Page 71
CBX ELECTRICAL CONNECTIONS
4
OUTPUT CONNECTIONS USING MATRIX 400™ POWER
CAUTION
Power is available directly to the Output Device, independently from the Power Supply Switch inside the CBX.
Output Device Power to Output device
Output Signal
Output device Reference
Figure 68 - Open Emitter Output Using MATRIX 400™ Power Output Device Power to Output device Output device Reference Output Signal
Figure 69 - Open Collector Output Using MATRIX 400™ Power
OUTPUT CONNECTIONS USING EXTERNAL POWER Output Device Pulled up to External Output Device Power Output Signal
Figure 70 - Output Open Emitter Using External Power Output Device Output Signal Pulled down to External Output Device Reference
Figure 71 - Output Open Collector Using External Power
61
Page 72
MATRIX 400™ REFERENCE MANUAL
4
4.7 EXTERNAL LIGHTING SYSTEMS If an External Illuminator is used, it can be powered from the CBX connection box. It must be connected to the Vdc and GND terminal clamps.
CAUTION
Power is available directly to the Illuminator, independently from the Power Supply Switch inside the CBX.
In the case of the LT-100, LT-200 or LT-300 illuminators, one of the available digital outputs must be connected as the control signal. In VisiSet™, configure the Output Line Function parameter to "External Lighting System" and the Matrix Output x External Lighting System Mode parameter to "Triggered". Control Signal for LT-100, LT-200 or LT-300 illuminators
Power to External Illuminator
Figure 72 – External Lighting System Connections
Below is a table summarizing the various External Illuminator wiring and power requirements: Illuminator LT-100 LT-200
LT-300
LT-210, LT-314, LT-316, LT-410 LT-510, LT-511
62
Wire Color Red Black Blue White Brown Black Yellow/Green Blue White White Black Shield
CBX/Matrix Signal Vdc GND O1- or O2O1+ or O2+ Vdc GND Earth O1- or O2O1+ or O2+ Vdc GND Earth
Meaning 10 to 30 Vdc Ground Control Signal Control Signal + 10 to 30 Vdc Ground Shield/Earth Ground Control Signal Control Signal + 24 Vdc Ground Shield/Earth Ground
Page 73
CBX ELECTRICAL CONNECTIONS
4
4.8 USER INTERFACE - HOST The following table contains the pinout for standard RS232 PC Host interface. For other user interface types please refer to their own manual. RS232 PC-side connections 5
1
6
9
9-pin male connector
Pin 2 3 5 7 8
Name RX TX GND RTS CTS
1
13
14
25
25-pin male connector
Pin 3 2 7 4 5
Name RX TX GND RTS CTS
63
Page 74
MATRIX 400™ REFERENCE MANUAL
5
5 MATRIX 400™ CONNECTOR ELECTRICAL CONNECTIONS 5.1 M16 19-PIN CONNECTOR The Matrix 400™ reader is equipped with an M16 19-pin male connector (Binder, 423 Series) for connection to the power supply, serial interfaces and input/output signals. The details of the connector pins are indicated in the following table:
Figure 73 – M16 19-pin Male Connector
19-pin M16 male connector pinout Pin A L
Name Vdc GND
K
CHASSIS
B C D E H F G I S O R P
I1A I1B I2A I2B O1+ O1O2+ O2RX TX ID+ ID-
Pin
Name
M U N T
MAIN INTERFACE (SW SELECTABLE)
Function Power supply input voltage + Power supply input voltage Cable shield internally connected by capacitor to the chassis External Trigger A (polarity insensitive) External Trigger B (polarity insensitive) Input 2 A (polarity insensitive) Input 2 B (polarity insensitive) Output 1 + Output 1 Output 2 + Output 2 Auxiliary RS232 RX Auxiliary RS232 TX ID-NET™ network + ID-NET™ network RS485 RS485 RS232 Full-Duplex Half-Duplex TX TX+ RTX+ RX *RX+ RTS TXRTXCTS *RX-
* Do not leave floating, see par. 5.4.2 for connection details. In order to meet EMC requirements:
connect the reader chassis to the plant earth ground by means of a flat copper braid shorter than 100 mm;
connect the main interface cable shield to pin K of the 19-pin connector;
64
Page 75
MATRIX 400™ CONNECTOR ELECTRICAL CONNECTIONS
5
5.2 M12-D 4-PIN CONNECTOR (ETHERNET) In Matrix 400 xxx-x1x models, an M12 D-Coded connector is provided for the on-board Ethernet connection. This interface is IEEE 802.3 10 BaseT and IEEE 802.3u 100 BaseTx compliant. See par. 5.7 for connection details.
Figure 74 - M12 D-Coded Female Ethernet Network Connector
M12 D-Coded Ethernet Network Connector pinout Pin 1 2 3 4
Name TX + RX + TX RX -
Function Transmitted data (+) Received data (+) Transmitted data (-) Received data (-)
5.3 POWER SUPPLY Power is supplied to the reader through the pins provided on the M16 19-pin connector (see Figure 75): USER INTERFACE
MATRIX
Vdc GND
Chassis
SHIELD
A L
V+ (10 - 30 Vdc) V- (Ground)
K
Earth Ground
CHASSIS Earth Ground
Figure 75 - Power Supply Connection
The allowed supply voltage range is 10 to 30 Vdc.
