CBX ELECTRICAL CONNECTIONS

4

4.3 ID-NET™ INTERFACE CBX100/500 Shield ID+ IDREF

4.3.1

Function Network Cable Shield ID-NET™ network + ID-NET™ network Network Reference

ID-NET™ Cables

The following instructions are referred to Figure 57, Figure 58 and Figure 59.

The general cable type specifications are: CAT5 twisted pair + additional CAT5 twisted pair, shielded cable AWG 24 (or AWG 22) stranded flexible. We recommend using DeviceNet cables (drop or trunk type) to the following reference standards: AN50325 – IEC 62026 UL STYLE 2502 80°C 30V

Cable Shield MUST be connected to earth ground ONLY at the Master.

NEVER use ID-NET™ cable shield as common reference.

The ID-NET™ max cable length depends on the baudrate used, (see the Baudrate Table below).

For Common Power Connections use only 2 wires (ID+ and ID-). DC Voltage Power cable (Vdc – GND) should be handled as a signal cable (i.e. do not put it together with AC cable): Wire dimensioning must be checked in order to avoid voltage drops greater than 0.8 Volts. Cable should lie down as near as possible to the ID-NET™ cable (avoiding wide loops between them).

Reader's chassis may be connected to earth.

Network inside the same building.

Baudrate Table Baud Rate

125 kbps

250 kbps

500 kbps

1Mbps

Cable Length

1200 m

900 m

700 m

*

* Application dependent, contact your Datalogic Automation representative for details.

NOTE

The default ID-NET™ baudrate is 500 kbps. Lower ID-NET™ baudrates allow longer cable lengths. The baudrate is software configurable by authorized Datalogic Automation personnel only.

51

Page 62

MATRIX 400™ REFERENCE MANUAL

4

4.3.2

ID-NET™ Response Time

The following figure shows the response time of the ID-NET™ network. This time is defined as the period between the Trigger activation and the beginning of data transmission to the Host. Max ID-NET™ Response Time 240 220 200

Response Time (ms)

180 160 140 120 100 80 60 40 20 0 0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

Number of Nodes 500 kbps

250 kbps

Figure 56 – ID-NET™ Response Time

CONDITIONS:

52

ID-NET™ M/S Synchronized layout message length = 50 bytes per node

125 kbps

15

16

Page 63 read from a scan by OCR; it may hold reading errors

CBX ELECTRICAL CONNECTIONS

Reader Master

Reader Slave #1

Reader Slave (up to 31)

CBX1 00/500 Main Interface HOST : ° He RS232/RS485 $ | Ue 7Te Mshiera : BYE o2°,| [Shield i = TE TREK ID- ID-NET™ P| ID+ Termination Resistor. O REF UW PG-6000 Earth Vdc * A o o CBX100/500 Shield ro 7 ; ; ID- (blue) w : : ° ip |lwhite) 2 e ° ° (black) e 0 e tte [he REF 3 5 2 WSN Wet snicta Le m © | fel [fet] Jfoating} [Shield ara «674 ° {is | ie ID- > O e e le] | @ » ID-NET™ ID+ ss Termination Resistor. O REF [ - V 5 @ PG-6000 Earth x GND | e Vdc vey > CBX100/500 Shield ; ; : ID- (blue) e e e (white) o [is | le ID* T(plack) o {fe [ls REF v D4 b4 b TT shieta e e le | floatingl ID-NET™ ~ Termination Resistor. O PG-6000 Earth a

GND Vdc

+

Figure 57, ID-NET™ Network Connections with isolated power blocks

53

Page 64

4

MATRIX 400™ REFERENCE MANUAL

Figure 58 - ID-NET™ Network Connections with Common Power Branch Network

54

Page 65

CBX ELECTRICAL CONNECTIONS

4

Figure 59 – ID-NET™ Network Connections with Common Power Star Network

55

Page 66

MATRIX 400™ REFERENCE MANUAL

4

4.3.3

ID-NET™ Network Termination

The network must be properly terminated in the first and last reader of the network. This is done by setting the ID-NET™ Termination Resistance Switch in the CBX100/500 to ON.

