Page 80
Other Serial Port Protocol Profile: Serial-Connected Slave
Other Serial Port Protocol Profile: Serial-Connected Slave When to Use Use this profile if you want to connect a slave device to the serial port using any IA serial port protocol not previously discussed.
Configuration Options In this configuration, you do not set up the port of the device server for an IA protocol. If you plan to use RealPort for COM port redirection, you simply set up the port for RealPort. If you plan to have the master access the device server using TCP or UDP sockets, you simply configure the standard serial port parameters required by the attached slave, such as line speed, number of data bits, and parity scheme. No special network configuration is required in either case. Setup Information • •
80
To set up the device server for RealPort, see "Set Up COM Port Redirection" on page 85. To set up the port for an “unsupported” IA protocol, see "Configure a Serial-Connected Slave: Other IA Protocol" on page 83.
Chapter 4 Configure Industrial Automation (IA)
Page 81
Other Serial Port Protocol Profile: Serial-Connected Master
Other Serial Port Protocol Profile: Serial-Connected Master When to Use Use this profile if you want to connect a master device to the serial port using any IA serial port protocol not previously discussed.
Configuration Options In this configuration, you do not set up the port of the device server for an IA protocol. You simply configure the standard serial port parameters required by the attached master, such as line speed, number of data bits, and parity scheme and then configure the port for autoconnection. Setup Information See "Configure a Serial-Connected Master: Other IA Protocol" on page 84.
Chapter 4
Configure Industrial Automation (IA)
81
Page 82
Configure a Serial-Connected Slave: Generic Procedure
Configure a Serial-Connected Slave: Generic Procedure When to Use Use this procedure when a protocol slave is connected to the serial port of the device server. Use it except when the associated master requires COM port redirection. (See "Set Up COM Port Redirection" on page 85 for information.) Procedure 1. Access the web interface by entering the device server IP address in a browser’s URL window. 2. Log in to the device server with the username root. The default password is dbps. 3. From the main menu, choose Setup Wizards > Industrial Protocols. 4. Choose the serial port protocol required by the slave that is connected to the serial port. 5. Choose Slave as the device type. Any number of network masters can communicate with the slave.
Configure a Serial-Connected Master: Generic Procedure When to Use Use this procedure when a protocol master is connected to the serial port of the device server. Use it except when the master requires TCP socket or UDP socket communication. (See "Configure a Serial-Connected Master: TCP/UDP Sockets" on page 83 for information.) Procedure 1. Access the web interface by entering the device server IP address in a browser’s URL window. 2. Log in to the device server with the username root. The default password is dbps. 3. From the main menu, choose Setup Wizards > Industrial Protocols. 4. Choose the serial port protocol required by the master. 5. Choose Master as the Mode. 6. Configure up to 8 network slaves.
82
Chapter 4 Configure Industrial Automation (IA)
Page 83
Configure a Serial-Connected Master: TCP/UDP Sockets
Configure a Serial-Connected Master: TCP/UDP Sockets When to Use Use this procedure in the following situations: • When a protocol master using one of the supported serial port protocols (Modbus ASCII, Modbus RTU, DF1 Full-Duplex, DF1 Half-Duplex, FINS, Hostlink, CompoWay/F or a protocol that meets Digi’s definition of a “user-defined” protocol) is connected to the serial port. • When the master requires TCP or UDP sockets for network communication. Procedure 1. Access the web interface by entering the device server IP address in a browser’s URL window. 2. Log in to the device server with the username root. The default password is dbps. 3. From the main menu, choose Setup Wizards > Industrial Protocols. 4. Choose the serial port protocol required by the master. 5. Choose Master as the Mode. 6. Configure up to 8 network slaves. 7. Change the default socket number only if required.
