Manual · Datalogic
Datalogic ED-100 Manual
Manual2 pagesPDF 354 KB
Both pages are below, each with its text.
Filed with · 1 model
Also filed with these models on the old site
From the manual · read page by page
Key facts from this manual
Each line names its page in the PDF.
Instruction manual for the Datasensor ES/ED series 1/8 DIN microprocessor temperature controllers, with page 1 for software release 2.00 and page 2 for release 3.00, which adds a third set point; it names the series, not single models. It explains the front panel, wiring, panel mounting, the three configuration levels, the factory settings and the error messages.
- Device type
- 1/8 DIN microprocessor temperature controller, ES/ED series p. 1, 2
- Power supply
- 12 … 24 Vdc/Vac ± 10% or 80 … 240 Vac ± 10%, 50/60 Hz; 5VA max. p. 1, 2
- Sensor input
- Thermocouple type J, K, E, T, R, S, L; RTD Pt100 Ω/0 °C (DIN43760) with 2 or 3 wires p. 1, 2
- Precision
- RTD ± 0.3% fs, TC ± 0.4% fs, ±1 digit p. 1, 2
- Control action
- Automatic direct or reverse, ON/OFF or PID with autotuning; manual output 0 to 100% p. 1, 2
- 1st point output
- Relay SPDT 250 Vac, 5 A resistive, or transistor 15 Vdc ± 20%, 20 mA short-circuit protected p. 1, 2
- Alarm outputs
- Release 2.00: 2nd point relay SPDT 250 Vac, 5 A; release 3.00 adds a 3rd point relay SPST 250 Vac, 5 A p. 1, 2
- Error messages
- OvFL (over range), UnFL (under range), 8888 (test message), FAIL (general failure), LFA1/LFA2 (loop fault) p. 1
- Panel cut-out
- 45.5x91 mm; panel thickness 1 … 4 mm suggested p. 1
- Dimensions and weight
- 1/8 DIN; 48x96x125 mm; 400 g p. 1
- Protection
- IP50 front panel, IP20 case, IP00 contacts p. 1, 2
- Humidity
- 35 … 85% rH non condensing p. 1
- Refresh and memory
- Input, output and indication every 500 ms; settings kept in EEPROM p. 1, 2
- Connection leads
- Screw terminals for cables up to 2.5 mm² p. 1, 2
What this manual walks you through
- Viewing and changing the 1st set point p. 1
- Switching between automatic and manual output control p. 1
- Entering the 2nd and 3rd configuration levels p. 1, 2
- Choosing the sensor type and °C or °F scale p. 1, 2
- Setting the alarm or fixed point action of the 2nd and 3rd points p. 1, 2
- Setting PID values, cycle time and autotuning p. 1, 2
- Locking configuration levels p. 1
- Wiring power, RTD, thermocouple, relay and transistor outputs p. 1
- Mounting the controller in a panel p. 1
- Reading error messages and loop fault alerts p. 1
Good to know
- Do not power the controller straight from power lines, and keep it away from electric motors and other electrical noise. p. 1
- With inductive loads the relay contact current must be reduced according to the power factor. p. 1
- RTD leads must be alike and under 4 ohms each; for a 2 wire RTD, link terminals 13 and 14. p. 1
- With a relay 1st point output, a cycle time of at least 20 seconds is recommended. p. 1
- On OvFL, UnFL, 8888, FAIL or LFA2 the first point output is turned off. p. 1
Questions this manual answers
What does OvFL mean on an ES/ED temperature controller?
The reading is above the sensor range: the RTD Pt100 or thermocouple is broken or the main connection is interrupted. The first point output turns off. p. 1
How do I put the ES/ED controller into manual mode?
Hold the AUTO/MAN key until the MAN LED lights, then set the output from M0 to M100%; hold it again until the LED goes off to return to automatic. p. 1
What panel cut-out does the ES/ED controller need?
