not require configuration. The only exception is if the master requires COM port redirection. In this case, the master is an application that resides on a PC, such as a Microsoft Windows system, and communicates only with devices on COM ports. Setup Information •

•

78

To configure the serial port of the device server for any of the Omron protocols, see "Configure a Serial-Connected Slave: Generic Procedure" on page 82. To setup a PC and the device server for COM port redirection using RealPort, see "Set Up COM Port Redirection" on page 85.

Chapter 4 Configure Industrial Automation (IA)

Page 79

Omron Family Profile: Serial-Connected Master

Omron Family Profile: Serial-Connected Master When to Use Use this profile if you want to connect a master device to the serial port using one of the Omron serial port protocols, Hostlink, FINS, or CompoWay/F.

Configuration Options The serial port connection must be configured for the protocol required by the master, in this case Hostlink, FINS, or CompoWay/F. If the remote slave supports TCP socket communication, which includes a slave connected to another device server, Digi recommends this network option. UDP Sockets is another supported network option. Setup Information To configure the port for one of the Omron protocols and the network for TCP or UDP socket communication, see "Configure a Serial-Connected Master: TCP/UDP Sockets" on page 83.

Chapter 4

Configure Industrial Automation (IA)

79