Page 21

1785 PLC-5 Addressing Reference

Figure 17 SFC Status Structure

15 SA

14 FS

13 12 11 10 9 8 7 6 5 4 LS OV ER DN Reserved PRE – Preset Value (–32,768 thru +32,767) TIM – Active Time (–32,768 thru +32,767)

3

2

1

0

17376–I

Table J Example SFC Status Addresses To Address:

PLC Data Type:

Example Address:

Whole SFC Status Structure structure

$SC9:0

Preset Word signed word

$SC9:0.PRE

Active-Time Word signed word

$SC9:0.TIM

Scan-active Bit bit

$SC9:0.SA

First-scan Bit bit

$SC9:0.FS

Last-scan Bit bit

$SC9:0.LS

Timer-overflow Bit bit

$SC9:0.OV

Step-errored Bit bit

$SC9:0.ER

Done Bit bit

$SC9:0.DN

Table K Block-Transfer Control Mnemonics

18

Mnemonic

Structure Member

Size

PLC Data Type

.EN

Enable

1 bit bit

.ST

Start

1 bit bit

.DN

Done

1 bit bit

.ER

Error

1 bit bit

.CO

Continue

1 bit bit

.EW

Enabled Waiting

1 bit bit

.NR

No Response

1 bit bit

.TO

Time Out

1 bit bit

.RW

Read/Write

1 bit bit

.RLEN

Requested Word Count

2 bytes signed word

.DLEN

Transmitted Word Count

2 bytes signed word

.FILE

File-type Number

2 bytes signed word

.ELEM

Word Number

2 bytes signed word

.RGS

Rack/Group/Slot

2 bytes signed word

Page 22

1785 PLC-5 Addressing Reference

Figure 18 Block-transfer Control Structure

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 EN ST DN ER CO EW NR TO RW Reserved RLEN – Requested Word Count (–32,768 thru +32,767) DLEN – Transmitted Word Count (–32,768 thru +32,767) FILE – File-type Number (–32,768 thru +32,767) ELEM – Word Number (–32,768 thru +32,767) not I/O Rack I/O Group used

0 slot

Table L Example Block-transfer Control Addresses To Address:

PLC Data Type:

Example Address:

Whole B-T Control Structure structure

$BT10:0

Requested-word Count signed word

$BT10:0.RLEN

Transmitted-word Count signed word

$BT10:0.DLEN

File-type Number signed word

$BT10:0.FILE

Word Number signed word

$BT10:0.ELEM

Rack/Group/Slot signed word

$BT10:0.RGS

Done Bit bit

$BT10:0.DN

Table M ASCII String Mnemonics Mnemonic

Structure Member

Size

PLC Data Type

.LEN

Length

2 bytes signed word

Figure 19 ASCII String Structure

15

14

13 12 11 10 9 8 7 6 5 4 3 2 1 LEN – Length specifies an even number of bytes (2 – 82) A maximum of 82 bytes of data accessible only by addressing the whole structure.

0

19

Page 23

1785 PLC-5 Addressing Reference

Table N Example ASCII Structure Addresses To Address:

PLC Data Type:

Example Address:

Whole ASCII String Structure structure

$ST12:0

Length Word signed word

$ST12:0.LEN

Table O PID Mnemonics in PD File Mnemonic .INI .SPOR .OLL .OLH .EWD .DVNA .DVPA .PVLA .PVHA .EN .CT .CL .PVT .DO .SWM .CA .MO .PE .SP .KP .KI .KD .BIAS .MAXS .MINS .DB .SO .MAXO .MINO .UPD .PV .ERR .OUT .PVH .PVL .DVP .DVN .PVDB

20

Structure Member PID Initialized SP Out of Range Output Limit Low Output Limit High Error Within Dead Band Deviation High Alarm Deviation Low Alarm PV Low Alarm PV High Alarm Enable Cascaded Type Cascaded Loop PV Tracking Derivative Software A/M Mode Control Action Station Mode (auto/manual) PID Equation Type Set Point Proportional Gain Integral Gain Derivative Time Output Bias % Set–point Maximum (scaled value) Set–point Minimum (scaled value) Dead Band Set Output % Output Limit High % Output Limit Low % Update Time Process Variable Error Output % PV Alarm High PV Alarm Low Deviation Alarm + Deviation Alarm – PV Alarm Dead Band

