The text of a manual · part 8 of 18

AtomScan+ Bar Code Readers User Manual (Cat. Nos. 2755-LS7-SA, 2755-LS7-SB, 2755-LS7-RA, 2755-LS7-RB, 2755-LS7-SBV, and 2755-LS7-RBV): 5 - Configuring Your Reader, pages 66 to 75

Pages 66 to 75 of 141, from AtomScan+ Bar Code Readers User Manual (Cat. Nos. 2755-LS7-SA, 2755-LS7-SB, 2755-LS7-RA, 2755-LS7-RB, 2755-LS7-SBV, and 2755-LS7-RBV)

The original document is the PDF (914 KB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.

For the Allen-Bradley 2755-LS7

Page 66

Configuring Your Reader

5–21

Relay–1 and Relay–2

• Output On. Allows you to set the conditions that will output a relay pulse either to pin 7 (Relay-1) or to pin 14 (Relay-2). Parameter

Description

Mismatch or No Read

Sends a pulse when the label’s data does not match that of the master label or the label is not decoded before the end of the read cycle.

Match (for good read)

Sends a pulse when the decoded label matches the master label. (To send the pulse on a good read, disable Match Code.)

Mismatch

Sends a pulse when the label’s data does not match that of the master label.

No Read

Sends a pulse when the label’s data is not decoded before the end of the read cycle.

Note: If Output On is set to Mismatch or No Read, Match, or Mismatch, a relay pulse will not output unless Match Code is enabled and a master label is downloaded into memory. Note: To send a pulse on a Good Read, enable Match and disable Match Code. • Polarity. Allows you to choose between positive and negative output signals for the relay output pin that is enabled. • Pulse Width. Allows you to set the duration of the good match/no read output signals at the relay output pin that is enabled. Note: After completing changes to Output On, Polarity, and Pulse Width, press [M] to advance to Bar Code Output and continue scrolling through the Scanner Output options. • Bar Code Output. Allows you to choose the conditions that will send label data (or no read messages) to the host. Parameter

Description

Good Read

The reader will output on any good read independent of how Match Code is set.

Disabled

The reader will not output label data or no read messages to the serial port.

Match (with Match Code enabled)

The reader will output when the label data information matches the master label. However, if Match Code is disabled it will output on any good read.

Mismatch (with Match Code enabled)

The reader will output when the label data information does not match the master label. However, if Match Code is disabled it will output on any good read.

Note: If Bar Code Output is set to Match or Mismatch, label data will not output unless Match Code is enabled and a master label is downloaded into memory. • When to Output. Allows you to choose when bar code data is sent to the host. Parameter

Description

As soon as Possible

Causes bar code data (good reads) to be transmitted immediately upon a good decode.

End of Read Cycle

Causes bar code data output to be delayed until the end of the read cycle.

Publication 2755-6.9

Page 67

5–22

Configuring Your Reader

• No Read Message. Allows you to define any combination of

•

•

• • •

ASCII characters (except NUL) up to seven characters as the no read message. When enabled, the no read message will be transmitted to the host at a timeout or the end of a read cycle if the bar code label has not been decoded. No Read Output. Allows you to enable or disable the no read message. Note: If No Read Output is enabled, the no read message will only output if Bar Code Output is also enabled and MS-sensor Status is disabled. Beeper Status. A beep is emitted either after each good read of a bar code label or after each no read. Note: The beep period will be short for triggered modes where a new trigger occurs immediately or the output is delayed to the end of the read cycle on edge and serial triggers. Beeper Volume Full Screens. Allows you to display either the full menu screen or just the command line. When Full Screens is disabled, only the command line will be displayed. Laser On/Off. When enabled, the laser is ON only during the read cycle. When disabled, the laser operates continuously. Note: A serial or external trigger must be enabled for Laser On/Off to take effect. Note: Laser On/Off does not relate to the <H> (Enable Laser Scanning) or <I> (Disable Laser Scanning) operational commands.

