For the Accu-Sort 2755-SN3, Accu-Sort 2755-SN5, Allen-Bradley 2755-SN5, Accu-Sort 2755-SN8 and Allen-Bradley 2755-SN8

Page 193

Communicating with an SLC 5/03 Processor on a DeviceNet Network using Explicit Messaging

10–31

Explicit Messaging Ladder Logic Program Note: The following ladder logic program is for reference only. Application specific interlocks may be necessary. Enable Rung B3 to initiate the writing of an APM command to the AdaptaScan. The APM command that resides in N20:0. The DeviceNet address being written to, in this example is, 10 or 0AH.

]

B3

COP

[

0

Copy File Source

#N20:0

Destination

#M0:1.224

Length

32

If bit 15 is enabled, read the response data from the above command into file N25:0.

]

COP

I:1

[ 15

Source

#M1:1.224

Destination Length

#N25:0 32

Example Data Tables Refer to p. 10–27 for information regarding each byte. Address

Data = Hex Code (matchcode download of 0300 data)

N20:0

0101

000C

100A

00CE

0001

0003

Address

Response File (good response)

N25:0

0101

Address

Data = Hex Code (turn on LED1)

N20:0

0101

0008

100A

0004

3330

3030

0002

0003

0001

900C

00C9

Note: You need to send a reset command for every explicit command that is executed in order to receive a good response.

Publication 2755-6.8

Page 194

10–32

Communicating with an SLC 5/03 Processor on a DeviceNet Network using Explicit Messaging

Notes on using Explicit Messaging • You can send messages sequentially from the SLC 5/03 to different bar code readers, but the response will not update properly (when the response is read in N25:0). • The TXID byte does not need to be incremented, although you may not know where the response came from. • To receive the correct response from the command sent from the SLC 5/03 you must: 1. Send command down, matchcode download (TXID=11). 2. Send a 03 in the status command. Refer to page 10–26 for more information. 3. Increment TXID to 12. 4. Send command down, turn on LED 1 (TXID=12). 5. View N25:0 for response to step 4. 6. Confirm that TXID=12. If your response is 90, the command was sent correctly. If you receive a 94, the was not sent correctly. • If an incorrectly formatted command is sent from the SLC 5/03, you must send a 03 in the status command byte in order for the system to operate properly. • When sending a 03 in the status command byte, the SDN card will produce an error until the next command is sent.

Publication 2755-6.8

Page 195

Communicating with an SLC 5/03 Processor on a DeviceNet Network using Explicit Messaging

Troubleshooting the Module and Network

10–33

The bicolor (green/red) module status indicator (MODULE) displays module status. It indicates whether the module has power and is functioning properly. If the Module LED is Off this indicates

Take this action Apply power.

Flashing green there is no power applied to the module. the module is operating in normal condition. the module is not configured.

Flashing red there is invalid configuration.

Check configuration setup.

Solid red the module has an unrecoverable fault.

Replace the module.

Solid green

None Configure the module.

The DeviceNet channel has a bicolor (green/red) network status indicator (NET). The next table provides troubleshooting information about the DeviceNet channel communication link. this indicates

Take this action

Off

If the NET indicator is the channel is disabled for DeviceNet communication.

Power-up the module, provide network power to channel, and be sure channel is enabled in both the module configuration table and module command word.

Flashing green Solid green the channel is enabled but no communication is occurring. all slave devices in the scan list table are communicating normally with the module.

Configure scan list table for channel to add devices. None.

Solid red the module may be defective.

Flashing red at least one of the slave devices in the module’s scan list table has failed to communicate with the module.

Reset module. If failures continue, replace module. Examine the failed device and the scan list table for accuracy.

Publication 2755-6.8

Page 196

10–34

Communicating with an SLC 5/03 Processor on a DeviceNet Network using Explicit Messaging

Your module uses numeric displays to indicate diagnostic information about the status of your module. The display flashes at 1 second intervals. The following table summarizes the meanings of the numeric codes. Numeric Code

Indicates

Network Address Displays 0 - 63 normal operation. The numeric display matches the scanner’s node address on the DeviceNet network.

