For the Allen-Bradley 2755-DD and Allen-Bradley 2755-DS
Page 56
Installing the Decoder
4–17
Figure 4.9 Connecting device to HOST port of NEMA Type 1 decoder
Supported Host Devices SCANNER A SCANNER B
AUX RS-232
HOST RS-232 /422 /485
Allen-Bradley PLC Controller via: - Cat. No. 1771-DB BASIC Module - Cat. No. 1771-DA ASCII I/O Module - Cat. No. 2760-RB Flexible Interface Module with Cat. No. 2760-SFC1/SFC2 Protocol Cartridge
①
Any RS-232 or RS-422 ASCII Device ① Construct your own cable using pinouts in Appendix E.
Pin
Abbreviation
1
GND
Chassis Ground
Function
2
TD
RS-232 Transmit Data (from decoder to host).
3
RD
RS-232 Receive Data (from host).
4
RTS
RS-232 Request to Send
5
CTS
RS-232 Clear to Send
6
DSR
RS-232 Data Set Ready
7
SIG GND
RS-232 Signal Common
9
SHLD
RS-485 Shield Ground
12
485 TERM
RS-485 Line Termination. Jumpers to 13.
13
485 A/TERM
RS-485 Line Termination. Jumpers to 12.
14
TxB+
RS-422(B) or RS-485(B) Transmit Data (from decoder to host).
15
TxA-
RS-422(A) or RS-485(A) Transmit Data (from decoder to host).
16
RxA ’-
RS-422 Receive Data (from host).
17
RxB ’+
RS-422 Receive Data (from host).
18
422 A/TERM
RS-422 Line Termination. Jumpers to 19.
19
422 TERM
RS-422 Line Termination. Jumpers to 18.
20
DTR
RS-232 Data Terminal Ready
The HOST port on the NEMA Type 4 decoder has a 19-pin (male) connector and communicates over an RS-232, RS-422, or RS-485 communication line. Figure 4.10 shows host devices you can connect to the HOST port of the NEMA Type 4 decoder.
Publication 2755-833
Page 57
4–18
Installing the Decoder
Figure 4.10 Connecting device to HOST port of NEMA Type 4 decoder
Supported Host Devices Allen-Bradley PLC Controller via: - Cat. No. 1771-DB BASIC Module - Cat. No. 1771-DA ASCII I/O Module - Cat. No. 2760-RB Flexible Interface Module with Cat. No. 2760-SFC1/SFC2 Protocol Cartridge
①
SCANNER A SCANNER B
AUX RS-232
HOST RS-232 /422 /485
Any RS-232 or RS-422 ASCII Device ① Use the Cat. No. 2755-CT1 communication cable or construct your own cable using the Cat. No. 2755-NC17 Connector Kit and the pinouts in Appendix E. Use 2755-CY1 for multidrop applications.
HOST Port (male) Connector
M M L K J H
NN
P
UU TT G
AA
VV SS FF
R EE
B C D
Pin
Abbreviation
A
GND
Chassis Ground
Function
B
RD
RS-232 Receive Data (from host).
C
TD
RS-232 Transmit Data (from decoder to host).
D
SIG GND
RS-232 Signal Common
E
DTR
RS-232 Data Terminal Ready
F
RTS
RS-232 Request to Send
H
DSR
RS-232 Data Set Ready
J
CTS
RS-232 Clear to Send
L
SHLD
RS-485 Shield Ground
M
485 TERM
RS-485 Line Termination. Jumpers to N.
N
485 A/TERM
RS-485 Line Termination. Jumpers to M.
P
TxB+
RS-422 Transmit Data (from decoder to host).
R
TxA-
RS-422 Transmit Data (from decoder to host).
S
RxA ’-
RS-422 Receive Data (from host).
T
RxB ’+
RS-422 Receive Data (from host).
U
422 A/TERM
RS-422 Line Termination. Jumpers to V.
V
422 TERM
RS-422 Line Termination. Jumpers to U.
See Appendix E for specific details on connecting to a host device using the different communication interfaces.
Publication 2755-833
Page 58
Installing the Decoder
Installing I/O Modules
4–19
This section shows how to install input and output modules on the optional I/O Module Board. The board has eight positions (MOD1-MOD8) for I/O modules. All eight positions accept output modules. The MOD8 position alternately accepts an input module for the match code AutoLoad function. The Accessories section in Chapter 2 provides a complete list of modules supported by the I/O board. Figure 4.11 shows two output modules installed in the MOD1 and MOD2 positions and one input module in the MOD8 position. A screw holds each module into position on the I/O board. Figure 4.11 I/O module board (with optional I/O modules installed MOD8 accepts input or output module
I/O Board I/O Modules MOD1 MOD2 MOD3 MOD4 MOD5 MOD6
Hold Down Screws
MOD7 MOD8
12V DC Power Source (100 mA Max) for Autoload Input Only – 1+
– 2+
– 3+
– 4+
– 5+
– 6+
– 7+
– 8+
Module Connectors (8) Fuses (F1 - F8) F 1
F 2
F 3
F 4
F 5
F 6
F 7
F 8
–+
12 V DC
To install a module on the I/O board: 1. Verify that power is disconnected from decoder and module connectors. 2. Loosen the two screws which secure the cover of the decoder and open. 3. Carefully align module pins over sockets in board. Plug module into MOD position on I/O board. 4. Note: The module pins must puncture the silicon seal of the I/O board sockets. 5. Tighten the hold-down screw to secure module in position. To remove a module, verify that the power is off, loosen the hold-down screw, and pull out module.