Configure a Serial-Connected Slave: Other IA Protocol When to Use Use this procedure in the following situations: • When the device connected to the serial port is a slave that is using a “non-supported” serial-port protocol, that is, the serial port protocol is not Modbus ASCII, Modbus RTU, DF1 Half-Duplex, DF1 Full-Duplex, FINS, Hostlink, CompoWay/F, or a protocol that meets the definition of a “user-defined” protocol. • When you do not want to set up the device server for RealPort COM Port redirection. • When multiple masters will not be communicating with this slave.
Chapter 4
Configure Industrial Automation (IA)
83
Page 84
Configure a Serial-Connected Master: Other IA Protocol Procedure 1. Access the web interface by entering the device server IP address in a browser’s URL window. 2. Log in to the device server with the username root. The default password is dbps. 3. From the main menu, choose Configure > Port. 4. From the Port configuration page, set the Device type to Printer, adjust other serial port communication parameters as required by the connected slave, and click Submit. 5. Choose Advanced, check Binary Mode, and click Submit.
Configure a Serial-Connected Master: Other IA Protocol When to Use Use this procedure when the device connected to the serial port is a master that is using a “non-supported” serial-port protocol, that is, the serial port protocol is not Modbus ASCII, Modbus RTU, DF1 Half-Duplex, DF1 Full-Duplex, FINS, Hostlink, CompoWay/F, or a protocol that meets the definition of a “user-defined” protocol. Procedure 1. Access the web interface by entering the device server IP address in a browser’s URL window. 2. Log in to the device server with the username root. The default password is dbps. 3. From the main menu, choose Configure > Port. 4. From the Port configuration page, set the Device type to Modem In, adjust other serial port communication parameters as required by the connected master, then choose Submit. The Terminal type field does not matter. 5. If you want to configure the port to launch an automatic connection to the slave, click Advanced. 6. Choose Enable Autoconnect. 7. Specify the IP address of the slave. 8. Specify a TCP port to use for this connection. If this is a connection to another device server, use 2101 as the TCP port number. 9. If you want the autoconnection to launch immediately, choose Force DCD. 10. Choose Binary Mode. 11. If you want to enable UDP sockets (instead of TCP sockets), choose UDP Serial, use the online help for information on completing configuration task. 12. When you complete configuration, click Submit. 84
Chapter 4 Configure Industrial Automation (IA)
Page 85
Set Up COM Port Redirection
Set Up COM Port Redirection When to Use Use these procedures when a slave is connected to the serial port of the device server and the master, which must be an application residing on a Microsoft Windows system, requires COM port redirection.
Setup Tasks: an Overview To enable Com port redirection--which requires that RealPort software be running on the same PC as the master application--complete the following tasks: 1. Configure the serial port for RealPort. See "Configure the Serial Port for RealPort" on page 86. 2. Install RealPort software on a host system. 3. Configure the port on the RealPort PC. See the PC’s documentation for information on configuring serial ports.
Chapter 4
Configure Industrial Automation (IA)
85
Page 86
Set Up COM Port Redirection Configure the Serial Port for RealPort Use this topic for information on configuring the Digi device. 1. Access the Digi device configuration from a web browser by entering the device’s IP address in the browser’s URL window. 2. Log on to the Digi device as the root user. The default password is dbps. 3. Do one of the following: If the slave is using a supported serial port protocol
If the slave is not using a supported serial port protocol
Choose Port from the main menu. Set the Device Profile to IA. Click Apply and enter the protocol information.
Install the RealPort driver on your SCADA system. Refer to the RealPort Installation Guide as needed.
4. Use the RealPort port profile and the associated help text to configure the RealPort driver with the IP address and TCP port number used by the device server. 5. Follow the prompts to complete configuration of the RealPort driver.
86
Chapter 4 Configure Industrial Automation (IA)
Page 87
RealPort: Determining Whether to Install RealPort
RealPort: Determining Whether to Install RealPort
Chapter 4
Configure Industrial Automation (IA)
87
Page 88
RealPort: Determining Whether to Install RealPort
88
Chapter 4 Configure Industrial Automation (IA)