PLC-5 Programmable Controllers Selection Guide 1785 and 1771: Select Network Communications
Pages 21 to 32 of 60, from PLC-5 Programmable Controllers Selection Guide 1785 and 1771
The original document is the PDF (4.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
Filed in the catalog under the Allen-Bradley 1785-LT
Page 21
Select Network Communications
Step 2 - Select: • EtherNet/IP Protocol • ControlNet Network • DeviceNet Network • Serial Network • Data Highway Plus • Remote I/O
19
Select Network Communications
Use specific PLC-5 controllers with network connections and install multiple communication modules into the PLC-5 backplane to route control and information data between the different networks. The networking capabilities, led by EtherNet/IP, ControlNet, and DeviceNet networks, allow information exchange between a range of devices and computing platforms and operating systems. PLC-5 controllers come with different network connections. Choose the network that best meets your needs.
NetLinx Architecture NetLinx open network architecture is the Rockwell Automation strategy of using open networking technology for seamless, top-floor to shop-floor integration. The networks in the NetLinx architecture - DeviceNet network, ControlNet network and EtherNet/IP network - speak a common language and share a universal set of communication services. NetLinx architecture, part of the Integrated Architecture, seamlessly integrates all the components in an automation system from a few devices on one network to multiple devices on multiple networks including access to the Internet - helping you to improve flexibility, reduce installation costs, and increase productivity. • EtherNet/IP network is an open industrial networking standard that supports implicit and explicit messaging and uses commercial, off-the-shelf Ethernet equipment and physical media. • ControlNet network allows intelligent, high-speed control devices to share the information required for supervisory control, work-cell coordination, operator interface, remote device configuration, programming, and troubleshooting. • DeviceNet network offers high-speed access to plant-floor data from a broad range of plant-floor devices and a significant reduction in wiring.
Publication 1785-SG001B-EN-P - June 2006
Page 22
20
Select Network Communications
Select a Network Configure your system for information exchange between a range of devices and computing platforms and operating systems. If your application requires
Use this network
Select
• High-speed data transfer between information systems and/or a large quantity of controllers • Internet/intranet connection • Program maintenance
EtherNet/IP
• • • •
• High-speed transfer of time-critical data between controllers and I/O devices • Deterministic and repeatable data delivery • Program maintenance • Media redundancy or intrinsic safety options
ControlNet
• 1785-L20C15 • 1785-L40C15 • 1785-L80C15
• Connections of low-level devices directly to plant floor controllers, without the need to interface them through I/O modules • More diagnostics for improved data collection and fault detection • Less wiring and reduced start-up time than a traditional, hard-wired system
DeviceNet
PLC-5 controller with 1771-SDN scanner module
• Plant-wide and cell-level data sharing with program maintenance
Data Highway Plus
All PLC-5 controllers have at least one built-in, configurable Data Highway Plus channel
• Connections between controllers and I/O adapters • Distributed controllers so that each controller has its own I/O and communicates with a supervisory controller
Remote I/O
All PLC-5 controllers have at least one built-in, configurable remote I/O channel
• Modems • Messages that send and receive ASCII characters to or from devices such as ASCII terminals, bar-code readers, message displays, weigh scales, or printers • Supervisory control and data acquisition (SCADA)
Serial Network
All PLC-5 controllers have one built-in serial port configurable for RS-232, RS-423, or RS-422A
Publication 1785-SG001B-EN-P - June 2006
1785-L20E controller 1785-L40E controller 1785-L80E controller Applicable PLC-5 controller with 1785-ENET interface module
Page 23
Select Network Communications
21
Ethernet/IP protocol is an open industrial-networking standard that supports implicit messaging (real-time I/O messaging), explicit messaging (messaging exchange), or both and uses commercial off-the-shelf Ethernet communication chips and physical media.
EtherNet/IP Protocol
Additionally, EtherNet/IP standard uses the protocols used by the Internet. Both the PLC-5 and Ethernet Interface Module (1785-ENET) contain features that let you to use the Internet to access product information and to create and enhance application diagnostics.
Ethernet PLC-5 Controllers Cat. No.