45.5x91 mm, in a panel 1 to 4 mm thick, held by a metal bracket fixed from the rear. p. 1
What sensor is the ES/ED controller set for from the factory?
The standard configuration uses a type J thermocouple (tc-J), -50 to +760 °C, with PID values P=20 °C, I=120 s and D=30 s. p. 1
What does LFA2 mean on the controller?
Loop Fault Alert with the 1st point turned off: the temperature did not change as expected at 100% output, so wrong configuration, lack of power, a broken heater or cooler, or a thermocouple fault is possible. p. 1
The file
Size and text
Every page · 2
Read it here
Each page as it is printed, and its words beside it, so a phone can search and copy them.
Page1of 2
Open in the PDF
The text of page 1, from the PDF itself
VIEWING AND SETTING OF THE 1st SET POINT st 1 configuration level To view the set point in the single display version, depress the SET key. To modify the set point act directly on the UP/DOWN keys, the new value is updated automatically when the indication UPDT appears or the SET key is pressed. By keeping the UP or DOWN keys depressed, the value will change at first slowly and then quickly. During the setting operations, regulation continues with the last stored value. The setting is locked if the option LOC1 is selected and the LOCK LED is lit up. MANUAL REGULATION OF THE OUTPUT POWER To change from automatic regulation (closed loop) to manual (open loop), keep the AUTO/MAN key depressed until the MAN LED turns on. The output power is at zero, make the 1st point setting operations to set the value from M0 to M100%. The regulator maintains the set value if switched off in manual regulation. To return to automatic regulation, keep the AUTO/MAN key depressed until the MAN LED turns off. VIEWING AND SETTING OF THE 2nd SET POINT nd rd 2 and 3 configuration levels (see the diagram on the right) nd rd To enter the 2 and 3 configuration levels, keep the PROG key depressed for more than 2 seconds. To change the values or the selections, use the UP/DOWN keys. To confirm and continue the configuration, depress the PROG key; to confirm and exit, depress the SET key. At the end of each level [End2] or [End3], you can repeat it by depressing the PROG key for less than 2 seconds or you can change the level by depressing the PROG key for more than 2 seconds. During the program scrolling the regulation continues, but it stops when a modification occurs. The setting exits automatically if no key is depressed within 30 seconds.
STANDARD CONFIGURATION
1/8 DIN MICROPROCESSOR TEMPERATURE CONTROLLER
ES/ED SERIES
- sw release 2.00 -
INSTRUCTION MANUAL FRONT PANEL Process value display
Settings: Autotuning: 1st point action: PID values: Cycle time: Adt function: 2nd point action.: Sensor: Scale and unity: Correction: LFA function: LOCK level:
1st pt.=0 °C; 2nd pt.=10 °C. AtOF = not active. automatic Pidd max. action. P=20 °C; I=120 s.; D=30 s. 20 s. relay vers.;12 s. transistor vers. Adt0 = not active. AL21 = alarm minimum action. tc-J = thermocouple type J. -50...+760 °C, without digital filter. 0.0 °C LFA0 = not active. LOC3 = levels 1 and 2 free, level 3 locked. CONNECTIONS
Process value display
set value display
deviation or output LED bar
2nd point output ON LED
special function LED (not used)
1st point output ON LED
active autotuning blinking LED
active LOCK LED function
active MAN function LED
setting SET key2. OUTPUT250Vac 5A RESISITIVE250Vac 5A RESISITIVE1. OUTPUT2. OUTPUTPOWER SUPPLY
TRANSISTOR VERSION (5VA
POWER SUPPLY
(5VA 250Vac 5A RESISITIVE
250Vac 5A RESISITIVEmanual function keyprogramming PROG keyTCBb
Electronic block extraction screw