4.4 AUXILIARY RS232 INTERFACE The RS232 auxiliary interface is available for Point-to-Point, Pass Through or Master/Slave connections. When it is connected to the host computer it allows both transmission of code data and reader configuration by VisiSet™. The parameters relative to the aux interface (baud rate, data bits, etc.) as well as particular communication modes such as LOCAL ECHO can be defined through the Communication folder of the VisiSet™ utility program. The 9-pin female Auxiliary Interface connector inside the CBX is the preferred connector for device configuration or communication monitoring. 1

5

9

6

Figure 60 - 9-pin female connector

If permanent system wiring is required, the following pins are used to connect the RS232 auxiliary interface: CBX100/500 RX TX SGND

Function Auxiliary Interface Receive Data Auxiliary Interface Transmit Data Auxiliary Interface Reference USER INTERFACE RX

TX

Reference

Figure 61 - RS232 Auxiliary Interface Connections

Do not connect the Aux Interface to the CBX spring clamp connectors and the 9-pin connector simultaneously. NOTE

56

Page 67

CBX ELECTRICAL CONNECTIONS

4

4.5 INPUTS There are two optocoupled polarity insensitive inputs available on the reader: Input 1 (External Trigger) and Input 2, a generic input: The External Trigger can be used in One Shot Mode or in Phase Mode. Its main functions are: acquisition trigger in One Shot Mode reading phase-ON/reading phase-OFF command in Phase Mode The main functions of the general purpose Input 2 are: second external trigger in Phase Mode match code storage command when the Match Code option is enabled The electrical features of both inputs are: VAB = 30 Vdc max. IIN = 10 mA (reader) + 12 mA (CBX) max. The active state of these inputs are selected in software. Refer to the VisiSet™ Help On Line. An anti-disturbance filter is implemented in software on both inputs so that the minimum pulse duration is 0.5 milliseconds. This value can be increased through the software parameter Debounce Filter, see the Digital I/O folder in the VisiSet™ Help On Line for further details. These inputs are optocoupled and can be driven by both NPN and PNP type commands.

Polarity insensitive inputs assure full functionality even if pins A and B are exchanged. NOTE

The connections are indicated in the following diagrams: CBX100/500 +V I1A I1B -V

Function Power Source - External Trigger External Trigger A (polarity insensitive) External Trigger B (polarity insensitive) Power Reference - External Trigger

The yellow Trigger LED (Figure 19, 5) is on when the active state of the External Trigger corresponds to ON.

57

Page 68

MATRIX 400™ REFERENCE MANUAL

4

EXTERNAL TRIGGER INPUT CONNECTIONS USING MATRIX 400™ POWER

CAUTION

Power is available directly to the Input Device, independently from the Power Supply Switch inside the CBX.

PH-1 Photocell (PNP) (brown)

(black)

(blue)

Figure 62 – PH-1 External Trigger Using MATRIX 400™ Power NPN Photocell Power to Photocell

Input Signal Photocell Reference

Figure 63 - NPN External Trigger Using MATRIX 400™ Power

EXTERNAL TRIGGER INPUT CONNECTIONS USING EXTERNAL POWER PNP Photocell Input Signal Pulled down to External Input Device Reference

Figure 64 - PNP External Trigger Using External Power NPN Photocell Pulled up to External Input Device Power Input Signal

Figure 65 - NPN External Trigger Using External Power

58

Page 69

CBX ELECTRICAL CONNECTIONS

CBX100/500 +V I2A I2B -V

4 Function Power Source - Inputs Input 2 A (polarity insensitive) Input 2 B (polarity insensitive) Power Reference - Inputs

INPUT 2 CONNECTIONS USING MATRIX 400™ POWER

CAUTION

Power is available directly to the Input Device, independently from the Power Supply Switch inside the CBX.

Input Device Power to Input Device Input Signal

Input Device Reference

PNP Input 2 Using MATRIX 400™ Power

Input Device Power to Input Input Device Signal Input Device Reference

NPN Input 2 Using MATRIX 400™ Power

INPUT 2 CONNECTIONS USING EXTERNAL POWER Input Device Input Signal Pulled down to External Input Device Reference

Figure 66 - PNP Input 2 Using External Power

59

Page 70

MATRIX 400™ REFERENCE MANUAL

4 Input Device Pulled up to External Input Device Power Input Signal

Figure 67 - NPN Input 2 Using External Power

4.6 OUTPUTS Two optocoupled general purpose outputs are available. The meaning of the two outputs Output 1 and Output 2 can be defined by the user. They are typically used either to signal the data collection result or to control an external lighting system. CBX100/500 +V O1+ O1O2+ O2-V

Function Power Source - Outputs Output 1 + Output 1 Output 2 + Output 2 Power Reference Outputs

The electrical features of the two outputs are the following: VCE = 30 Vdc max. ICE = 40 mA continuous max.; 130 mA pulsed max. VCE saturation = 1 Vdc max. @ 10 mA PD = 80 mW Max. @ 45 °C ambient temp. By default, Output 1 is associated with the Partial Read and No Read events, which activates when the code(s) signaled by the external trigger are not decoded, and Output 2 is associated with the Complete Read event, which activates when all the selected codes are correctly decoded. The output signals are fully programmable being determined by the configured Activation/Deactivation events, Deactivation Timeout or a combination of the two. Refer to the Digital I/O folder in the VisiSet™ Help On Line for further details.

60