Partial Output

• Status. When enabled, allows you to transmit part of the label to the host. • Start Position. Allows you to define the starting character of label information that is sent to the host. • Length. Allows you to define the number of characters of a label that are sent to the host.

Publication 2755-6.9

Page 68

Configuring Your Reader

5–23

Scanner Setup Menu The Scanner Setup menu, shown below, allows you to set specific bar code scanning parameters that affect decode rate. Default settings are in bold type face. Note: Unlike most configuration settings, Scanner Type, Scans per Second, and Gain Adjustment are not saved for power-on (but are initialized) when you press [Y]. To save new settings to NOVRAM for these parameters, press [<ZP>]. Scanner Setup Scanner Type – Standard – High Density

➀

Scans per Second➀ Gain Adjustment

AGC Sampling

– 50

– 45 (nominal)

– Continuous

– User Definable

– User Definable

– Disabled

(30 to 55)

(10 to 255)

– Leading Edge

Multiply the number entered on the command line by 10 for actual scans per second.

• Scanner Type. The Scanner Type “default” from the factory indicates the density type of the reader (with the unit’s optics adjusted accordingly). Note: Entering the <Zp> command will save the current setting for Scanner Type to NOVRAM. If you need to verify the density type of a unit, see the FIS options. • Scans per Second. Allows you to set the number of scans per second by controlling mirror motor speed. The range is 300 to 550 scans per second. • Gain Adjustment. Allows you to specify a gain value for the analog circuitry. Changes to Gain Adjustment should typically be done by qualified technicians. Note: Gain Adjustment is optimized at the factory before shipment; your default value may not be 45. Note: Before saving any changes to Gain Adjustment, first record the optimized factory setting for future reference. • AGC Sampling. Allows you to specify how automatic gain control sampling will be done. Continuous mode continually samples 14 transitions and stores the highest value of the samples and adjusts the AGC value at the end of the scan. Leading Edge mode finds the leading edge by looking for a 40 ms quiet zone followed by 14 transitions and stores the highest value of the samples and adjusts the AGC at the end of the scan. Leading Edge is especially effective when labels are skewed. Changes to AGC Sampling should typically be done by qualified technicians.

Publication 2755-6.9

Page 69

5–24

Configuring Your Reader

Serial Configuration

Most of the configuration changes to the reader that can be made in the menu can also be accomplished by command strings from the host. Serial command strings are entered from an ASCII device. As with menu configuration commands, serial configuration commands relate to the initial reader setup.

Serial Configuration Command Format The format for a serial configuration command is: <Kparameterdata,data,...etc.><initializing command> Keep the following in mind when using serial configuration commands. • Less than < and greater than > symbols are included as part of the commands. • “parameter,” as used here, are those character(s) that precede the data. • The “initializing command” <A> or <Z> is sent after configuration is complete. <Z> resets and saves for power up. <A> initializes the change to RAM. • Parameters and data are “case sensitive.” That is, characters must be entered as upper or lower case, as specified. • All data fields (except the last) must be followed by a comma (without a space). • If there is no change in a given field, then commas can be entered alone, or with the existing data (for example, <Ka,,,0> or <Ka4,1,0,0>). • All fields preceding the modified field must be included. For example, in Host Port, to change Data Bits to Eight without changing any other field, press either: [<Ka,,,1>] or [<Ka4,1,0,1>]. • All fields following the modified field can be left out. For example, in the RS-232 port, to change Baud Rate to 4800, press [<Ka3>]. To ensure that a serial configuration command will take affect, follow it with one of the operational commands below. • <A> To reset but not save changes for power-on • <Z> To reset and save changes for power-on For example, to change Baud Rate and reset without saving changes for power-up, press [<Ka3><A>]. To change Baud Rate and reset, saving the changes to NOVRAM, press [<Ka3><Z>].

Publication 2755-6.9

Page 70

Configuring Your Reader

5–25

To ensure that a command was received and accepted, you can enter the Show Scanner Status command, <?>.