Power consumption: Sensor input: Measurement precision *: 1st point control action: 1st point output: 2nd point control action: 2nd point output: Refresh time: Data retention: Insulation resistance: Operating temperature: Storage temperature: Humidity: Vibration resistance: Shock resistance: Housing: Mechanical protection: Connection leads: Dimensions: Weight:
version 12 … 24 Vdc/Vac ± 10%, 50/60 Hz; or version 80 … 240 Vac ± 10%, 50/60 Hz. 5VA max. thermocouple type J, K, E, T, R, S, L; with reference junction compensation; RTD Pt100 Ω/0 °C according to standard DIN43760; with 2 or 3 wires connection. RTD ± 0.3% fs, TC ± 0.4% fs, ±1 digit; (tc-r, tc-S ± 1% fs from 0 to 200°C) temperature drift 0.01% fs/°C of Tamb. automatic direct or reverse, ON/OFF or PID with autotuning; manual with output setting from 0 to 100%. relay version SPDT 250 Vac, 5 A on resistive load; or transistor version with 15 Vdc ± 20%, 20 mA short-circuit protected. ON/OFF with hysteresis ± 0.2 °C, direct or reverse, dead zone on or off, stand-by option; alarm or fixed point. relay SPDT 250 Vac, 5 A on resistive load. input, output and indication every 500 ms. non volatile memory type EEPROM. minimum 20 MΩ at 500 Vdc. -10 … +55 °C. -20 … +65 °C. 35 … 85% rH non condensing. 0.35 mm amplitude, 10…55 Hz frequency for every axis (EN60068-2-6) 18 ms (30 G) for every axis (EN60068-2-27) ABS IP50 front panel, IP20 case, IP00 contacts screw terminals for cables up to 2.5 mm². 1/8 DIN; 48x96x125 mm 400 g.
DECLARATION OF CONFORMITY We DATASENSOR S.p.A. declare under our sole responsibility that these products are conform to the 2004/108/CE, 2006/95/CE Directives and successive amendments.
RTD
Power supply input: do not supply the temperature controller directly through power lines and avoid installing near electric motors or other sources of electrical disturbance. Resistance thermometer input (RTD): ensure all conductors used to attach the resistance thermometer are alike and with a resistance less than 4 ohms/each; when using a 2 wire resistance thermometer, link terminals 13 and 14 together. Thermocouple input (TC): connect the sensor using the correct compensated extension cable for the utilized thermocouple. Relay output: in case of connected inductive loads, the maximum current permitted through the contacts decreases in relation to the power factor. Transistor output: when the output is high, the ON1 LED lights, the terminals 1 (+) and 3 (-) have a rating of 15 Vdc 20 mA, protected and suitable to drive a Solid State Relay (SSR), recommended in case of high currents or frequent switching. DIMENSIONS AND INSTALLATION 48
137
- Radiated radio-frequency electromagnetic fields (see ENV 50140), or conducted disturbances induced by radio-frequency fields (see ENV 50141), can be the cause of process value variations in any case not higher than ± 2 % fs.
A12125mm
Panel cut-out: 45.5x91 mm Panel thickness (suggested): 1 … 4 mm Insert the controller from panel front face, fix the metallic bracket on the rear of the controller with the proper nuts. WARRANTY DATASENSOR S.p.A. warrants its products to be free from defects. DATASENSOR S.p.A. will repair or replace, free of charge, any product found to be defective during the warranty period of 36 months from the manufacturing date. This warranty does not cover damage or liability deriving from the improper application of DATASENSOR products.
DATASENSOR S.p.A. Via Lavino 265 40050 Monte S. Pietro - Bologna - Italy Tel: +39 051 6765611 Fax: +39 051 6759324 http://www.datasensor.com e-mail: info@datasensor.com DATASENSOR S.p.A. cares for the environment: 100% recycled paper. DATASENSOR S.p.A. reserves the right to make modifications and improvements without prior notification.
