Page 21

INSTALLATION

2.3.1

2

Power Supply

Power can be supplied to the scanner through the pins provided on the 25- or 9-pin connector used for communication with the host (Figure 6): DS2100 9-pin

DS2100 25-pin

7

13

USER INTERFACE VS

VS

V+ (10 - 30 Vdc) 5 or

25

GND

1

CHASSIS

GND 1 CHASSIS

VGND CHASSIS

Earth Ground

Figure 6 - Power supply connections

The power must be between 10 and 30 Vdc only. It is recommended to connect pin 1 (CHASSIS) to a common earth ground.

2.3.2

Main Serial Interface

The signals relative to the following serial interface types are available on the input/output connector of DS2100 depending on the DS2100 model (see par. 1.3). A passive 20-mA Current Loop interface is available if the optional INT-22 accessory is installed. This accessory interface replaces the main serial interface of the DS2100 model. The INT-22 accessory board is not available for DS2100-X3X0 models. If the interface type is not compatible with the current communication handshaking, then the system forces the handshake to none. The parameters relative to the interface selected (baud rate, data bits, etc.) can be defined using the WinHost utility program or "Host Mode" programming procedure through ESC sequences installed from the diskette. Details regarding the connections and use of the interfaces are given in the next paragraphs.

9

Page 22

DS2100

2

RS232 Interface The serial interface is used in this case for point-to-point connections; it handles communication with the host computer and allows both transmission of code data and the programming of the scanner. This is the default setting. The following pins are used for RS232 interface connection: Connector 9-Pin

25-Pin

2 3 6 4 5

2 3 4 5 7

Name

Function

TX232 RX232 RTS232 CTS232 GND/SGND transmitted data received data request to send clear to send signal ground

It is always advisable to use shielded cables. The overall maximum cable length must be less than 15 m (49.2 ft).

DS2100 25-pin

DS2100 9-pin TX232 RX232 RTS232 CTS232 SGND

USER INTERFACE

2

2

TX232

3

3

RX232

TXD

4

RTS232

DCD

5

CTS232

DTR

7

SGND

6 4 5 or

RXD

SGND Earth Ground

Figure 7 – RS232 main interface connections using hardware handshaking

The RTS232 and CTS232 signals control data transmission and synchronize the connected devices.

10

Page 23

INSTALLATION

2 START OF TRANSMISSION

END OF TRANSMISSION

+V RTS -V

DATA TRANSMISSION

DATA TRANSMISSION

+V TX DATA -V

C1 C2

C3

C4

C5

TRANSMISSION STOPPED ENABLED

+V CTS -V

ENABLED

DISABLED

IDLE

IDLE

Figure 8 - RS232 control signals

If the RTS/CTS handshaking protocol is enabled, the DS2100 activates the RTS232 output to indicate a message is to be transmitted. The receiving unit activates the CTS232 input to enable the transmission.

RS485 Full-Duplex Interface The RS485 full-duplex (5 wires + shield) interface is used for non-polled communication protocols in point-to-point connections over longer distances (max 1200 m / 3940 ft) than those acceptable for RS232 communications or in electrically noisy environments. The connector pinout follows: Connector 25-Pin 2 4 3 5 7

Name

Function

TX485+ TX485RX485+ RX485SGND

RS485 transmitted data + RS485 transmitted data RS485 received data + RS485 received data signal ground

11

Page 24

DS2100

2 DS2100 25-pin

USER INTERFACE

2

TX485+

4

TX485-

3

RX485+

5

RX485-

7

SGND

+ RX485 + TX485 +

SGND

Earth Ground

Figure 9 - RS485 full-duplex connections

RS485 Half-Duplex Interface The RS485 half-duplex (3 wires + shield) interface is used for polled communication protocols. It can be used in a master/slave layout or for Multidrop connections with a Datalogic Multiplexer, (see par. 2.5.4 and 2.5.5) exploiting a proprietary protocol based on polled mode called MUX32 protocol, where a master device polls slave devices to collect data. The connector pinout follows: Connector

Name

Function

RTX485+ RTX485SGND

RS485 transmitted/received data + RS485 transmitted/received data signal ground

25-Pin 2 4 7

DS2100 25-pin

MULTIPLEXER 2

RTX485 +

4

RTX485 -

7

SGND

RTX485 + RTX485 RS485REF

Figure 10 - RS485 half-duplex connections

This interface is forced by software when the protocol selected is MUX32 protocol.

12

Page 25

INSTALLATION

2

In a Multiplexer layout or for slaves, the Multidrop address must also be set via serial channel by the WinHost utility or by ESC sequences. Figure 11 shows a multidrop configuration with DS2100 scanners connected to a Multiplexer. 120 Ohm max 2 m DS2100 #x (up to 31)

max 1200 m

DS2100 #1 RTX485 +

DS2100 #0 CHASSIS

RTX485 SGND

Three wires + shield RTX485 + RTX485 MULTIPLEXER RS485 REF SHIELD

120 Ohm

Figure 11 - DS2100 Multidrop connection to a Multiplexer

13

Page 26

DS2100

2

20 mA Current Loop Interface (INT-22 Accessory Only) When the INT-22 accessory board is installed, the DS2100 is equipped with a 20 mA passive current loop. The following pins of the 25-pin connector are used: Connector 25-Pin 5 3 4 2

Name

Function

CLINCLIN+ CLOUTCLOUT+ current loop input current loop input + current loop output current loop output +