1785-L20E
User Memory (words), Max 16,000
1785-L40E
48,000
1785-L80E
100,000
Total I/O, Max
Channels
Number of I/O Chassis, Max Cable Total Extended Remote ControlNet -local
512 any mix or 512 in + 512 out (complement) 2048 any mix or 2048 in + 2048 out (complement) 3072 any mix or 3072 in + 3072 out (complement)
1 Ethernet 1 DH+ 1 DH+/remote I/O 1 Ethernet 2 DH+/remote I/O
13
0
12
0
61
0
60
0
1 Ethernet 2 DH+/remote I/O
65
0
64
0
Power Backplane Dissipation, Current Max Load
5810-TC02 18.9 W or 5810-TC15 5810-TC02 18.9 W or 5810-TC15 5810-TC02 18.9 W or 5810-TC15
3.6 A 3.6 A 3.6 A
Laptop Internet Server Workstation
Personal Computer
Modem
PLC-5/20E Controller
SLC 5/05 Controller
Ethernet
PLC-5 Controller with Ethernet Interface Module
ControlLogix Gateway or Logix5550 Controller
ControlLogix Gateway
PLC-5 Controller
Data Highway Plus ControlNet
Publication 1785-SG001B-EN-P - June 2006
Page 24
22
Select Network Communications
PLC-5 Ethernet Interface Module The PLC-5 Ethernet Interface Module (1785-ENET) is a single-slot module that attaches to the side of any Enhanced PLC-5 series B or later controller, Ethernet PLC-5 controller, or ControlNet PLC-5 controller to provide additional Ethernet connectivity. Cat. No.
When used with
The interface module provides
1785-ENET
Ethernet PLC-5 controller
Additional Ethernet connectivity by supporting dual Ethernet links
Enhanced PLC-5 controller
Ethernet connectivity without sacrificing DH+ or remote I/O ports
ControlNet PLC-5 controller
Dedicated Ethernet connectivity for plant and office integration
Using the Ethernet Interface Module’s built-in communication capabilities, your entire enterprise can use standard Ethernet or Internet connectivity to control and monitor production. Using the Internet and Web browser, you can create your own custom Web pages to provide executive summaries of process information. These pages are accessible to any Internet user who has network access to the PLC-5 controller. The embedded Web server provides access to PLC-5 diagnostics. Domain Name Service (DNS) and Simple Network Management Protocol (SNMP) are also supported. Cat. No.
Comm. Rate
1785-ENET 10/100 Mbps
Connections
Design Considerations
64 TCP/IP connections Place in I/O chassis second leftmost slot 512 unsolicited definitions per module attached to controller
Publication 1785-SG001B-EN-P - June 2006
Power Dissipation, Max
Backplane Current Load
11.5 W
2.2 A
Page 25
Select Network Communications
ControlNet Network
23
ControlNet PLC-5 controllers offer embedded ControlNet communication capabilities for control and information processing. The ControlNet network provides both I/O control and peer-to-peer communications on a 5 Mbps network, with repeatability and determinism. You can have multiple ControlNet PLC-5 controllers on one ControlNet network, with each controller handling its own I/O on the network, and at the same time communicating with each other. Multiple controllers can receive input data from one I/O or device node.
ControlNet PLC-5 Programmable Controllers Cat. No.
User Memory (words), Max
Total I/O Max
Channels
Number of I/O Chassis, Max
ControlNet Cable I/O Map Entries
Power Dissipation, Max
Backplane Current Load
1785-L20C15
16,000
512 any mix or 512 in + 512 out (complement)
1 ControlNet 1 DH+ 1 DH+/remote I/O
77
0
12
64
1786-CP
15.8 W
3.0 A
1785-L40C15
48,000
2048 any mix or 1 ControlNet 2048 in + 2048 out 2 DH+/remote I/O (complement)
125
0
60
96
1786-CP
15.8 W
3.0 A
1785-L46C15 Protected
48,000
2048 any mix or 1 ControlNet 2048 in + 2048 out 2 DH+/remote I/O (complement)
125
0
60
96
1786-CP
15.8 W
3.0 A
1785-L80C15
100,000
3072 any mix or 1 ControlNet 3072 in + 3072 out 2 DH+/remote I/O (complement)
125
0
92
128
1786-CP
15.8 W
3.0 A
Total Extended Remote -local
Workstation Running Programming Software with 1784-KTCx
ControlNet
FLEX I/O Adapter PanelView 1200 Operator Terminal ControlLogix Gateway or Logix5550 Controller
PLC-5/40C Controller
1395 Drive
Publication 1785-SG001B-EN-P - June 2006
Page 26
24
Select Network Communications
ControlNet Communication Adapters Cat. No.