826000951 Rev. A
Exit from every point of the program nd
2
level
SENSOR RTD Pt100 ohm/0°C RTD Pt100 ohm/0°C TC Pt10%Rh-Pt, TC Pt13%Rh-Pt, TC Cu-CuNi, TC NiCr-CuNi, TC NiCr-NiAl, TC Fe-Cuni, TC Fe-Cuni,
°C SCALE int. -150 ... 450 dec. -99.9 ... 450.0 type S 0 ... 1700 type R 0 ... 1700 type T -100 ... 400 type E 0 ... 600 type K -100 ... 1250 type J -50 ... 760 type L -50 ... 760 Table 2
PROG
(PROG depressed for more than 2 seconds)
A L 2 1
2nd point code - (value follows). 2nd point setting value in °C/°F. ALxx: -999 … +999 relative to 1st point. FPxx: independent over full scale. (see note A)
1
A t O F
AtOf: autotuning not active. AtOn: autotuning active.
E n d 2
End of the second configuration level.
PROG
(PROG depressed for less than 2 seconds)
PROG
3rd level
(PROG depressed for more than 2 seconds) Pidd: 1st point PID max. action. Pidr: 1st point PID min. action. OnFd: 1st point on/off max. action. OnFr:1st point on/off min. action.
P i d dHPROG1.0
H: on/off hysteresis ± 0.1 … ± 99.9 °C/°F
PROG P20
P: proportional band 1 …999 °C/°F.
PROG i 1 2 0
i: integrative time 0 …960 sec.
PROG d30
d: derivative time 0 …240 sec.
PROG 1
2
t: cycle time 1 …120 sec. (see note B)
PROG A d t 0 PROG A L 2 1
Adt0:Adaptative function not active. Adt1: Adaptative function active. (see note C) ALxx/FPxx: 2nd point control action.(see Table 1 on the left)
PROG tcJ
tc-x/rt-x: input sensor. (see Table 2 on the left and note D)
PROG
°F SCALE -200 ... 850 -99.9 ... 850.0 30 ... 3000 30 ... 3000 -150 ... 750 0 ... 1100 -150 ... 2300 -50 ... 1400 -50 ... 1400
ERROR AND TEST MESSAGGES
U °C n PROG
Lower set point code - value follows. -
5
0
H S P Higher set point code - value follows.
OvFL
Overflow, indication over the sensor range. RTD Pt100 or TC sensor broken or interruption of the main connection.
PROG
8888
Au...-test, if the message remains fixed the controller must be repaired.
°0.
General failure; the controller must be repaired.
PROG
LFA: DETECTION OF FAULTS IN THE REGULATION LOOP Loop Fault Alert: with the 1st point output 100% ON state the measured temperature is not changed according ... the control action within the LFA2 s...red integral time; a fault in the regulation loop is possible: wrong configuration, lack of power, heater or cooler broken, thermocouple shortcircuited or polarity reversed, etc. ... reset the LFA function, please modify the configuration or the set-point, or switch the temperature controller off and then on again. The function LFA is not active in the following cases: with output lower than 100% ON, with integral time at zero, during the au...tuning, in manual position. NOTE: In case of OvFL, UnFL, 8888, FAIL, LFA2, the first point output is turned off.
1st point setting lower limit. (see note D)
PROG
Underflow, indication below the sensor range. Short circuit of the sensor RTD Pt100 or interruption of the compensation connection.
LFA1
U°Cn: Celsius degrees, without digital filtering. U°Cd: Celsius degrees, with digital filtering. U°Fn: Fahrenheit degrees, without digital filtering. U°Fd: Fahrenheit degrees, with digital filtering. (see note E)
L S PUnFLFAIL0PROG
Table 1 CODE rt l rt d tc S tc r tc t tc E tc C tc J tc L
(QS-ES PROCESS VALUE)SET VALUESETt
ALARM FIXED POINT 2ND POINT CONTROL ACTION AL20 Output blocked with relay off FP20 AL21 Minimum action FP21 AL22 Maximum action FP22 AL23 Dead zone on FP23 AL24 Dead zone off FP24 AL25 Minimum action with stand-by FP25 AL26 Maximum action with stand-by FP26 AL27 Dead zone on with stand-by FP27 AL28 Dead zone off with stand-by FP28 In this area the relay contact is closed. In this area the relay contact is closed when the alarm set-point or fixed point is passed for the second time.