None.

70 module failed Duplicate Node Address check.

Change the module channel address to another available one. The node address you selected is already in use on that channel.

71 illegal data in scan list table (node number alternately flashes). slave device stopped communicating (node number alternately flashes). device key parameters do not match scan list table entry (node number alternately flashes).

Reconfigure the scan list table and remove any illegal data. Inspect the field devices and verify connections.

72 73

Enter a matching scan list device ID. Make sure that the device at the flashing node address matches the desired key parameters (vendor, product code, product type). Modify your configuration and check for invalid data. Verify connections.

74 data overrun on port detected.

75 no network traffic has been detected.

76 no direct network traffic for module detected.

77

79 data size returned does not match scan lists entry (node number alternately flashes). slave device in scan list table does not exist (node number alternately flashes). module has failed to transmit a message.

None. The module hears other network communication. Reconfigure your module and change the addressing. Add the device to the network, or delete the scan list entry for that device. Make sure that your module is connected to a valid network. Check for disconnected cables. Verify baud rate.

80 module is in IDLE mode.

None.

81 module is in FAULT mode.

None.

82 error detected in sequence of fragmented I/O Check scan list table entry for slave device to messages from device (node number alternately make sure that input and output data lengths flashes). are correct. Check slave device configuration.

83 slave device is returning error responses when module attempts to communicate with it (node number alternately flashes).

Check accuracy of scan list table entry. Check slave device configuration.

84 module is initializing the DeviceNet channel.

None. This code clears itself once module attempts to initialize all slave devices on the channel.

85 data size returned is bigger than expected.

86 device is producing idle state data while the scanner is in Run Mode. available for allocation. Scanner has not yet been detected by allocated master, or slave mode is enabled but scanner is not allocated to a master. this is not an error. At power-up and reset, the module displays all 14 segments of the node address and status display LEDs.

Check accuracy of scan list table entry. Check slave device configuration. Check device configuration/slave node status.

78

87

88

Table continued on the next page.

Publication 2755-6.8

Take this action

Monitor scanner to determine if error code clears when master detects scanner. If error remains, check scanner slave mode configuration. None.

Page 197

Communicating with an SLC 5/03 Processor on a DeviceNet Network using Explicit Messaging

Numeric Code

Indicates

10–35

Take this action

90 user has disabled communication port reconfigure your module. Check the disable bit in the Module Command Register. Check DeviceNet connections and physical media integrity. Check system for failed slave devices or other possible sources of network interference. Provide network power. Make sure that module drop cable is providing network power to module comm port.

91 bus-off condition detected on comm port. module is detecting communication errors.

92 no network power detected on comm port.

95 application FLASH update in progress.

None. Do not disconnect the module while application FLASH is in progress. You will lose any existing data in the module’s memory.

97 module halted by user command.

None.

98

Unrecoverable firmware failure.

Service or replace your module.

99

Unrecoverable hardware failure.

Service or replace your module.

Publication 2755-6.8

Page 198

10–36

Communicating with an SLC 5/03 Processor on a DeviceNet Network using Explicit Messaging

Downloading Other Host Commands

You can download other host commands using the same procedures described in the match code example. The following tables provide the commands and responses for the other host commands (all values are hexadecimal).

Read Performance Indicator Command

Read Performance Indicator Response

Packet Contents

Data Sent

Packet Contents

DeviceNet Address

3F*

DeviceNet Address

Response 3F

Get Performance Request

4C

Get Performance Response

CC

Class

C8

Data (LSB)

01

Instance Number (LSB)

01

Data (MSB)

00

Instance Number (MSB)

00

*3F = Address 63, modify as required

Reset Package Counter Command

Reset Package Counter Response

Packet Contents

Data Sent

Packet Contents

Response

DeviceNet Address

3F*

DeviceNet Address

3F

Set Attribute Request

10

Set Attribute Response

90

Class

D2

Instance Number (LSB)