Function
1734-ACNR
Interfaces POINT I/O modules in a POINTBus backplane to ControlNet controllers across a ControlNet network 1747-ACN15, Interfaces SLC I/O modules in an SLC -ACNR15 chassis to a ControlNet scanner port across a ControlNet network 1771-ACN15, Interfaces 1771 I/O modules in a 1771 -ACNR15 chassis to a ControlNet scanner port across a ControlNet network 1794-ACN15, Interfaces FLEX I/O modules in a FLEX -ACNR15 I/O rack to a ControlNet scanner port across a ControlNet network 1797- -ACNR15 Interfaces FLEX Ex I/O modules in a FLEX Ex rack to a ControlNet scanner port across a ControlNet network
Comm. Rate
Design Considerations
Cable
5 Mbps
Requires a remote ControlNet PLC-5 controller, Series F, Revision E, or later. Requires a remote ControlNet PLC-5 controller.
Quad shield RG-6 coaxial cable
5 Mbps 5 Mbps 5 Mbps 5 Mbps
Power Dissipation, Max 5.0 W
Backplane Current Load 1.0 A
Quad shield RG-6 coaxial cable
5W
900 mA
Place in remote ControlNet chassis. Requires a ControlNet PLC-5 controller. Requires a remote ControlNet PLC-5 controller.
Quad shield RG-6 coaxial cable
5.2 W
1.0 A
Quad shield RG-6 coaxial cable
4.6 W
640 mA
Requires a remote ControlNet PLC-5 controller.
Quad shield RG-6 coaxial cable
8.5 W
640 mA
ControlNet Hot Backup Module The ControlNet Hot Backup Module provides backup of ControlNet I/O. A secondary controller qualifies critical control information with the primary controller. Both controllers consume information from inputs and connect to outputs, but only the primary controller controls the outputs. The secondary controller establishes control of outputs if the primary controller shuts down.
ControlNet Hot Backup Basic System Cat. No. 1785-CHBM 1785-L40C15/F or 1785-L80C15/F(1) 1771-A1B through 1771-A4B 1771-P4 through 1771-P10 1771-ACN(R)15, 1747-ACN(R), or 1794-ACN(R) 1784-KTCX15 or 1784-PCC card 9234 Series 9357-CNETL3 9234 Series Other System Requirements (1)
Quantity 2 2
Description ControlNet Hot Backup Modules ControlNet PLC-5 Programmable Controllers, Series F or later
2 2 1
1771 I/O Chassis 1771 Power Supplies ControlNet Adapter
1 Communication card for personal computer or laptop computer 1 RSLogix 5 Programming Software, version 3.22 or later 1 RSNetWorx for ControlNet Software, version 1.80.xx or later 1 RSLinx Gateway Communication Software, version 2.00.97.30 or later ControlNet network cables, taps, and terminators for connections between the PLC-5 controllers and I/O adapters
Both controllers must have the same series and firmware revision.
PanelView Plus or Other Interface Device ControlNet PLC-5 Controller with 1785-CHBM Cartridge Installed
1794 FLEX I/O
Redundant ContolNet Network and/ or and/ or 1746 I/O
Publication 1785-SG001B-EN-P - June 2006
ControlNet PLC-5 Controller with 1785-CHBM Cartridge Installed
1771 I/O
Page 27
Select Network Communications
25
The 1771-SDN DeviceNet scanner module acts as an interface between DeviceNet devices and a PLC-5 controller. The scanner module communicates with DeviceNet devices over the network to:
DeviceNet Network
• read and write inputs and outputs to and from a device. • download configuration data to a device. • monitor operational status of a device. The scanner module is a single-slot module that resides in a 1771 I/O chassis that either contains a PLC-5 controller or is on an extended-local I/O link, remote I/O link, or ControlNet network connected to a PLC-5 controller. The scanner module has Auto Device Replacement, change of state, cyclic I/O, pass-through, and Slave mode capability. The number of PLC DeviceNet scanners that can reside in the same I/O chassis is limited only by the I/O chassis size, power supply capacity, and available memory. Cat. No.
