Page 9

Select I/O Modules

Step 1 - Select: • 1771 I/O Modules • 1746 I/O Modules • 1794 FLEX I/O Modules • 1797 FLEX Ex I/O Modules • 1791D CompactBlock I/O Modules • 1734 POINT I/O Modules • Encompass Partner Program I/O Modules

7

Select I/O Modules Rockwell Automation offers many types of I/O modules and has more than 3 million modules installed in applications worldwide. Rockwell Automation offers chassis-based and both block and modular-distributed modules. The following sections outline the available I/O modules. For more information about these I/O modules, see the Allen-Bradley I/O Module Brochure, publication ACIG-BR002, or visit the Rockwell Automation Distributed I/O Web page at http://www.ab.com/io.

If your application requires preferred I/O for PLC-5, and

Use this type of I/O

On any of these networks

• • • •

1771 I/O see page 8

- ControlNet - Remote I/O - Extended Local I/O

If your application

Use this type of I/O

On any of these networks

• Is chassis-based and requires different types of I/O • Has smaller size requirements than 1771 • Communicates with SLC controllers

1746 I/O see page 13

- ControlNet - Remote I/O - Extended Local I/O

• Has distributed control that requires multiple types of I/O devices near a machine

1794 FLEX I/O see page 14

- EtherNet/IP - ControlNet - DeviceNet - Remote I/O - Extended Local I/O - PROFIBUS DP

• Has distributed control in a hazardous area

1797 FLEX Ex I/O see page 15

- ControlNet via coax or fiber - DeviceNet via bus isolator - EtherNet/IP via bus isolator - PROFIBUS DP via bus isolator

• Requires rackless design with panel or DIN-rail mounting • Requires modular, high-density I/O

1769 Compact I/O see page 15

- DeviceNet - Local I/O

• Has distributed control • Must have I/O mounted near sensors or actuators • Uses motor starters, solenoids, or indicators

1791D I/O CompactBlock I/O see page 16

- DeviceNet - Remote I/O - PROFIBUS DP

• Requires high modularity • Requires flexibility and low-cost of ownership

1734 POINT I/O see page 17

- DeviceNet - ControlNet - EtherNet/IP - PROFIBUS DP

• Requires functionality not delivered in Rockwell Automation products

Encompass Partners Program products, see page 18

Multiple

Native I/O providing highest performance Is chassis-based and needs to accommodate a wide range of I/O types Controls an entire process Is a master/slave configuration for distributed control

Publication 1785-SG001B-EN-P - June 2006

Page 10

8

Select I/O Modules

1771 I/O Modules

The 1771 series I/O modules offer digital, analog, and special-requirement modules. The 1771 I/O modules feature a wide range of: • signal interfaces to ac and dc sensors and actuators. • I/O densities with as many as 32 I/O points per module. • signal levels, including standard analog inputs and outputs and direct thermocouple and RTD temperature inputs. PLC-5 controllers support 1771 I/O over these networks: • Local I/O • Remote I/O • Extended-local I/O • ControlNet When you select 1771 I/O modules, you must also select: • Chassis • Power supply • Adapter module (if in remote chassis or extended-local chassis)

1771 Digital Input Modules Category

Cat. No.

Inputs and Outputs

Voltage

Backplane Current Load

TTL

1771-IG

8 in

--

122 mA

24V dc Sink Source Load

16 in

--

130 mA

1771-IB

8 in

10...27V

74 mA

1771-IBD

16 in

10...30V

250 mA

1771-IBN

32 in

10...30V

280 mA

1771-IT

8 in

12...24V

74 mA

1771-IQ

8 in

5...30V

150 mA

1771-IQ16

16 in

10...32V isolated

100 mA

1771-IS

72 in

5V multiplexer

800 mA

1771-DW

7 in

15...27 wire fault

300 mA

1771-DS

8 in

10...27V latching

375 mA

48V dc Sink Source Load

1771-IC

8 in

42...56V

74 mA

1771-IH

8 in

24...50V

74 mA

24V dc Source Sink Load

1771-IV

8 in

12...24V

74 mA

1771-IVN

32 in

10...30V

280 mA

1771-IQ

8 in

5...30V

150 mA

1771-IQ16

16 in

10...32V isolated

100 mA

24V ac

Publication 1785-SG001B-EN-P - June 2006

1771-IGD

1771-IN

8 in

12...28V

80 mA

1771-IND

16 in

16...30V ac 9...30V dc

250 mA

Page 11

Select I/O Modules

Category

Cat. No.