96
- TECHNICAL DATA Power supply
- PROGRAMMING NOTES A) in case of second point with dead zone, the indication [2 LO] will appear followed by the lower limit value, then [2 HI] followed by the higher limit value; the autotuning selection will appear only in case of PID control action. B) in case of relay 1st point output, a minimum cycle time of 20 seconds [t 20] is recommended. C) adaptative function to improve the response to frequent or fast variations of the load, i.e. start and stop process. D) settings not included in the sensor scale or in the setting limits, are automatically corrected with the nearest threshold limit value. E) in case of Fahrenheit degrees selection, please cover the °C symbol on the front panel with the label °F which is supplied with the controller.
RELAY VERSIONdecreasing DOWN keyincreasing UP key1. OUTPUT1st level7 6 00
L F A 0 PROG L O C 3 PROG E n d 3 PROG
1st point setting higher limit. (see note D)
Correction -99.9 … 99.9 °C/°F.
LFA0: loop fault alert not active. LFA1: LFA indication active. LFA2: LFA indication active with 1st point OFF in case of loop fault detection. FREE: levels 1, 2, 3 free. LOC3: levels 1 and 2 free, level 3 locked. LOC2: level 1 free, levels 2 and 3 locked. LOC1: levels 1, 2, 3 locked. End of the third configuration level. PROG depressed for less than 2 seconds) (PROG depressed for more than 2 seconds)
PROG
Page2of 2
Open in the PDF
The text of page 2, from the PDF itself
VIEWING AND SETTING OF THE 1st SET POINT st 1 configuration level To view the set point in the single display version, depress the SET key. To modify the set point act directly on the UP/DOWN keys, the new value is updated automatically when the indication UPDT appears or the SET key is pressed. By keeping the UP or DOWN keys depressed, the value will change at first slowly and then quickly. During the setting operations, regulation continues with the last stored value. The setting is locked if the option LOC1 is selected and the LOCK LED is lit up. MANUAL REGULATION OF THE OUTPUT POWER To change from automatic regulation (closed loop) to manual (open loop), keep the AUTO/MAN key depressed until the MAN LED turns on. The output power is at zero, make the 1st point setting operations to set the value from M0 to M100%. The regulator maintains the set value if switched off in manual regulation. To return to automatic regulation, keep the AUTO/MAN key depressed until the MAN LED turns off. VIEWING AND SETTING OF THE 2nd AND 3rd SET POINTS nd rd 2 and 3 configuration levels (see the diagram on the right) nd rd To enter the 2 and 3 configuration levels, keep the PROG key depressed for more than 2 seconds. To change the values or the selections, use the UP/DOWN keys. To confirm and continue the configuration, depress the PROG key; to confirm and exit, depress the SET key. At the end of each level [End2] or [End3], you can repeat it by depressing the PROG key for less than 2 seconds or you can change the level by depressing the PROG key for more than 2 seconds. During the program scrolling the regulation continues, but it stops when a modification occurs. The setting exits automatically if no key is depressed within 30 seconds.
