Page 1 of 1785 PLC-5 Programmable Controllers Addressing Reference Manual

Manual · Allen-Bradley

1785 PLC-5 Programmable Controllers Addressing Reference Manual

Manual28 pagesPDF 172 KB

Addressing reference manual for Allen-Bradley 1785 PLC-5 processors: memory map, logical ASCII addressing and status file.

Download the PDF172 KB

Filed with · 1 model

Also filed with these models on the old site

Summary

What is in it

A short Allen-Bradley reference that shows how to specify addresses in the data table of 1785 PLC-5 processors, from the PLC-5/10 to the PLC-5/80. It gives the memory map, the general format for logical ASCII addressing, addressing for the I/O image tables, a word-by-word description of the status file with fault codes, addressing for ASCII, binary, BCD, floating-point and integer files, and structured data such as timers, counters, control, PID and message files.

Its parts

  1. Summary of Changes
  2. Addressing for 1785 PLC-5 Processors

From the manual · read page by page

Key facts from this manual

Some pages are scans or cannot be read; this says only what the readable text supports. Each line names its page in the PDF.

The Allen-Bradley 1785 PLC-5 Programmable Controllers Addressing Reference Manual, publication 5000-6.4.4 of August 1995. It covers the PLC-5/10, -5/11, -5/12, -5/15, -5/20, -5/25, -5/30, -5/40, -5/40L, -5/60, -5/60L and -5/80 processors as a family and does not name the 1785-LT part number. It explains the data table memory map, logical ASCII address formats, the status file with its fault bits and codes, and the structures of timer, counter, control, PID and message files.

Document
Addressing reference for the 1785 PLC-5 data table, using logical ASCII addresses p. 4
Processors
PLC-5/10, /11, /12, /15, /20, /25, /30, /40, /40L, /60, /60L and /80 p. 4
Address format
$ B 123 : 123 / 15: file type, file number, word number, bit number p. 7, 15
Fixed files
Output, input and status files are always file numbers 0, 1 and 2; no file number is entered for them p. 7
Data file types
A = ASCII display, B = Binary, D = BCD display, F = Floating-point, N = Integer p. 15
Status file size
Words 0 - 128; 0 - 31 on PLC-5/10, -5/12, -5/15 and -5/25 p. 7, 9
Fault codes (S:12)
0-9 user-defined; 10 failed data table check; 11 bad user program checksum; 16 bad instruction found; 19 download aborted; 34 bad timer parameters entered p. 12
Low battery bit
S:10 bit 0: battery is low (replace in 1-2 days) p. 11
Major fault word
S:11, with bits for corrupted program file, programming error, SFC fault, watchdog faulted and system configured wrong p. 11
Switch settings
S:2: bits 0 - 7 DH+ station number; bits 11-12 I/O chassis addressing (1/2-slot, 1-slot or 2-slot) p. 10
Scan time and clock
S:8 last program scan and S:9 maximum program scan (ms); S:18 to S:23 processor clock year to second p. 10, 13
Data ranges
Integer and binary words -32,768 thru +32,767; floating point IEEE 32-bit, +/- 1.1754944 E-38 thru +/- 3.4028237 E+38 p. 16
Example addresses
Whole timer $T4:5, timer accumulated $T4:3.ACC, whole counter $C5:4, whole control $R6:0 p. 18, 20
ASCII strings
Up to 82 bytes of data per string; length an even number of bytes (2 - 82) p. 22

What this manual walks you through

  • Reading the PLC-5 data table memory map p. 5
  • Building a logical ASCII address p. 6, 7
  • Addressing the input and output image tables p. 8
  • Reading the status file: processor status, minor and major faults, fault codes p. 9, 10, 11, 12, 13, 14, 15
  • Addressing ASCII, binary, BCD, floating-point and integer files p. 15, 16
  • Addressing timer, counter and control structures p. 17, 18, 19, 20
  • Addressing SFC status, block-transfer and ASCII string structures p. 21, 22, 23
  • PID control and message control file layouts p. 23, 24, 25, 26

Good to know

  • BT, MG, PD, SC and ST files are not available on the PLC-5/10, -5/12, -5/15 and -5/25 processors. p. 7
  • The $ identifier is an entry for INTERCHANGE software and for 6200 messages from other stations, not for 6200 internal addressing. p. 7
  • Except for data entry and display, values in A, B, D and N files are processed as integers in natural binary. p. 15

Questions this manual answers

What does PLC-5 fault code 11 mean?

Fault code 11 in status word S:12 is a bad user program checksum. p. 12

How do I know the PLC-5 battery is low?

Status word S:10 (minor fault) bit 0 is set when the battery is low; the manual says to replace it in 1-2 days. p. 11

How do I address a timer accumulated value on a PLC-5?

Use the .ACC member, for example $T4:3.ACC; $T4:3.PRE is the preset. p. 18

Which PLC-5 processors do not support PID and message files?

BT, MG, PD, SC and ST files are not available on the PLC-5/10, -5/12, -5/15 and -5/25. p. 7

What is the integer range of a PLC-5 word?

A signed word holds -32,768 thru +32,767, with negative values in 2's complement form. p. 16

Contents

Chapters and sections

Each line opens the PDF at its page.

  1. PLC-5® Programmable Controllers, Addressing Reference Manual1
    1. Important User Information2
    2. Summary of Changes3
    3. Addressing for 1785 PLC-5 Processors4
    4. Back Cover28

From the PDF’s own bookmarks.

The whole text · 3 parts

Read the manual here as text

Its text as extracted from the PDF, unedited, in parts; each page opens the PDF at that page.

  1. Pages 1 to 101-10
  2. Pages 11 to 2011-20
  3. Pages 21 to 2821-28

The file

Revision and size

RevisionPublication 5000-6.4.4, August 1995
PublisherAllen-Bradley Company, Inc.
Pages28
PDF172 KB
TextText from the PDF itself; page 1 is a scan, read by OCR, which may hold reading errors.

The first pages · 3 of 28

Look before you download

Each page opens the PDF at that page.

Page 1
Page 1of 28
Page 2
Page 2of 28
Page 3
Page 3of 28

More documents · 1

For the same models