Inputs and Outputs

Voltage

Backplane Current Load

120V ac/dc

1771-ID

6 in

92...38V isolated

74 mA

1771-IAD

16 in

79...138V

195 mA

1771-ID16

16 in

77...138V ac 105...138V dc isolated

75 mA

1771-IA

8 in

87...138V ac 97...138V dc

75 mA

120V ac

1771-IAN

32 in

85...138V

280 mA

220V ac/dc

1771-ID01

6 in

184...276V ac/dc

74 mA

1771-IM

8 in

184...276V ac/dc

75 mA

9

1771 Digital Output Modules Category

Cat. No.

Inputs and Outputs

Voltage

Backplane Current Load

TTL

1771-OG

8 in

5.0...5.3V

168 mA

1771-OGD

16 in

5.0...5.3V

230 mA

1771-OVN

32 out

10...30V

330 mA

1771-OQ16

16 out

10...32V isolated

400 mA

1771-OQ

8 out

20.4...26.4V isolated

225 mA

1771-OQ16

16 out

10...32V isolated

400 mA

1771-OB

8 out

10...27V

165 mA

1771-OBD

16 out

10...60V

300 mA

1771-OBN

32 out

10...30V

330 mA

48V dc Source

1771-OC

8 out

42...53V

165 mA

24V ac

1771-ON

8 out

20...30V

225 mA

120V ac

1771-OP

4 out

92...138V protected

350 mA

1771-OD

6 out

92...138 isolated

225 mA

1771-ODZ

8 out

92...138V isolated

350 mA

1771-ODD

16 out

85...138V isolated

420 mA

1771-OA

8 out

92...138V

210 mA

1771-OD16

16 out

74...138V isolated

200 mA

24V dc Sink 24V dc Source

1771-OAD

16 out

10...138V

295 mA

120/240V ac

1771-OAN

32 out

80...265V

800 mA

220V ac

1771-OR

6 out

184...276V isolated

255 mA

1771-OM

8 out

184...250V

225 mA

Publication 1785-SG001B-EN-P - June 2006

Page 12

10

Select I/O Modules

Category

Cat. No.

Inputs and Outputs

Voltage

Backplane Current Load

24-120V ac/dc Relay Contact

1771-OW

8 out

24...138V ac resistive load 24-125V dc

700 mA

1771-OW16

16 out

24...250V ac isolated 24...150V dc isolated

1.3 A

1771-OWN

32 out

24...138V ac 24...125V dc

2.5 A

1771-OWNA

32 out

24...138V ac resistive load 24-125V dc

2.5 A

1771-OX

4 out

0...250V ac isolated inductive load 0...175V dc isolated

550 mA

1771-OYL

8 out

0...24V ac/dc

420 mA

1771-OZL

8 out

0...24V ac/dc

420 mA

0-24V ac/dc

1771 Analog Input Modules Category

Cat. No.

Inputs and Outputs

Range: Voltage and Current

Backplane Current Load

Selectable

1771-IFE

8 differential or 16 single

+10V dc +20 mA

750 mA

1771-IFF

8 differential or 16_single

+10V dc +20 mA

750 mA

1771-IL

8 differential, isolated

+10V dc +20 mA

1.3 A

1771-IE

8 single

+10V dc

500 mA

1771-NIV

8 in

+5V dc +2 0mA

1.5 A

1771-NIV1

8 in

+10V dc +20 mA

1.5 A

Voltage Only

1771-IFMS

8 differential

0...50 mV

750 mA

Current Only

1771-NIS

8 in isolated

4...20 mA

2.9 mA

Thermocouple

1771-IXE

8 floating differential

+99.99 mV

750 mA

1771-IXHR

8 floating differential

+99.99 mV

750 mA

1771-NT1

8 mV/TC

+100 mV

1.5 A

1771-NT2

8 mV/TC

-5/+55 mV dc

1.5 A

1771-IR

6 in

RTD

800 mA

1771-NR

8 in

RTD isolated

1.5 A

1771-NIVR

4V/current in

+5V dc +20 mA

1.5 A

1771-NIVT

4V/current and 4 mV/TC in

+5V dc for volt/current +20 mA +100 mV for mV/TC

1.5 A

RTD Mixed

Publication 1785-SG001B-EN-P - June 2006

Page 13

Select I/O Modules

11

1771 Analog Output Modules Category

Cat. No.

Inputs and Outputs

Range: Voltage and Current

Backplane Current Load

Selectable

1771-OFE1

4 out

+10V dc

1.5 A

Current Only

Voltage Only

1771-OFE2

4 out

4...20 mA

1.5 A

1771-OFE3

4 out

0...50 mA

2.5 A

1771-NOC

8 out

0...25 mA

2.9 A at 20 mA 3.3 A at 25 mA

1771-NOV

8 out

+10V dc

2.1 A

1771 Analog Combination Modules Category

Cat. No.