5.4 MAIN SERIAL INTERFACE The signals relative to the following serial interface types are available on the M16 19-pin connector: The main serial interface type and its parameters (baud rate, data bits, etc.) can be defined by the user via VisiSet™ software. The RS485 half duplex is automatically set whenever MUX32 communication protocol is enabled. For more details refer to the "Communication" folder in the VisiSet™ Help On Line. Details regarding the connections and use of the interfaces are given in the next paragraphs. 65
Page 76
MATRIX 400™ REFERENCE MANUAL
5
5.4.1
RS232 Interface
The RS232 interface can be used for Point-to-Point, Pass Through or Master/Slave connections. When it is connected to the host computer it allows both transmission of code data and reader configuration by VisiSet™. The following pins of the M16 19-pin connector are used for RS232 interface connection: Pin M U N T L
Name TX RX RTS CTS GND
Function Transmit Data Receive Data Request To Send Clear To Send Ground
It is always advisable to use shielded cables. The overall maximum cable length must be less than 15 m (49.2 ft). MATRIX TX RX RTS CTS GND Chassis
SHIELD
USER INTERFACE M U
RXD TXD
N T L
Handshaking Signals Reference Ground
K
Earth Ground
Earth Ground
Figure 76 - RS232 Main Interface Connections
The RTS and CTS signals control data transmission and synchronize the connected devices.
Figure 77 - RS232 Control Signals
If the RTS/CTS handshaking protocol is enabled, Matrix 400™ activates the RTS output to indicate a message is to be transmitted. The receiving unit activates the CTS input to enable the transmission. 66
Page 77
MATRIX 400™ CONNECTOR ELECTRICAL CONNECTIONS
5.4.2
5
RS485 Full-Duplex Interface
The RS485 full-duplex (5 wires + shield) interface is used for non-polled communication protocols in point-to-point connections over longer distances (max 1200 m / 3940 ft) than those acceptable for RS232 communications or in electrically noisy environments. The following pins of the M16 19-pin connector are used for RS485 full-duplex communication: Pin M N U T L
Name TX+ TXRX+ RXGND
Function RS485 Transmit Data (+) RS485 Transmit Data (-) RS485 Receive Data (+) RS485 Receive Data (-) Ground
MATRIX TX+ TXRX+ RXGND Chassis
SHIELD
USER INTERFACE M N U T L
+ RX485 + TX485 Reference Ground
K
Earth Ground
Earth Ground
Figure 78 - RS485 Full-duplex Connections
For applications that do not use RX485 signals, do not leave these lines floating but connect them to GND as shown below. NOTE MATRIX TX+ TXRX+ RXGND Chassis
SHIELD
Earth Ground
USER INTERFACE M N
+ RX485 -
U T L
Reference Ground
K
Earth Ground
Figure 79 - RS485 Full-duplex Connections using Only TX Signals
67
Page 78
MATRIX 400™ REFERENCE MANUAL
5
5.4.3
RS485 Half-Duplex Interface This interface is provided for backward compatibility. We recommend using the more efficient ID-NET™ network for Master/Slave or Multiplexer layouts.
NOTE The RS485 half-duplex (3 wires + shield) interface is available for polled communication protocols. It can be used for Multidrop connections with a Datalogic Multiplexer, (see par. 6.5) exploiting a proprietary protocol based on polled mode called MUX32 protocol, where a master device polls slave devices to collect data. The following pins of the M16 19-pin connector are used for RS485 half-duplex communication:
Pin M N L
Name RTX+ RTXGND
Function RS485 Receive/Transmit Data (+) RS485 Receive/Transmit Data (-) Ground
MATRIX RTX+ RTXGND Chassis
SHIELD
MULITPLEXER M N L
RTX485+ RTX485RS485REF
K
Earth Ground
Earth Ground
Figure 80 - RS485 Half-duplex Connections
This interface is forced by software when the protocol selected is MUX32 protocol. In a Multiplexer layout, the Multidrop address must also be set via serial channel by the VisiSet™ utility or by the Host Programming Mode.
68
Page 79
MATRIX 400™ CONNECTOR ELECTRICAL CONNECTIONS
5
The figure below shows a multidrop configuration with Matrix 400™ readers connected to a Multiplexer.
CAUTION
This is an example of multidrop wiring. Consult the multiplexer manual for complete wiring instructions.
Figure 81 - Matrix 400™ Multidrop Connection to a Mutiplexer
69
Page 80
MATRIX 400™ REFERENCE MANUAL
5
5.5 ID-NET™ INTERFACE Pin R P L
5.5.1
Name ID+ IDGND
Function ID-NET™ network + ID-NET™ network Ground
ID-NET™ Cables
The following instructions are referred to Figure 83, Figure 84 and Figure 85.
The general cable type specifications are: CAT5 twisted pair + additional CAT5 twisted pair, shielded cable AWG 24 (or AWG 22) stranded flexible. We recommend using DeviceNet cables (drop or trunk type) to the following reference standards: AN50325 – IEC 62026 UL STYLE 2502 80°C 30V
Cable Shield MUST be connected to earth ground ONLY at the Master.
NEVER use ID-NET™ cable shield as common reference.
The ID-NET™ max cable length depends on the baudrate used, (see the Baudrate Table below).
For Common Power Connections use only 2 wires (R and P). DC Voltage Power cable (Vdc – GND) should be handled as a signal cable (i.e. do not put it together with AC cable): Wire dimensioning must be checked in order to avoid voltage drops greater than 0.8 Volts. Cable should lie down as near as possible to the ID-NET™ cable (avoiding wide loops between them).
Reader's chassis may be connected to earth.
Network inside the same building.
Baudrate Table Baud Rate
125 kbps
250 kbps
500 kbps
1Mbps
Cable Length
1200 m
900 m
700 m
*
* Application dependent, contact your Datalogic Automation representative for details.
NOTE
70
The default ID-NET™ baudrate is 500 kbps. Lower ID-NET™ baudrates allow longer cable lengths. The baudrate is software configurable by authorized Datalogic Automation personnel only.