Page 23
INSTALLATION
2
DS4600A
USER INTERFACE 2
TX485+
4
TX485-
3
RX485+
5
RX485-
7
SGND Main
RX485
TX485
RS485REF Earth Ground
Figure 10 - RS485 Full-Duplex Connections
RS485 Half-Duplex Interface The RS485 half-duplex (3 wires + shield) interface is used for polled communication protocols. It can be used for Multidrop connections in a master/slave layout or with a Datalogic Multiplexer, (see par. 2.6.4 and 2.6.5). The following pins of the 25-pin connector are used for RS485 half-duplex communications: Pin 2 4 7
Name RTX485+ RTX485SGND Main
Function RS485 transmitted/received data + RS485 transmitted/received data signal ground main interface
DS4600A
MULTIPLEXER 2
RTX485+
4
RTX485-
7 SGND Main
RTX485+ RTX485RS485REF
Figure 11 - RS485 Half-Duplex Connections
11
Page 24
DS4600A
2
The figure below shows a multidrop configuration with DS4600A scanners connected to a Multiplexer. max. 2 m.
1
DS4600A
2
#x
4
(up to 31)
7
DS4600A
2
#1
4
1
CHASSIS
120 Ohm
7 DS4600A
2
#0
4
1
7 max. 1200 m.
RTX485+ RTX485SGND Main three wires + shield RTX485+
MULTIPLEXER
RTX485RS485REF SHIELD
120 Ohm Figure 12 - DS4600A Multidrop Connection to a Multiplexer
12
Page 25
INSTALLATION
2
20 mA Current Loop (C-Box 100 w/INT-30 Accessory Only) To adapt DS4600A to 20 mA current loop interfaces, it must be connected to a C-BOX 100 equipped with an INT-30 (20 mA current loop adapter accessory board). The INT-30 converts RS232 communication on the scanner into 20 mA current loop signals to the host. See the C-BOX 100 Installation Manual and the INT-30 instructions.
2.3.3
Auxiliary RS232 Interface
The auxiliary serial interface is used exclusively for RS232 point-to-point connections. The parameters relative to the auxiliary interface (baud rate, data bits, etc.) as well as particular communication modes such as Local Echo can be defined using the WinHost utility program or Host Mode programming. For more details refer to paragraph 2.6 and to the section "Auxiliary Interface Menu" in the WinHost Help On Line. The following pins of the 25-pin connector are used to connect the RS232 auxiliary interface: Pin 20 21 23
Name RXAUX TXAUX SGND Aux
Function auxiliary RS232 received data auxiliary RS232 transmitted data signal ground auxiliary interface
DS4600A
USER INTERFACE 20
RXAUX
21 TXAUX 23
SGND Aux
TXD RXD SGND
Figure 13 - RS232 Auxiliary Interface Connections
When the auxiliary interface is permanently connected as part of the system cabling, it is recommended to connect the cable shield to earth ground.
13
Page 26
DS4600A
2
2.3.4
Inputs
There is an input available on the DS4600A scanner relative to the External Trigger. There are also 2 general purpose inputs: IN1 can be used to store the code verifier (see "Store verifier HW" in the WinHost Help On Line). IN2 can be used as the Reading Field Control signal which determines either the Code Reading Condition or the Code Resolution parameter for each reading phase. Refer to the WinHost Help On Line. The pinouts are indicated below: Pin 18 19 6 10 14 15
Name EXT TRIG+ EXT TRIGIN1+ IN1IN2+ IN2-
Function external trigger + external trigger input 1 + input 1 input 2 + input 2 -
The EXT TRIG inputs are used in the On-Line Operating mode and tells the scanner to scan for a code. The active state of this input is selected in software. Refer to the WinHost Help On Line. The yellow led, (Figure A, 7), is on when the External Trigger signals the active reading phase. These inputs are optocoupled and can be driven by both an NPN or PNP type command. The connections are indicated in the following diagrams: Vext 30 Vdc max.
DS4600A + 5V
18/6/14
+
19/10/15
-
USER INTERFACE V
Signal
Figure 14 - Input NPN Command Using External Power
14
Page 27
INSTALLATION
2 DS4600A
+ 5V
USER INTERFACE 9
VS
18/6/14
+
19/10/15
-
25
GND
V
Signal Ground
Figure 15 - Input NPN Command Using DS4600A Power
Vext 30 Vdc max.
USER INTERFACE
DS4600A
V + 5V 18/6/14
+
19/10/15
-
Signal
Ground
Figure 16 - Input PNP Command Using External Power
DS4600A
+ 5V
USER INTERFACE 9
VS
18/6/14
+
19/10/15
-
25
GND
V Signal
Figure 17 - Input PNP Command Using DS4600A Power
15
Page 28
DS4600A
2
The electrical features of the inputs are: Maximum voltage = 30 Vdc Maximum current = 25 mA. An anti-disturbance hardware filter is implemented on the External Trigger input (< 5 milliseconds delay). An additional 15 ms (typical) delay can be implemented through a dedicated software parameter (refer to WinHost Help On Line).
2.3.5
Outputs
The following pins are present on the 25-pin connector of the scanner: Pin 8 22 11 12
Name OUT1+ OUT1OUT2+ OUT2-
Function output 1 + output 1 output 2 + output 2 -
The meaning of the two outputs OUT1 and OUT2 can be defined by the user (No Read, Right or Wrong). Refer to WinHost Help On Line. By default, OUT1 is associated with the No Read event, which activates when the code signaled by the External Trigger is not decoded. OUT2 is associated with the Right event, which activates when the code is decoded correctly.
DS4600A
USER INTERFACE Vext 40 Vdc max
C
8/11
+
22/12
-
E Figure 18 - Open Collector Output Connection
These outputs are both level or pulse configurable.
16
Page 29
INSTALLATION
2.4
2
USER INTERFACE RS232 PC-side connections 5
1
6
9
9-pin male connector
Pin 2 3 5 7 8
1
13
14
25
25-pin male connector
Name RX TX GND RTS CTS
Pin 3 2 7 4 5
Name RX TX GND RTS CTS
How To Build A Simple Interface Test Cable:
The following wiring diagram shows a simple test cable including power, external (push-button) trigger and PC RS232 COM port connections. 25-pin D-sub male
9-pin D-sub female
21
TXAUX
2
RX
20
RXAUX
3
TX
23 SGND
5
GND
PC
13 VS 25 GND
DS4600A
9
VS
18 EXT TRIG+ 19 EXT TRIG-
Power Supply VS (10 – 30 Vdc) Power GND
Trigger
Test Cable for DS4600A
17