Function
Comm. Rate
1771-SDN
Interfaces a local PLC-5 controller to a max of 2 DeviceNet networks
125 Kbps 63 connections per 250 Kbps DeviceNet channel 500 Kbps
Connections
Design Considerations
Cable
Place in the local I/O chassis
1771-CD 6.3 W 10-pin linear plug, 1787-PLUG10R
PLC-5 Controller with 1771-SDN Scanner Module
Power Backplane Dissipation, Current Max Load 1.2 A
Logix5550 Controller with 1756-DNB Module
DeviceNet
Other Devices
Sensor Push button Cluster
Motor Starter Laptop
Input/output Devices
Indicator Lights
Bar Code Scanner
Drive
Publication 1785-SG001B-EN-P - June 2006
Page 28
26
Select Network Communications
The PLC-5 serial port is configurable for RS-232, RS-423, or RS-422A compatible serial communication. Use the serial port to connect devices that:
Serial Network
• communicate using the DF1 protocol, such as modems, communication modules, programming workstations, or other serial devices. • send and receive ASCII characters, such as ASCII terminals, bar-code readers, and printers. When configured for System mode, the serial port supports the DF1 protocol. Use System mode to communicate with others devices on the serial link. Use This DF1 Mode
For
Point-to-point
• Communication between a PLC-5 controller and other DF1-compatible devices. • In Point-to-Point mode, the PLC-5 controller uses DF1 full-duplex protocol.
DF1 Master
• Control of polling and message transmission between the master and each remote node. • In Master mode, the PLC-5 controller uses DF1 half-duplex polled protocol.
DF1 Slave
• Using the controller as a slave station in a master/slave serial network. • In Slave mode, the PLC-5 controller uses DF1 half-duplex protocol.
The serial port, in System mode, also supports supervisory control and data acquisition (SCADA) applications. SCADA systems let you monitor and control remote functions and processes using serial communication links between master and slave locations.
(1)
Cat. No.
Function
Comm. Rate
1771-DA
Interfaces a PLC-5 controller and a peripheral device that generates ASCII characters
Configurable, RS-232-C depending Current loop, 20 mA on serial protocol
Connections
Design Considerations
Cable
Power Backplane Dissipation, Current Max Load
Place in the local I/O chassis
Custom 26-pin cable(1)
6.8 W
See the Enhanced and Ethernet PLC-5 Programmable Controllers User Manual, publication 1785-UM012.
Publication 1785-SG001B-EN-P - June 2006
1.3 A
Page 29
Select Network Communications
27
The PLC BASIC Module occupies one slot in the 1771 I/O chassis and runs user-written BASIC and C programs. These programs are independent of your PLC-5 controller and provide an easy and fast interface between a PLC-5 controller, 1771 backplane, and RS-232, -422, or -485 devices. The module can also communicate with a remote SLC controller or remote device on the DH-485 network through a DH-485 port. Cat. No.
Function
Comm. Rate
1771-DB
Provides an interface between a PLC-5 controller, 1771 backplane, and RS-232, -422, or -485 devices
Configurable, • 2 ports for RS-232, Place in the local I/O depending on -422, or -485 chassis serial protocol • 1 port for DH-485
Connections
Design Considerations
Cable
• Data Highway 1770-CD • RS-232 1770-CG or Modem Interface Cable 1770-CP
Power Dissipation, Max 4W
Backplane Current Load 0.75 A (with 1747-PIC) 0.65 A
The communication controller modules, 1771-KE and 1771-KF, link intelligent RS-232-C devices to Data Highway. Both of these modules provide a choice of two protocols on the RS-232-C link - full-duplex and half-duplex. These modules perform the same functions, however their mounting styles and power supply requirements are different. Cat. No.
Function
Comm. Rate
Connections
Design Considerations
1771-KE
Provides an interface between RS-232-C devices and Data Highway link with both full-duplex and half-duplex protocols
• Data Highway 57 Kbps • RS-232-C from 110 to 19 Kbps
Data Highway, RS-232
Place in the local I/O chassis. Power source is the 1771 I/O chassis power supply.
1771-KF
Provides an interface between RS-232-C devices and Data Highway link with both full-duplex and half-duplex protocols
• Data Highway 57 Kbps • RS-232-C from 110 to 19 Kbps
Data Highway, RS-232
Cable
Power Dissipation, Max 6.3 W
• Data Highway 1770-CD • RS-232 1770-CG or Modem Interface Cable 1770-CP Includes mounting • Data Highway 6.3 W bracket for external 1770-CD mounting or in a standard • RS-232 industrial enclosure 1770-CG or (NEMA Type 12 or Modem similar). Power source is Interface Cable user-supplied (1771-P2 or 1770-CP similar).