Concatenating Serial Commands Commands can be concatenated (added together) to a maximum of 64 characters in a single string or data block. Additional data blocks of 64 or less characters can be sent provided there is at least a 10 ms pause between blocks. For example, <Kc1><Kh1><Ko1><A> enables LRC, sets End of Read Cycle mode to New Trigger, enables Narrow Margins and resets the data buffers (without saving the changes for power-on).

Serial Command Status Request The status of serial commands can be requested by entering the command followed by a question mark. For example, press [<Ke?>] to request the Postamble status.

Losing Communications Making changes to communications parameters such as Baud Rate, Parity, Stop Bits, LRC, etc. without corresponding changes in linked device(s) can result in the loss of menu access. If this should occur, default the reader with the <Zd> Restore/Save Default Configuration for Power-on command. Note: Defaulting the reader will reset all standard configuration parameters except Scanner Type, Scans per Second, and Gain Adjustment to their original default values. Note: Power must be available to the reader during the default procedure.

Publication 2755-6.9

Page 71

5–26

Configuring Your Reader

Serial Configuration Commands The table starting below lists the serial configuration commands. Function

Communications

Command Communications Protocol Preamble Postamble LRC Response Timeout Intercharacter Delay Host Port Auxiliary Port Communications Status Request Triggering Mode End of Read Cycle Serial Trigger Character External Trigger Level Good Decode Read

Operations

Parameter Kf

<Kfprotocol,address>

Kd Ke Kc KA KB Ka

<Kdstatus,ASCII characters> <Kestatus,ASCII characters> <Kcstatus> <KAtimeout setting> <KBnumber> <Kabaud,parity,stop bits,data bits> <Kymode,baud rate,parity,stop bits,data bits>

Ky KT

<KT?>

Kg Kh

<Kgmode,filter time> <Khmode,time>

Ki

<Kicharacter>

Kj Km

<Kjmode> <Kmnumber> <Kntype,sequential matching,match start position,match length,wild card character,sequence on no read,sequence on every mismatch> <Kzstatus> <KLnumber of labels,multilabel separator>

Match Code Type

Kn

New Master Pin

Kz

Number of Labels

KL

Operations Status Request

KV

Narrow Margins

Ko

Code 39

Kp

Codabar

Kq

I 2 of 5

Kr

UPC/EAN

Ks

Code 128 Code Types Status Request

Kt

<Konarrow margin status,symbology ID status> <Kpstatus,check digit status,check digit output status,large intercharacter gap,fixed code length status,code length> <Kqstatus,start & stop match status,start & stop output status,large intercharacter gap,fixed code length status,code length,check digit type,check digit output> <Krstatus,check digit,check digit output,length 1,length 2> <Ksstatus,EAN status,supplementals status,separator status,separator cha.> <Ktstatus,fixed length,length>

KW

<KW?>

Code Types

Table continued on the next page.

Publication 2755-6.9

Format

<KV?>

Page 72

Configuring Your Reader

Function

Scanner Output

Command Kv Kw Kl Kk Ku KC

Serial Verification

KS

Scanner Output Status Request Partial Output Scanner Type Scans per Second Auto Gain Control

Scanner Setup

Parameter

Relay 1 Relay 2 Bar Code Output No Read Message Beeper Laser On/Off

Bad Bar Code Message No Bar Code Message No Object Bar Code Message Scanner Setup Status Request

Format <Kvoutput on,polarity,pulse width> <Kwoutput on,polarity,pulse width> <Klstatus,when to output> <Kkstatus,output> <Kustatus,volume> <KCstatus> <KSserial command status,serial command beep status,control/hex output>

KX

<KX?>

KY KP KE

<KYstatus,start position,length> <KPdensity> <KEspeed> <KDgain adjustment,AGC sampling,tracking>

KD

5–27

KM

<KMstatus,message>

KN

<KNstatus,message>

KO

<KOstatus,message>

KU

<KU?>

The sections that follow describe the commands listed in the table starting on the previous page. The defaults listed in the tables are in bold type.