STANDARD CONFIGURATION
1/8 DIN MICROPROCESSOR TEMPERATURE CONTROLLER
ES/ED SERIES
- sw release 3.00 -
INSTRUCTION MANUAL FRONT PANEL Process value display
Process value display
set value display
deviation or output LED bar
2nd point output ON LED
3rd point output ON LED
1st point output ON LED
active autotuning blinking LED
Settings: Autotuning: 1st point action: PID values: Cycle time: Adt function: 2nd point action.: 3rd point action.: Sensor: Scale and unity: Correction: LFA function: LOCK level:
CONNECTIONS 1. OUTPUT
active MAN function LED
setting SET key(5VA m ax.)3. OUTPUT
1st point output: 2nd point control action: 2nd point output: 3rd point control action: 3rd point output: Refresh time: Data retention: Insulation resistance: Operating temperature: Storage temperature: Humidity: Vibration resistance: Shock resistance: Housing: Mechanical protection: Connection leads: Dimensions: Weight:
250Vac 5A m ax. RESISITIVE LOAD
version 12 … 24 Vdc/Vac ± 10%, 50/60 Hz; or version 80 … 240 Vac ± 10%, 50/60 Hz. 5VA max. thermocouple type J, K, E, T, R, S, L; with reference junction compensation; RTD Pt100 Ω/0 °C according to standard DIN43760; with 2 or 3 wires connection. RTD ± 0.3% fs, TC ± 0.4% fs, ±1 digit; (tc-r, tc-S ± 1% fs from 0 to 200°C) temperature drift 0.01% fs/°C of Tamb. automatic direct or reverse, ON/OFF or PID with autotuning; manual with output setting from 0 to 100%. relay version SPDT 250 Vac, 5 A on resistive load; or transistor version with 15 Vdc ± 20%, 20 mA short-circuit protected. ON/OFF with hysteresis ± 0.2 °C, direct or reverse, dead zone on or off, stand-by option; alarm or fixed point. relay SPDT 250 Vac, 5 A on resistive load. ON/OFF with hysteresis ± 0.2 °C, direct or reverse, dead zone on or off, stand-by option; alarm or fixed point. relay SPST 250 Vac, 5 A on resistive load. input, output and indication every 500 ms. non volatile memory type EEPROM. minimum 20 MΩ at 500 Vdc. from -10 … +55 °C. from -20 … +65 °C. from 35 … 85% rH non condensing. 0.35 mm amplitude, 10…55 Hz frequency for every axis (EN60068-2-6) 18 ms (30 G) for every axis (EN60068-2-27) ABS IP50 front panel, IP20 case, IP00 contacts screw terminals for cables up to 2.5 mm². 1/8 DIN; 48 x 96 x 125 mm 400 g.
- Radiated radio-frequency electromagnetic fields (see ENV 50140), or conducted disturbances induced by radio-frequency fields (see ENV 50141), can be the cause of process value variations in any case not higher than ± 2 % fs.
DECLARATION OF CONFORMITY We DATASENSOR S.p.A. declare under our sole responsibility that these products are conform to the 2004/108/CE, 2006/95/CE Directives and successive amendments.
TCBbARTD
Power supply input: do not supply the temperature controller directly through power lines and avoid installing near electric motors or other sources of electrical disturbance. Resistance thermometer input (RTD): ensure all conductors used to attach the resistance thermometer are alike and with a resistance less than 4 ohms/each; when using a 2 wire resistance thermometer, link terminals 13 and 14 together. Thermocouple input (TC): connect the sensor using the correct compensated extension cable for the utilized thermocouple. Relay output: in case of connected inductive loads, the maximum current permitted through the contacts decreases in relation to the power factor. Transistor output: when the output is high, the ON1 LED lights, the terminals 1 (+) and 3 (-) have a rating of 15 Vdc 20 mA, protected and suitable to drive a Solid State Relay (SSR), recommended in case of high currents or frequent switching. DIMENSIONS AND INSTALLATION 48
13796TECHNICAL DATA
- 1st point control action
- POWER SUPPLY
(5VA m ax.) 250Vac 5A m ax. RESISITIVE LOAD
Electronic block extraction screw
- Measurement precision *
- 2. OUTPUT
RELAY VERSIONmanual function keyprogramming PROG key
- Power consumption: Sensor input
- POWER SUPPLY
250Vac 5A m ax. RESISITIVE LOAD
decreasing DOWN keyincreasing UP key2. OUTPUTTRANSISTOR VERSION1. OUTPUT
active LOCK LED function
- Power supply
- 1st pt.=0 °C; 2nd pt.=10 °C; 3rd pt.=10 °C. AtOF = not active. automatic Pidd max. action. P=20 °C; I=120 s.; D=30 s. 20 s. relay vers.;12 s. transistor vers. Adt0 = not active. AL21 = alarm minimum action. AL31 = alarm minimum action. tc-J = thermocouple type J. -50 ... +760 °C, without digital filter. 0.0 °C LFA0 = not active. LOC3 = levels 1 and 2 free, level 3 locked.
