Page 33
31
Select Controllers
Step 3 - Select: • Enhanced PLC-5 Controllers • Ethernet PLC-5 Controllers • ControlNet PLC-5 Controllers • Protected PLC-5 Controllers • EEPROM Memory Modules • Replacement Batteries
Select Controllers
PLC-5 controllers are high-speed, single-slot controllers you can use for control and information processing. PLC-5 controllers are designed for larger sequential and regulatory control applications with specialized I/O requirements and/or the need to coordinate with other controllers and devices. PLC-5 controllers come with different memory sizes and network connections. The Enhanced PLC-5 controllers offer a standard set of functions and communication options. The other PLC-5 controllers offer different communication options, while maintaining the same functions. Choose the controller that best meets your needs.
Publication 1785-SG001B-EN-P - June 2006
If your application requires
Select from
• Connectivity to a large number of Remote I/O devices • Connectivity to a large number of DH+ devices
Enhanced PLC-5 Controllers see page 32
• EtherNet/IP connectivity • Communication with other Ethernet PLC-5 controllers and host computers
Ethernet PLC-5 Controllers see page 33
• High-speed communication for control and information processing • Deterministic, repeatable data transfers • ControlNet connectivity
ControlNet PLC-5 Controllers see page 34
• Limited access to critical or proprietary areas of programs • Selectively access to processor memory and I/O elements • Restricted use of processor operations
Protected PLC-5 Controllers see page 35
Page 34
32
Select Controllers
Enhanced PLC-5 Controllers Every PLC-5 controller offers built-in, configurable ports for Data Highway
Plus (DH+) or Remote I/O. A DH+ connection supports remote programming and information access, in addition to peer-to-peer communication between the PLC-5, other controllers, and devices. A Remote I/O connection supports real-time data exchange for I/O, operator interface, and other third-party devices.
Cat. No.
User Memory (words), Max
Total I/O, Max
1785-L11B
8000
512 any mix or 384 in + 384 out (complement)
1785-L20B
16,000
1785-L30B
Channels
Number of I/O Chassis, Max
Power Backplane Dissipation, Current ControlNet Max Load
Total
Extended Remote -local
1 DH+/remote I/O
5
0
4
0
12 W
2.3 A
512 any mix or 512 in + 512 out (complement)
1 DH+ 1 DH+/remote I/O
13
0
12
0
12 W
2.3 A
32,000
1024 any mix or 1024 in + 1024 out (complement)
2 DH+/remote I/O
29
0
28
0
12 W
2.3 A
1785-L40B
48,000
2048 any mix or 2048 in + 2048 out (complement)
4 DH+/remote I/O
61
0
32 max/link
0
17.3 W
3.3 A
1785-L60B
64,000
3072 any mix or 3072 in + 3072 out (complement)
4 DH+/remote I/O
93
0
32 max/link
0
17.3 W
3.3 A
1785-L80B
100,000
3072 any mix or 3072 in + 3072 out (complement)
4 DH+/remote I/O
93
0
32 max/link
0
17.3 W
3.3 A
Publication 1785-SG001B-EN-P - June 2006
Page 35
33
Select Controllers
Ethernet PLC-5 Controllers
The Ethernet PLC-5 controller integrates the Allen-Bradley architecture into an industry-standard EtherNet/IP system, offering a flexible and open solution. With the Ethernet PLC-5 controller’s built-in communication capabilities, your entire enterprise can use standard Ethernet or Internet connectivity to control and monitor production. Using the Internet and Web browser, you can create your own custom Web pages to provide executive summaries of process information. These pages are accessible to any Internet user who has network access to the PLC-5 controller. The embedded Web server provides access to PLC-5 diagnostics. Domain Name Service (DNS) and Simple Network Management Protocol (SNMP) are also supported.
Cat. No.
User Memory (words), Max
Total I/O, Max
1785-L20E
16,000
512 any mix or 512 in + 512 out (complement)
1785-L40E
48,000
1785-L80E
100,000
Total
Extended -local
Remote
Power Backplane Dissipation, Current ControlNet Max Load
1 Ethernet 1 DH+ 1 DH+/remote I/O
13
0
12
0
19 W
3.6 A
2048 any mix or 2048 in + 2048 out (complement)
1 Ethernet 2 DH+/remote I/O
61
0
60
0
19 W
3.6 A
3072 any mix or 3072 in + 3072 out (complement)
1 Ethernet 2 DH+/remote I/O
65
0
64
0
19 W
3.6 A
Publication 1785-SG001B-EN-P - June 2006
Channels
Number of I/O Chassis, Max
Page 36
34
Select Controllers
The ControlNet PLC-5 controller offers embedded ControlNet communication capabilities for control and information processing. The ControlNet network provides both I/O control and peer-to-peer communications on a 5 Mbps network, with repeatability and determinism.