Publication 2755-6.9

Page 73

5–28

Configuring Your Reader

Communications Commands

• Protocol. If selecting one of the options from 0 to 4 (Point-to-Point, Point-to-Point with RTS/CTS, Point-to-Point with XON/XOFF, Point-to-Point with RTS/CTS and XON/XOFF, or Polling Mode D), use the format below. Command

Parameter

Protocol 0 = Point-to-Point 1 = Point-to-Point with RTS/CTS 2 = Point-to-Point with XON/XOFF 3 = Point-to-Point with RTS/CTS and XON/XOFF 4 = Polling Mode D

Kf

Format

<Kfprotocol>

Example

To change the Protocol to Polling Mode D, press [<Kf4>].

If selecting Multidrop (5), you must define an address and append it to the command string. The address can be from 1 to 50. Command

Parameter

Format

Protocol Kf

<Kfprotocol,address>

5 = Multidrop

Example To change the Protocol to Multidrop with an address of 33, press [<Kf5,33>].

If selecting User Defined (6) or User Defined Multidrop (7), complete the format by either choosing new parameters or concatenating unchanged data fields (separate by commas). For User Defined, first select Point-to-Point <Kf0> and then User Defined <Kf6...>. For user Defined Multidrop, first select Multidrop <Kf5>, then User Defined Multidrop <Kf7...>. Command

Parameter

Format

Example

<Kfprotocol,RES,address, REQ,EOT,STX,ETX,ACK, NAK>

To select an unpolled ACK/NAK User Defined protocol with LRC disabled, press [<Kf0><Kf6,,,,,,, ^F,^U><Kc0>]➀. ACK and NAK will be displayed in the menu➁.

Protocol 6 = User Defined

Kf

7= User Defined Multidrop ➀

<Kf0> nulls the address and <Kc0> disables LRC.

➁

A control character, represented here as two characters (^F or ^U, etc.), is actually a single ASCII character that is entered on the keyboard by holding down the control key while pressing the desired letter.

• Preamble. You can enter one or two preamble characters except a null (00H). Command Status 0 = Disabled 1 = Enabled

Publication 2755-6.9

Parameter Kd

Format <Kdstatus,preamble character(s)>

Example To enable Preamble with just one character, an FF (form feed), press [<Kd1,^L>].

Page 74

Configuring Your Reader

5–29

• Postamble. You can enter one or two postamble characters except a null (00H). Command Status 0 = Disabled 1 = Enabled

Parameter Ke

Format <Kestatus,postamble character(s)>

Example To disable Postamble, press [<Ke0>].

• LRC Command Status 0 = Disabled 1 = Enabled

Parameter Kc

Format <Kcstatus>

Example To enable LRC, press [<Kc1>].

• Response Timeout. You can use any number from zero to 65,000. (A zero causes an indefinite wait.) The default is 12 ms. Parameter KA

Format <KAtimeout setting>

Example To change Response Timeout to 30 ms, press [<KA30>].

• Intercharacter Delay. You can use any number from zero to 255. The default is zero. Parameter KB

Format <KAtime interval>

Example To change Intercharacter Delay to 30 ms, press [<KB30>].

Publication 2755-6.9

Page 75

5–30

Configuring Your Reader

• Host Port. Changes made in the reader’s communications parameters such as baud rate, parity, stop bits, LRC, etc., must be matched in the other device(s) or communications will be lost. If this occurs, default the reader with the <Zd> Restore/Save Default Configuration for Power-on command. Command Baud Rate 0 = 600 1 = 1200 2 = 2400 3 = 4800 4 = 9600 5 = 19200 6 = 38400 7 = 76800 8 = 300 Parity 0 = None 1 = Even 2 = Odd Stop Bits 0 = One 1 = Two Data Bits 0 = Seven 1 = Eight

Publication 2755-6.9

Parameter

Ka

Format

Example

<Kabaud rate,parity,stop bits,data bits>

To change Host Port Baud Rate to 2400, press [<Ka2>].