For the Allen-Bradley 2755-LS7

Page 94

Hardware Operation

Operating Scanner System Hardware

6–9

The following sections describe how to operate your scanner system hardware.

Operating the Reader The reader turns on as soon as power is applied to it. The reader reads bar codes after the settings are configured through the menu commands or through the serial commands. At the Main menu, press [Esc]. This will give you a blank screen. When a bar code is read by the reader, the data will be visible on the terminal screen. To make changes to the reader’s parameters while the reader is reading bar codes, type the appropriate operational command. You do not need to access the Main menu or access the serial commands to make changes. Daisy-Chain Operation The daisy-chain configuration option allows you to read different bar codes on different sides of the same package. The various readers act as a single device, as far as the host device is concerned, and can be connected to a single serial port. You can only use Series B or higher of the reader when using the daisy-chain configuration except for the last reader used in the chain. Refer to the drawing below for daisy-chain connections.

Host Reader (Master)

Interface Box

Scanner Port Reader (Slave)

Pin 2 3 7 4 5

RS-232 Port

Interface Box

Scanner Port Reader (Slave)

Pin 2 3 7 4 5

RS-232 Port

Interface Box

Scanner Port

Pin 2 3 7

RS-232 Port

Publication 2755-6.9

Page 95

6–10

Hardware Operation

The reader will check the auxiliary port parameter for data when the reader is about to send a no read message after exiting a read cycle. The reader will wait up to 20 ms for the first character from the next reader down the line. If there is no data within 20 ms, the reader will send a no read message. If there is a character, the reader will wait for a terminating CR up to 20 ms after every auxiliary character received and sends the message up the line to the next reader (or to the host if it is the master scanner). If no CR is received in time, the reader will send a no read message up to the line to the next reader (or to the host if it is the master reader). If you are using more than one label, field separators are necessary to separate each label and are used by the master reader to count the number of labels received by the auxiliary port parameter. The master reader must receive and read at least the number of bar codes set in Number of Labels. If the reader reads less, the reader will interpret the auxiliary data it receives as the missing labels and will add a no read message to the data for each missing label. The reader connected to the auxiliary port must have the following settings. • Postamble = CR (^M). • Postamble is enabled. • Multilabel separator and serial trigger character must match the master setting. Auxiliary Port Operation Auxiliary Port Parameters allow you to set communications parameters between daisy-chained readers or between the reader and an auxiliary monitor. An auxiliary monitor can be used to configure the menus, send data to the host, and display data transmissions originating from the host or reader. The auxiliary port cannot be used in conjunction with RS-485 or RTS/CTS on the host port. Note: The Aux Port baud rate should never exceed Host Port baud rate or auxiliary port data could be lost.

Publication 2755-6.9

Page 96

Hardware Operation

6–11

You can only use Series B or higher of the reader when using an auxiliary monitor. Refer to the drawing below for auxiliary port connections. Host

TXD RXD GND 2

Reader

3

7

Interface Box

Scanner Port

TXD 2 RXD 3 AUX TXD 4 AUX RXD 5 GND 7

RS-232 Port

Auxiliary Monitor TXD 2 RXD 3 GND 7

The monitor can be configured to operate in one of three modes. The modes are: • transparent • non–buffered full-duplex • non-buffered half-duplex Transparent mode can work with all protocols. Full-duplex and half-duplex modes can work with all protocols except polled protocols.

Publication 2755-6.9

Page 97

6–12

Hardware Operation

Transparent mode is used to batch data from the auxiliary monitor to the host. The decoder buffers data from the auxiliary monitor and displays the keyed data on the auxiliary monitor. The decoder transmits auxiliary monitor data to the host when a label is scanned or a carriage return is entered from the auxiliary monitor.

Publication 2755-6.9

When

Then

Data is initiated from the monitor

•monitor data is passed through to the host whenever a return key is pressed at the monitor or whenever bar code data is sent. If monitor data is sent with bar code data, monitor data is processed first-in/first-out basis. •monitor data to the host is always sent with a preamble and a postamble. •monitor data will still pass through if the decoder is in a polled mode to the host. •a <D> command is the only command accepted by the decoder from the monitor. All other commands will pass through to the host.

Data is initiated from the reader

•transmission to the monitor occurs immediately upon a good read. •scan data to the monitor does not include a preamble or a postamble. •transmission to the host conforms to all the parameters specified in the configuration menu. •communications with the monitor is always point-to-point protocol even if the host is in a polled protocol mode.

Data is initiated from the host

•in a polled mode, data echoed from the host to the monitor must be in the format <B_>. •in unpolled mode, all host data is echoed to the monitor.

Page 98

Hardware Operation

6–13

Full-duplex allows the auxiliary monitor data and bar code data to be sent directly to the host. The bar code data is not displayed on the auxiliary monitor screen. When

Then

Data is initiated from the monitor

•monitor data is passed directly through the host whenever it is received by the reader, unless the reader is in a polled mode, in which case the data will be ignored. •monitor data is not echoed. •monitor data to the host will not have a preamble or a postamble. •a <D> command is the only command accepted by the decoder from the monitor. All other commands will pass through to the host.