Inputs and outputs

Range: Voltage and Current

Backplane Current Load

Selectable Voltage

1771-NBV1

6 in 2 out

+10V dc +20 mA

1.8 A

Selectable Current

1771-NBVC

6 in 2 out

+5V dc/+20mA 0...25 mA

1.8 A

Current

1771-NB4S

2 in 2 out isolated

4...20 mA 0...25 mA

1.6 A

1771-NBSC

6 in 2 out isolated

4...20 mA 0...25 mA

3.0 A

1771-NB4T

2 in 2 out mV/TC +100 mV 0...25 mA

1.5 A

1771-NBRC

6 in 6 out

RTD 0...25 mA

1.8 A

1771-NBTC

6 in 2 out mV/TC +100 mV 0...25 mA

1.6 A

RTD

Publication 1785-SG001B-EN-P - June 2006

Page 14

12

Select I/O Modules

1771 Intelligent Modules Category

Cat. No.

Use

Backplane Current Load

Counter

1771-IJ

Incremental encoder/counter

1.2 A

Positioning

1771-IK

High-speed counter

1.2 A

1771-VHSC

Very high speed counter

0.65 A

1771-DE

Absolute encoder

0.8 A

1771-DL

Gray encoder

0.12 A

1771-QA

Stepper motor positioning

0.8...2.4 A

1771-QB

Linear positioning

1.6 A

1771-QC

Servo positioning

1.75 A

1771-M3

Servo controller

1.75 A

1771-ES

Servo encoder feedback expander

1.7 A

1771-M1

Stepper motor controller

1.75 A

1771-QD

Injection molding

0.5 A

1771-QDC

Plastic molding

1.2 A

1771-QH

Force control

1.2 A

1771-HS

IMC 120 motion control

0.72 A

1771-HS1

IMC 121 motion control

1.06 A

1771-HS3

IMC 123 motion control

1.06 A

1771-HRA

Resolver excitation

0.065 A

Flow

1771-CFM

Configurable flowmeter

1.0 A

Specialty

1771-PM

Clutch/brake control

1.2 A

1771-SIM

I/O simulator

0.2 A

1771-DR

High-speed logic

1.1 A

1771-PD

PID control

1.2 A

1771-DC

Real-time clock

1771-DB

BASIC

1771-LC

Loop control

1771-TCM

Temperature control

1.5 A

Temperature

0.65 A without DH-485 0,75 A with DH-485

Hydraulic

1771-QH

High-speed transparent transition

1.2 A

Plastics

1771-QDC

Plastic molding

1.2 A

1771-QI

Co-injection

1.2 A

For more information about the family of 1771 I/O modules, see the following publications.

Publication 1785-SG001B-EN-P - June 2006

Publication Title

Publication Number

1771 Digital I/O ac Input and Output Modules Product Data

1771-2.182

1771 Analog Input and Output Modules Product Data

1771-2.183

1771 Digital I/O dc Input and Output Modules Product Data

1771-2.180

Page 15

Select I/O Modules

1746 I/O Modules

13

The 1746 I/O modules (SLC 500 I/O) provide a cost-effective, Remote I/O option. Use an SLC 500 Remote I/O module (1747-ASB) or ControlNet adapter module (1747-ACN15 or -ACNR15) to directly interface 1746 I/O modules to the PLC-5 system. The 1746 I/O modules feature: • high-density, 32-point and combination modules, which reduce rack size and panel space requirements. • removable terminal blocks and 16-point modules, which simplify wiring and replacing modules. • industrial design, including input filtering and optical isolation. PLC-5 controllers support 1746 I/O over these networks: • Remote I/O • ControlNet When you select 1746 I/O modules, you must also select: • Chassis • Power supply • Cabling components • Adapter module, if in remote chassis or extended-local chassis For more information, see the following publications. Publication Title

Publication Number

SLC 500 System Overview

1747-SG001

SLC Analog I/O Modules Technical Data

1746-TD001

SLC Modular Chassis and Power Supplies Technical Data

1746-TD003

Publication 1785-SG001B-EN-P - June 2006

Page 16

14

Select I/O Modules

1794 FLEX I/O Modules

FLEX I/O is a cost-effective, flexible, modular I/O system for distributed applications and offers all the functions of larger rack-based I/O without the space requirements. You can independently select the I/O type, termination, and network, appropriate for your specific application. This means one I/O product line can fit all your needs. The 1794 FLEX I/O modules feature: • modular design, which reduces costs by solving a large range of application requirements with one I/O architecture. • small size, which reduces packaging costs. • individual wire-termination locations, which reduce purchasing costs and complexity, as well as packaging costs. • diagnostics and removal and insertion under power (RIUP), which lowers the mean time to repair equipment and leverages your control investment. • flexible communications, which helps to control future costs by providing an economical migration path. PLC-5 controllers support 1794 I/O over these networks: • Remote I/O • ControlNet • DeviceNet For more information about 1794 FLEX I/O, see the FLEX I/O and FLEX Ex I/O Selection Guide, publication 1794-SG002.