00

Instance Number (MSB)

00

Attribute Number– Reset Counters Data

09 01

*3F = Address 63, modify as required

Read Match Counters Command

Read Match Counters Response

Packet Contents

Data Sent

Packet Contents

Response

DeviceNet Address

3F*

DeviceNet Address

3F

Get Attribute Request

0E

Get Attribute Response

8E

Class

CE

Data

6C, 08, 00, 00

Instance Number (LSB)

01

Instance Number (MSB)

00

Attribute Number

08

*3F = Address 63, modify as required

Read Package Counters Command

Read Package Counters Response

Packet Contents

Data Sent

Packet Contents

Response

DeviceNet Address

3F*

DeviceNet Address

3F

Get Attribute Request

0E

Get Attribute Response

8E

Data

6C, 08, 00, 00

Class

D2

Instance Number (LSB)

01

Instance Number (MSB)

00

Attribute Number– Match Count *3F = Address 63, modify as required

Publication 2755-6.8

08

Page 199

Communicating with an SLC 5/03 Processor on a DeviceNet Network using Explicit Messaging

Reset Match Counters Command Packet Contents

Data Sent

Reset Match Counters Response Packet Contents

Response

Response Codes

3F*

DeviceNet Address

3F

Set Attribute Request

10

Set Attribute Response

90

Class

CE

Instance Number (LSB)

00

Instance Number (MSB)

00

Attribute NumberReset Counters Data

0B

10–37

01

*3F = Address 63, modify as required

Read Message Command Packet Contents

Data Sent

Read Message Response Packet Contents

Response

DeviceNet Address

3F*

DeviceNet Address

3F

Get Attribute Request

0E

Get Attribute Response

8E

Class

CC

Data (LSB)

04

Instance Number (LSB)

00

Data (MSB)

00

Instance Number (MSB)

00

ASCII Message Data

30*

Attribute Number - Message

14

ASCII Message Data

32

ASCII Message Data

30

ASCII Message Data

30

*3F = Address 63, modify as required

* Example data = 0200

Read LED Status Command

Read LED Status Response

Packet Contents

Data Sent

Packet Contents

DeviceNet Address

3F*

3F

Response 3F

Read LEDS Request

43

Read LEDS Response

C3

Class

CB

I/O 1

See Table Next Page

Instance Number (LSB)

01

I/O 2

See Table Next Page

Instance Number (MSB)

00

Trigger / Read

See Table Next Page

On Symbol

See Table Next Page

Laser On

See Table Next Page

Module

See Table Next Page

Network

See Table Next Page

*3F = Address 63, modify as required

Publication 2755-6.8

Page 200

10–38

Communicating with an SLC 5/03 Processor on a DeviceNet Network using Explicit Messaging

Set Output Timer Command Packet Contents

Data Sent

Set Output Timer Response Packet Contents

Response

DeviceNet Address

3F*

DeviceNet Address

3F

Set Attribute Request

10

Set Attribute Response

90

Class

D0

Instance Number (LSB)

02

Instance Number (MSB)

00

Attribute Number - Max Time

09

Data (LSB)

FA

Data (MSB)

00

*3F = Address 63, modify as required ** Time in milliseconds

LED Status Response Data at Indicated Bit Address = LED State Byte 0

0 = Off

1 = Yellow

I/O 1

OFF

ON

3-5

I/O 2

OFF

ON

0-2

TRIGGER / READ

No Trigger

Triggered

3-5

ON SYMBOL

Not Reading

Reading

0-2

LASER ON

OFF

ON

3-5

MODULE

No Power

0-2

NETWORK

Bits

LED Indicator

0-2

1

2

3 3-5

Publication 2755-6.8

6 = Flash Green

7 = Flash Red

Hardware Fault

Power Up

Minor Fault

DeviceNet DeviceNet OK Fault

Established

No Response

2 = Green

3 = Red

4 = Not Used

5 = Flash Yellow

Valid Read Read <100%

Device OK