Data is initiated from the reader

•scan data is not sent to the monitor.

Data is initiated from the host

•in a polled mode, data echoed from the host to the monitor must be in the format <B_>. •in unpolled mode, all host data is echoed to the monitor.

Half-duplex operates exactly like Full-duplex except that the bar code data is displayed on the auxiliary monitor screen at the same time the data is sent to the host. When

Then

Data is initiated from the monitor

•monitor data to the host is ignored if the reader is in a polled mode. •monitor data or scanned data is sent to the host whenever it is received. •monitor data is not echoed. •monitor data to the host will not have a preamble or a postamble. •a <D> command is the only command accepted by the decoder from the monitor. All other commands will pass through to the host.

Data is initiated from the reader

•scan data is transmitted to the monitor at the same time it is transmitted to the host. •transmission to the host conforms to all the parameters specified in the configuration menu.

Data is initiated from the host

•in a polled mode, data echoed from the host to the monitor must be in the format <B_>. •in unpolled mode, all host data is echoed to the monitor.

Publication 2755-6.9

Page 99

6–14

Hardware Operation

Defaulting the Reader Defaulting the reader resets all reader configuration parameters except Gain Adjustment to their original default values. The value for Gain Adjustment is saved to NOVRAM for power-on by pressing [<Zp>] (Save SPS/Gain for Power-on). Note: The reader can also be defaulted using various methods with the interface box, if used. Refer to page 6–15 for more information regarding faulting the reader via the interface box. Defaulting is necessary if: • You wish to quickly restore default settings to the configuration program after making some temporary changes. • Communications between the reader and another device are interrupted because of incompatible settings (for example, a terminal is set to communicate at 9600 baud, but the reader is configured at 38.4K baud). • The reader has been assigned a polling address and you wish to access the reader’s menu. Note: Power must be available to the reader during all default procedures. Software Default The software default is done by pressing [<Zd>] (Restore/Save Default Configuration for Power-on).

Operating the Interface Box There are two interface boxes available for your application. The units have: • RS-232 and RS-485 communication (Catalog No. 2755-LS7-IB1) • RS-232 and RS-422 communication (Catalog No. 2755-LS7-IB2) RS-232 and RS-485 Communication (Catalog No. 2755-LS7-IB1) When the Mode switch is in the out position, the RS-232 signals go through to the 25-pin (host) connector.

Reader

Publication 2755-6.9

RS-232

IB1

RS-232

Host

Page 100

Hardware Operation

6–15

When the Mode switch is in the in position, the interface box takes RS-232 signals (TXD, pin 2, RXD, pin 3) and converts them to RS-485 levels. The RS-485 levels are present at both the RS-485/422 (LAN) connector and the 25-pin (host) connector.

Reader

RS-232

RS-485

Host

RS-485

LAN

IB1

Note: In this mode the reader must be set up for Multidrop communications. Note: The second RS-232 TXD pin (pin 4 of the host connector) is not available in this mode. RS-232 and RS-422 Communication (Catalog No. 2755-LS7-IB2) In this configuration the Mode switch must be in the in position for proper operation. The second serial port (aux) is present on pins 2 and 3 of the 25-pin

(host) connector. This allows a standard RS-232 cable to connect to the second serial port.

Reader

RS-232

RS-232

Aux

RS-422

LAN

IB2

Defaulting the Interface Boxes Access to the configuration menus of a reader that is in a polled mode can be forced (without defaulting) by pressing [<D>] from an auxiliary terminal via the auxiliary RS-232 port. Using the Default Switch on the Interface Box to Default the Reader To default the reader with the default switch, insert 16 to 26 gauge wire (paper clip) into the small hole to the left of the Power switch. Listen for a series of short beeps. While the beeping is occurring, insert the wire into the hole again within 3 seconds. A longer beep should be heard. If not, repeat the process.

Publication 2755-6.9

Page 101

6–16

Hardware Operation

Shorting Pins 7 and 11 You may also default the reader by shorting pins 7 and 11 of the 25-pin (host) connector together on the interface box. To short the interface box:

!

ATTENTION: Be certain that the correct pins are shorted. Shorting the wrong pins can cause serious damage to the unit.

1. Turn power to the reader and interface box ON. 2. Locate pins 7 and 11 on the interface box’s host connector and mark with a pen. 11

7

3. Short pins 7 and 11 momentarily by inserting mating connector or wire. (The length of light wire should be approximately 4 inches, 18 to 26 gauge). 4. Listen for a series of short beeps. While the beeping is occurring, insert the wire into the hole again within 3 seconds. A longer beep should be heard. If not, repeat the process. 11

7

Operating the Power Supply To operate the power supply, make sure the power supply is connected to the interface box and to the power receptacle supplying 100-240V ac. Refer to chapter 4 for more information regarding installing the power supply.

Operating the Host Device To operate the host device, refer to documentation specific to that product’s operation.

Publication 2755-6.9