Publication 1785-SG001B-EN-P - June 2006

Page 17

Select I/O Modules

1797 FLEX Ex I/O Modules

15

The 1797 series I/O modules (FLEX Ex I/O) are a flexible I/O system that mounts directly to the controlled equipment in a hazardous area. This eliminates the need for intrinsically safe (IS), barriers/isolators and separation of control and process. Additionally, the modules: • offer modularity for distributed intrinsically-safe systems. • have dual-fault protection IS circuits that provide high fault tolerance. • have I/O circuitry that provides full IS field-device protection. PLC-5 controllers support 1797 I/O over these networks: • Remote I/O • ControlNet • DeviceNet When you select 1797 FLEX Ex I/O modules, you must also select: • adapter module and cabling components. • bus isolator module and cabling components. • terminal base unit. • DIN rail. • power supply. For more information about 1797 FLEX Ex I/O, see the FLEX I/O and FLEX Ex I/O Selection Guide, publication 1794-SG002.

Publication 1785-SG001B-EN-P - June 2006

Page 18

16

Select I/O Modules

1791D CompactBlock I/O Modules

The 1791D I/O modules (CompactBlock I/O) are designed for applications that require I/O to be distributed close to sensors and actuators or to be placed in small enclosures. The modules feature: • self-contained package that provides cost-effective distribution of up to 32 points per node. • small size that lets you install in shallow and confined areas. • hardware watchdog circuit. • DeviceLogix Smart Component Technology that provides limited I/O logic for intelligent I/O block. PLC-5 controllers support 1791D I/O over these networks: • Remote I/O • DeviceNet • PROFIBUS DP When you select 1791D I/O modules, the I/O circuits, a built-in power supply, and a Remote I/O adapter are included. You must select an enclosure and cabling components. For more information about 1791D CompactBlock I/O, see the 1791D Block I/O Technical Data, publication 1791D-TD001.

Publication 1785-SG001B-EN-P - June 2006

Page 19

Select I/O Modules

1734 POINT I/O Modules

17

POINT I/O is a family of I/O modules that are ideal for applications where flexibility and low-cost of ownership are key for successful control system design and operation. POINT I/O can be used in remote device panels, local control panels, and can be accessed from many locations including the Internet. This product is just-what-you-need granularity in one to eight points to reduce system cost and size. POINT I/O modules feature: • A highly modular design with 1 point to 8 point modularity • Broad application coverage • Parameter-level explicit messaging • Removal and insertion under power • Channel-level open-wire detection with electronic feedback • Robust backplane design • Built-in DIN-rail grounding PLC-5 controllers support POINT I/O over these networks: • DeviceNet • ControlNet • PROFIBUS DP When you select POINT I/O modules, you must also select: • A communication interface • I/O devices based on field devices • Wiring base assembly • Power distribution modules For more information about POINT I/O, see the POINT I/O Selection Guide, publication 1734-SG001.

Publication 1785-SG001B-EN-P - June 2006

Page 20

18

Select I/O Modules

Additional I/O Selections

The Encompass Partners Program, Rockwell Automation’s third-party product referencing program, builds on the strengths of our products. As a technology-sharing program, Encompass is product-based and application-focused. Encompass allows third-party companies to provide functionality not delivered in Rockwell Automation products. The following table lists additional I/O choices that are part of the Encompass program. Encompass Partner

Products

Advanced Micro Controls, Inc.

• 1771 LDT Interface Module • 1771 Programmable Limit Switch • 1771 Resolver Interface Module

Ametek Automation and Process Technologies

Gemco Series 1771 Programmable Limit Switch

Hardy Instruments

1771-WS Weigh Scale Module

Hiprom Ltd.

1771 GPS Time Stamp Module

Miille Applied Research Company, Inc.

Dial Up and Leased Line Modems and Protocol Converters

Phoenix Digital Corporation

Optical Comm Modules for: • Ethernet • ControlNet • DF-1 • Data Highway • DH-485 • Modbus • RS-232 • RS-485

ProSoft Technology, Inc.

• • • • • • •

Spectrum Controls, Inc.

• High-density 32 Analog Input Module • 200V ac/dc Isolated 16 Input Module • 120/240V ac Isolated 16 Output Module

Weed Instrument

Fiber Optic Modems

Woodhead

PLC-5 Scanners for PROFIBUS DP

“C” Programmable Solutions AGA/API Flow Computers HART Honeywell DE Interface Modbus Plus Communications-PLC PLC Protocol Solutions PLC Protocol Solutions-MVI

For more detailed information, refer to the Encompass product directory, publication 6873-QR004, or see www.rockwellautomation.com/encompass.

Publication 1785-SG001B-EN-P - June 2006