Backplane Current Load 1.2 A
1.2 A
Publication 1785-SG001B-EN-P - June 2006
Page 30
28
Select Network Communications
When configured for User mode, the serial port supports ASCII devices. Use the PLC-5 ASCII instructions to send and receive information from these devices.
Computer Workstation Server
Computer Workstation
DCE Remote Station
Ethernet
Modem PLC-5/40E Workstation Remote Station Modem
Master Station
Oil Well
Modem
Gas Well
Remote Station
Remote Station
Unloading Storage Facility Storage Tanks
Tank Farm
Unloading Dock
Mainline Pump Station
Remote Station
Remote Station
Refinery Storage Storage Tanks
Remote Station Mainline Pump Station
Storage Tanks
Remote Station Storage/ Delivery Facility Storage Tanks
Metered Truck Rack 20031-M
Publication 1785-SG001B-EN-P - June 2006
Page 31
Select Network Communications
29
The Data Highway Plus (DH+) network is a local area network designed to support remote programming and data acquisition for factory-floor applications. You can also use DH+ communication modules to implement a small peer-to-peer network.
Data Highway Plus
You can use a DH+ network for data transfer to other PLC-5 controllers or high-level computers and as a link for programming multiple PLC-5 controllers. A PLC-5 controller can communicate over a DH+ network with other controllers and with a workstation. The DH+ network supports daisy-chain and trunkline-dropline configurations. PLC-5 Controller
PLC-5 Controller
Workstation
Workstation with RSLogix 5 Software
Data Highway Plus
SLC-5/04 Controller
Cat. No.
Function
1785-KA
1785-KE
Comm. Rate
ControlLogix Chassis with 1756-DHRIO Module
Connections
Design Considerations
Cable
Power Dissipation, Max 10.5 W
Provides an interface • DH+ 57 Kbps between Data Highway • DH-485 Plus and Data configurable Highway-485 link
DH+ DH-485
Provides an interface • DH+ 57 Kbps between Data Highway • RS-232-C Plus and RS-232-C link configurable
DH+ RS-232-C
Place in the local chassis • Data Highway 1770-CD • RS-232 1770-CG or Modem Interface Cable 1770-CP Place in the local chassis • Data Highway 6.3 W 1770-CD • RS-232 1770-CG or Modem Interface Cable 1770-CP
Backplane Current Load 2.0 A
1.2 A
Publication 1785-SG001B-EN-P - June 2006
Page 32
30
Select Network Communications
The strength and versatility of the remote I/O network comes from the breadth of products it supports. In addition to 1771 I/O, the remote I/O network supports many Rockwell Automation and third-party devices.
Remote I/O
Typical applications range from simple I/O links with controllers and I/O, to links with a variety of other devices. You connect devices through remote I/O adapter modules or built-in remote I/O adapters. Using the remote I/O network instead of direct-wiring a device over a long distance to a local I/O chassis helps reduce installation, startup, and maintenance costs by placing the I/O closer to the sensors and actuators. Some devices, like PLC-5 support Pass-Through, let you configure devices on a remote I/O network from an Ethernet, ControlNet, or Data Highway Plus network.
Workstation with PanelBuilder Software
ControlNet, EtherNet/IP, or DH+ Network
PLC-5 Controller
Remote I/O Link
FLEX I/O Adapter
1771 I/O Adapter
Cat. No.
SLC I/O Adapter PanelView 1200 Operator Terminal
Function
Comm. Rate
Connections
Design Considerations
Interfaces I/O modules in an I/O chassis to a remote scanner port across a remote I/O link 1771-DCM Provides a remote I/O adapter port for a local PLC-5 controller to communicate with a remote I/O scanner port of a supervisory process across a remote I/O link
57.6 Kbps 115 Kbps 230 Kbps
Remote I/O adapter port
57.6 Kbps 115.2 Kbps
Remote I/O adapter port
Place in a remote chassis. 1770-CD Requires a PLC-5 Belden 9463 controller that supports remote I/O Place in the local chassis 1770-CD Belden 9463
1771-ASB
Publication 1785-SG001B-EN-P - June 2006
Cable
Power Dissipation, Max 5.2 W
Backplane Current Load 1.0 A
6.3 W
1.2 A