PROGRAMMING NOTES A) in case of second point with dead zone, the indication [2 LO] will appear followed by the lower limit value, then [2 HI] followed by the higher limit value. B) in case of third point with dead zone, the indication [3 LO] will appear followed by the lower limit value, then [3 HI] followed by the higher limit value; the autotuning selection will appear only in case of PID control action. C) in case of relay 1st point output, a minimum cycle time of 20 seconds [t 20] is recommended. D) adaptative function to improve the response to frequent or fast variations of the load, i.e. start and stop process. E) settings not included in the sensor scale or in the setting limits, are automatically corrected with the nearest threshold limit value. F) in case of Fahrenheit degrees selection, please cover the °C symbol on the front panel with the label °F which is supplied with the controller. ALARM FIXED POINT 2ND, 3RD POINT CONTROL ACTION AL20 / AL30 FP20 / FP30 Output blocked with relay off AL21 / AL31 FP21 / FP31 Minimum action AL22 / AL32 FP22 / FP32 Maximum action AL23 / AL33 FP23 / FP32 Dead zone on AL24 / AL34 FP24 / FP34 Dead zone off AL25 / AL35 FP25 / FP35 Minimum action with stand-by AL26 / AL36 FP26 / FP36 Maximum action with stand-by AL27 / AL37 FP27 / FP37 Dead zone on with stand-by AL28 / AL38 FP28 / FP38 Dead zone off with stand-by In this area the relay contact is closed. In this area the relay contact is closed when the alarm set-point or fixed point is passed for the second time.
mm
Panel cut-out: 45.5 x 91 mm Panel thickness (suggested): 1 … 4 mm Insert the controller from panel front face, fix the metallic bracket on the rear of the controller with the proper nuts.
WARRANTY DATASENSOR S.p.A. warrants its products to be free from defects. DATASENSOR S.p.A. will repair or replace, free of charge, any product found to be defective during the warranty period of 36 months from the manufacturing date. This warranty does not cover damage or liability deriving from the improper application of DATASENSOR products.
DATASENSOR S.p.A. Via Lavino 265 40050 Monte S. Pietro - Bologna - Italy Tel: +39 051 6765611 Fax: +39 051 6759324 http://www.datasensor.com e-mail: info@datasensor.com DATASENSOR S.p.A. cares for the environment: 100% recycled paper. DATASENSOR S.p.A. reserves the right to make modifications and improvements without prior notification.
826000083 Rev. C
(PROG depressed for more than 2 seconds)
PROG
level
2nd point code - (value follows). 2nd point setting value in °C/°F. ALxx: -999 … +999 relative to 1st point. FPxx: independent over full scale. (see note A)
A L 2 1 10A L 3 1 1
3rd point code - (value follows). 3rd point setting value in °C/°F. ALxx: -999 … +999 relative to 1st point. FPxx: independent over full scale. (see note B)
0
A t O F AtOF: autotuning not active. AtOn: autotuning active.
E n d 2
End of the second configuration level. (PROG depressed for less than 2 seconds)
PROG
(PROG depressed for more than 2 seconds)
PROG
3rd level
Pidd: 1st point PID max. action. Pidr: 1st point PID min. action. OnFd: 1st point on/off max. action. OnFr:1st point on/off min. action.