DS2100 25-pin

USER INTERFACE

5

C.L. IN-

3

C.L. IN+

4

C.L. OUT-

2

C.L. OUT+

I = 20 mA

I = 20 mA

MAX. 300 METERS

Figure 12 - 20 mA C.L. connections

14

Page 27

INSTALLATION

2.3.3

2

Auxiliary RS232 Interface

The auxiliary serial interface is used exclusively for RS232 point-to-point connections. The parameters relative to the aux interface (baud rate, data bits, etc.) as well as particular communication modes such as LOCAL ECHO can be defined using the WinHost utility program or "Host Mode Programming", installed from the diskette. The following pins of the 25-pin connector are used to connect the RS232 auxiliary interface:

Connector

Name

Function

RXAUX TXAUX CTSAUX RTSAUX SGND received data transmitted data clear to send request to send signal ground

25-Pin 20 21 23 24 7

DS2100 25-pin

USER INTERFACE

20 RXAUX

TXD

21 TXAUX RXD 23 CTSAUX 24 RTSAUX 7

SGND

DTR DCD SGND

Figure 13 - RS232 auxiliary interface connections using hardware handshaking

When the auxiliary interface is permanently connected as part of the system cabling, it is recommended to connect the cable shield to earth ground. The RTSAUX and CTSAUX signals control data transmission and synchronize the connected devices. If the RTS/CTS handshaking protocol is enabled, the DS2100 activates the RTSAUX output to indicate a message is to be transmitted. The receiving unit activates the CTSAUX input to enable the transmission.

15

Page 28

DS2100

2

Code Verifier If the DS2100 is used as a Code Verifier, it is possible to indicate to the scanner what code to store as the verifier code by means of an external hardware input. The Code Verifier parameter must be enabled and the configuration parameters to allow correct Code Type reading must be saved to the scanner in order to read the verifier code. To activate the input, connect together pins 23 and 24 (CTSAUX and RTSAUX) of the 25-pin connector (for example with a push-button), before the active edge of the External Trigger input (or before the code passes under the laser beam for the Automatic operating mode). The next read code will be stored as the verifier code in the scanner's RAM and NON-VOLATILE (EEPROM) memory by default. Then, the two pins must be disconnected. Since it uses part of the RS232 auxiliary serial interface, this interface is limited when using this option and the Handshake selection must not be set to RTS/CTS.

2.3.4

Inputs

The inputs available on the connector supplied with the scanner are the pins relative to the External Trigger, as indicated below:

Connector 9-Pin

25-Pin

8 9

18 19

Name

Function

EXT TRIG+ EXT TRIG- external trigger + external trigger -

The External Trigger input is used in the On-Line operating Mode and tells the scanner to scan for a code. The active state of this input is selected in software. Refer to the WinHost Help On Line. The yellow LED (Figure A, 4) is on when the External Trigger forces a current flow through the EXT TRIG+ and EXT TRIG- pins. This input is optocoupled and can be driven by both an NPN or PNP type command. The connections are indicated in the following diagrams:

16

Page 29

INSTALLATION

2

DS2100 9-pin

DS2100 25-pin 8

EXT TRIG +

18

EXT TRIG+

19

EXT TRIG-

V or

9

EXT TRIG -

Vext 30 Vdc max. EXTERNAL TRIGGER

+ 5V

Signal

Figure 14 - Input NPN command using external power

DS2100 9-pin

DS2100 25-pin

7

VS

EXTERNAL TRIGGER 9

+ 5V

VS

V

18 EXT TRIG+

8 EXT TRIG+ or

9

EXT TRIG-

19 EXT TRIG25

5

Signal GND

Ground

GND

Figure 15 - Input NPN command using DS2100 power

DS2100 9-pin

Vext 30 Vdc max.

DS2100 25-pin

EXTERNAL TRIGGER V

+ 5V

8

EXT TRIG+ or

9

EXT TRIG-

Signal

18 EXT TRIG+ 19

EXT TRIGGround

Figure 16 - Input PNP command using external power

DS2100 9-pin

EXTERNAL TRIGGER

DS2100 25-pin 9

7 VS

+ 5V 8

VS

18

EXT TRIG+

19

EXT TRIG-

25

GND

V Signal

EXT TRIG+ 9 or

EXT TRIG5 GND

Ground

Figure 17 - Input PNP command using DS2100 power

17

Page 30

DS2100

2 Electrical features:

Maximum voltage: Maximum current:

30 Vdc 25 mA

An anti-disturbance hardware filter is implemented on the External Trigger input (< 5 milliseconds delay). An additional 15 ms (typical) delay can be implemented through a dedicated software parameter (refer to WinHost Help On Line).

2.3.5

Outputs

Two general purpose outputs are available which can be connected only in open collector configurations. The outputs are available only on 25-pin connector models. The following pins are present on the 25-pin connector of the scanner:

Connector

Name

Function

OUT1+ OUT2+ OUT REF output 1 + output 2 + output reference

25-Pin 8 11 12, 22

The meaning of the two outputs OUT1 and OUT2 can be defined by the user (No Read, Right or Wrong). Refer to the WinHost Help On Line. By default, OUT1 is associated with the No Read event, which activates when the code signaled by the external trigger is not decoded, and OUT2 is associated with the Right event, which activates when the code is correctly decoded.

DS2100 25-pin

USER INTERFACE

8/11

+

12/22

OUT REF

Vext 40 Vdc max

Figure 18 - Output open collector connections

These outputs are both level or pulse configurable.

18