ControlNet PLC-5 Controllers
You can have multiple ControlNet PLC-5 controllers on one ControlNet network, with each controller handling its own I/O on the network, and at the same time communicating with each other. Multiple controllers can receive input data from one I/O or device node.
Cat. No.
User Memory (words), Max
Total I/O, Max
1785-L20C15
16,000
512 any mix or 512 in + 512 out (complement)
1785-L40C15
48,000
1785-L46C15 Protected 1785-L80C15
Total
Extended Remote -local
ControlNet Power Backplane I/O Map Dissipation, Current Entries Max Load
1 ControlNet 1 DH+ 1 DH+/remote I/O
77
0
12
64
15.8 W
3.0 A
2048 any mix or 2048 in + 2048 out (complement)
1 ControlNet 2 DH+/remote I/O
125
0
60
96
15.8 W
3.0 A
48,000
2048 any mix or 2048 in + 2048 out (complement)
1 ControlNet 2 DH+/remote I/O
125
0
60
96
15.8 W
3.0 A
100,000
3072 any mix or 3072 in + 3072 out (complement)
1 ControlNet 2 DH+/remote I/O
125
0
92
128
15.8 W
3.0 A
Publication 1785-SG001B-EN-P - June 2006
Channels
Number of I/O Chassis, Max
Page 37
35
Select Controllers
Protected PLC-5 Controllers The Protected PLC-5 controller lets you limit access to critical or proprietary areas of programs, selectively guard controller memory and I/O, or restrict use of controller operations. The distinctive safety-yellow labels on the controller identify the protected PLC-5 controller. Use the programming software to assign class privileges to specific user accounts or a user’s job function, such as system administrator, plant engineer, maintenance engineer, or operator. Using four privilege classes and associated passwords, you can limit access to critical areas of programs and restrict access to: • communication channels. • remote nodes attached to the ControlNet or DH+ network. • program files. • data files. The protected PLC-5 controller expands system validity and security beyond that provided by the password-and-privilege feature of the other PLC-5 controllers. The Rockwell Automation clutch/brake application package combines the protected PLC-5 controller with specially-designed software to support stamping press applications.
Cat. No.
User Memory (words), Max
Total I/O, Max
1785-L26B
16,000
512 any mix or 512 in + 512 out (complement)
1785-L46B
48,000
1785-L46C15 Protected 1785-L86B
Channels
Number of I/O Chassis, Max
ControlNet Power Backplane I/O Map Dissipation, Current Entries Max Load
Total
Extended Remote -local
1 DH+ 1 DH+/remote I/O
13
0
12
0
12 W
2.3 A
2048 any mix or 2048 in + 2048 out (complement)
4 DH+/remote I/O
61
0
32 max/link
0
17.3 W
3.3 A
48,000
2048 any mix or 2048 in + 2048 out (complement)
1 ControlNet 2 DH+/remote I/O
125
0
60
96
15.8 W
3.0 A
100,000
3072 any mix or 3072 in + 3072 out (complement)
4 DH+/remote I/O
93
0
32 max/link
0
17.3 W
3.3 A
Publication 1785-SG001B-EN-P - June 2006
Page 38
36
Back Up Controller Memory You can back up program files using an EEPROM module. Cat. No. (1)
1785-ME16 1785-ME32 1785-ME64 1785-CHBM
Provides this amount of backup memory 16,000 words 32,000 words 64,000 words 100,000 words
(1)Not for use with ControlNet PLC-5 controllers.
Battery Replacement and Life Estimates Cat. No.
Applies to
When used in this controller
At this temperature
1770-XYC
All PLC-5 Programmable Controllers
PLC-5/11, -5/20 and -5/20E
60 oC (140 oF)
Battery Life Estimate Power off 100% Power off 50% 256 days 1.4 years
25 oC (77 oF)
2 years
4 years
60 oC (140 oF)
84 days
150 days
25 oC (77 oF)
1 year
1.2 years
All Others