P i d dHPROG1.0
H: on/off hysteresis from ± 0.1 … ± 99.9 °C/°F
PROG P20
P: proportional band 1 … 999 °C/°F.
PROG i 1 2 0
i: integrative time 0 … 960 sec.
PROG d30
d: derivative time 0 … 240 sec.
PROG t12A d t 0
t: cycle time 1 … 120 sec. (see note C)
PROG
Adt0:Adaptative function not active. Adt1: Adaptative function active. (see note D)
A L 2 1
ALxx/FPxx: 2nd point control action (see Table 1 on the left)
PROG A L 3 1
CODE rt l rt d tc S tc r tc t tc E tc C tc J tc L
SENSOR RTD Pt100 ohm/0°C RTD Pt100 ohm/0°C TC Pt10%Rh-Pt, TC Pt13%Rh-Pt, TC Cu-CuNi, TC NiCr-CuNi, TC NiCr-NiAl, TC Fe-Cuni, TC Fe-Cuni,
°C SCALE int. -150 … 450 dec. -99.9 ... 450.0 type S 0 ... 1700 type R 0 ... 1700 type T -100 ... 400 type E 0 ... 600 type K -100 ... 1250 type J -50 ... 760 type L -50 ... 760 Table 2
°F SCALE -200 ... 850 -99.9 ... 850.0 30 ... 3000 30 ... 3000 -150 ... 750 0 ... 1100 -150 ... 2300 -50 ... 1400 -50 ... 1400
Underflow, indication below the sensor range. Short circuit of the sensor RTD Pt100 or interruption of the compensation connection.
tcJU °C n PROG
U°Cn: Celsius degrees, without digital filtering. U°Cd: Celsius degrees, with digital filtering. U°Fn: Fahrenheit degrees, without digital filtering. U°Fd: Fahrenheit degrees, with digital filtering. (see note F)
L S P Lower set point code - value follows. -
5
0
1st point setting lower limit. (see note E)
PROG H S P 7 6 0 PROG
Overflow, indication over the sensor range. RTD Pt100 or TC sensor broken or interruption of the main connection.
°0.
8888
Au...-test, if the message remains fixed the controller must be repaired.
PROG
FAIL
General failure; the controller must be repaired.
0L F A 0 PROGLFA1
NOTE: In case of OvFL, UnFL, 8888, FAIL, LFA2, the first point output is turned off.
tc-x/rt-x: input sensor. (see Table 2 on the left and note E)
PROG
OvFL
LFA: DETECTION OF FAULTS IN THE REGULATION LOOP Loop Fault Alert: with the 1st point output 100% ON state the measured temperature is not changed according ... the control action within the L F A 2 s...red integral time; a fault in the regulation loop is possible: wrong configuration, lack of power, heater or cooler broken, thermocouple shortcircuited or polarity reversed, etc. ... reset the LFA function, please modify the configuration or the set-point, or switch the temperature controller off and then on again. The function LFA is not active in the following cases: with output lower than 100% ON, with integral time at zero, during the au...tuning, in manual position.
ALxx/FPxx: 3rd point control action. (see Table 1 on the left)
PROGTable 1UnFL 1252nd(ES PROCESS VALUE)SET VALUESETPROG
ERROR AND TEST MESSAGGES
12
1st level Exit from every point of the program
L O C 3
Higher set point code - value follows. 1st point setting higher limit. (see note E) Correction -99.9 … 99.9 °C/°F. LFA0: Loop Fault Alert not active. LFA1: LFA indication active. LFA2: LFA indication active with 1st point OFF in case of loop fault detection. FREE: levels 1, 2, 3 free. LOC3: levels 1 and 2 free, level 3 locked. LOC2: level 1 free, levels 2 and 3 locked. LOC1: levels 1, 2, 3 locked.
PROG End of the third configuration level. E n d 3 PROG PROG
(PROG depressed for less than 2 seconds) (PROG depressed for more than 2 seconds)