Publication 2755-833
Page 59
4–20
Installing the Decoder
Connecting I/O Modules to External Devices
The bottom of the decoder has two holes for I/O module field wiring. The 7/8 inch holes accept standard 1/2 inch conduit fittings or NEMA 4 Conduit Hubs, or the 2755-NB0 NEMA 4 Connector Kit. The NEMA 4 connector can be used with either NEMA 1 or NEMA 4 decoders. Figure 4.12 shows the location of the holes in the bottom of the enclosure. Figure 4.12 Connecting I/O to external devices
I/O Module Field Wiring Holes
Switch and Power Connector Area
Connect I/O Devices using: 7/8 inch holes for 1/2 inch conduit Two Catalog No. 2755-NB0 NEMA 4 Connector Kits
Switch and Power Connector Area
See the next section for details on how to install conduit hubs in the I/O module field wiring holes. Use the 2755-NB0 Connector Kit or the 1490-N1 conduit hubs in the NEMA Type 4 decoder to maintain the environmental rating.
Wiring I/O Modules
Publication 2755-833
Figure 4.13 shows how the factory installed NEMA Type 4 Connectors are pre-wired to the I/O module locations. Below each output module is a terminal block connector which accepts up to 12 gauge wire.
Page 60
Installing the Decoder
4–21
To wire each output module: 1. Strip 1/4 inch of the insulation from wires (removing wire particles). 2. Loosen terminal screws on pull-apart connector. For easier installation, remove connector from the I/O board by gently lifting the connector. 3. Insert wires into connector. Note polarity on module connectors when using DC modules. 4. Tighten terminal screws on connector to secure the wires. 5. Replace pull-apart connector if removed from I/O board. Figure 4.13 Wiring I/O modules I/O Board
Wire modules to external equipment using conduit or the NEMA Type 4 Connector Kit and Cables.
I/O Modules
MOD1 MOD2 MOD3 MOD4
MOD5 MOD6
MOD7 MOD8
MOD8 accepts input or output module
Hold Down Screws
– 1+
– 2+
– 3+
– 4+
– 5+
– 6+
– 7+
– 8+
F 1
F 2
F 3
F 4
F 5
F 6
F 7
F 8
12V DC Power Source 100 mA Max –+ (for use with input module in position 8) 12 V DC
Module Pull-Apart Connectors (8)
Locknut
Locknut Washer
Washer
I/O Connector
I/O Connector
GREEN RED/BLACK
ORANGE BLUE
WHITE/BLACK
– 7+
– 8+
GREEN RED/BLACK
– 6+
WHITE RED
– 5+
BLACK
– 4+
WHITE RED
5+ 6–
– 3+
BLACK
Blue 1+ White/Black 2– Black 2+ White 3– Red 3+ Green 4– Red/Black 4+
– 2+
WHITE/BLACK
Pin # Wire Color Left Right 1– 5– Orange
– 1+
ORANGE BLUE
Factory Installed I/O Connector Wiring
6+ 7– 7+ 8– 8+
Publication 2755-833
Page 61
4–22
Installing the Decoder
Installing Conduit Hubs/NEMA Type 4 Decoder
Use the Bulletin 1490-N1 conduit hub with the NEMA Type 4 decoder to maintain environmentally sealed connections at conduit entrances. The NEMA Type 1 and Type 4 decoders accept Catalog Number 1490-N1 conduit hubs (for a 7/8 inch hole size and 1/2 inch conduit).
Conduit
Bulletin 1490 Conduit Connector (Hub)
”O” Ring Outside Enclosure Enclosure Hole
Conduit Holes The conduit hubs install in the two output module field wiring holes in the bottom of the enclosure. Each hole size is 7/8 inch and accepts 1/ inch conduit. 2
Locknut
Conduit Connections
!
ATTENTION: To guard against enclosure damage, align the conduit so as to prevent unnecessary stress on the enclosure walls.
You can connect conduit to the conduit connector (hub) before or after the conduit connector is secured into the prepared hole using the connector locknut. Tighten connector locknut securely to provide bonding to equipment enclosure.
!
Publication 2755-833
ATTENTION: To complete the bonding between grounding bushings and the enclosure, bonding must be provided in accordance with all applicable codes.