Size 1 bit 1 bit 1 bit 1 bit 1 bit 1 bit 1 bit 1 bit 1 bit 1 bit 1 bit 1 bit 1 bit 1 bit 1 bit 1 bit 1 bit 1 bit 4 bytes 4 bytes 4 bytes 4 bytes 4 bytes 4 bytes 4 bytes 4 bytes 4 bytes 4 bytes 4 bytes 4 bytes 4 bytes 4 bytes 4 bytes 4 bytes 4 bytes 4 bytes 4 bytes 4 bytes

PLC Data Type bit bit bit bit bit bit bit bit bit bit bit bit bit bit bit bit bit bit IEEE float IEEE float IEEE float IEEE float IEEE float IEEE float IEEE float IEEE float IEEE float IEEE float IEEE float IEEE float IEEE float IEEE float IEEE float IEEE float IEEE float IEEE float IEEE float IEEE float

Page 24

1785 PLC-5 Addressing Reference

Mnemonic .DVDB .MAXI .MINI .TIE .ADDR[1] .DATA[2] 1 0–3

Structure Member Deviation Alarm Dead Band Input Range Maximum Input Range Minimum Tieback % Address of Master for the Slave Reserved/Internal Use 2 0 – 13

Size 4 bytes 4 bytes 4 bytes 4 bytes 4 X 2 bytes 14 X 4 bytes

PLC Data Type IEEE float IEEE float IEEE float IEEE float signed words IEEE float

Figure 20 PID Control Structure in PD file 15 EN

14

13

12

11

INI

SPOR OLL Set Point

SP

10

9 CT OLH

8 CL EWD

7 PVT

6 DO

5

4 SWM

3 DVNA

4 bytes

2 CA DVPA

1 MO PVLA

0 PE PVHA

IEEE float

KP

Proportional Gain

4 bytes

IEEE float

KI

Initial Gain

4 bytes

IEEE float

KD

Derivative Gain

4 bytes

IEEE float

BIAS

Output Bias %

4 bytes

IEEE float

MAXS

Maximum Scaled Value

4 bytes

IEEE float

MINS

Minimum Scaled Value

4 bytes

IEEE float

DB

Dead Band

4 bytes

IEEE float

SO

Set Output %

4 bytes

IEEE float

MAXO

Maximum Output Limit

4 bytes

IEEE float

MINO

Minimum Output Limit

4 bytes

IEEE float

UPD

Update Time

4 bytes

IEEE float

PV

Process Variable

4 bytes

IEEE float

ERR

Error: Scaled

4 bytes

IEEE float

OUT

Output

4 bytes

IEEE float

PVH

PV Alarm High

4 bytes

IEEE float

PVL

PV Alarm Low

4 bytes

IEEE float

DVP

Deviation Alarm +

4 bytes

IEEE float

DVN

Deviation Alarm –

4 bytes

IEEE float

PVDB

PV Alarm Dead Band

4 bytes

IEEE float

DVDB

Deviation Alarm Dead Band

4 bytes

IEEE float

MAXI

Maximum Input

4 bytes

IEEE float

MINI

Minimum Input

4 bytes

IEEE float

TIE

Tieback %

4 bytes

IEEE float

ADDR [0] thru ADDR [3] DATA [0] thru DATA [13]

Master-to-Slave Address

8 bytes signed words

Reserved / Internal Use

14 X 4 bytes

IEEE float

21

Page 25

1785 PLC-5 Addressing Reference

Table P Example PID Control Addresses To Address:

PLC Data Type:

Example Address:

Whole PD Control Structure structure

$PD13:0

Set-point value

IEEE float

$PD13:0.SP

Proportional-gain value

IEEE float

$PD13:0.KP

PID-initialized bit bit

$PD13:0.INI

SP out-of-range bit bit

$PD13:0.SPOR

Table Q PID Control Block in Integer File Word:

Contains:

Term:

Range:

0

Bit 15 Bit 13 Bit 11 Bit 10 Bit 9 Bit 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0

1 2 reserved Setpoint

SP

6 7 8 9

Independent: Proportional gain (unitless) ISA: Controller gain (unitless) Independent: Integral gain (1/s) ISA: Reset term (minutes per repeat) Independent: Derivative gain ISA: Rate term x 100 (minutes) Feedforward or bias Maximum scaling Minimum scaling Dead band

KP KC KI TI KD TD FF/Bias Smax Smin DB

10 11 12 13

Set output Maximum output limit (% of output) Minimum output limit (% of output) Loop update time (seconds)

SETOUT Lmax Lmin dt

0 thru 4095 (unscaled) Smin thru Smax (scaled) 0 thru 327.67 0 thru 327.67 0 thru 327.67 0 thru 327.67 0 thru 327.67 0 thru 327.67 0 thru 4095 –32,768 thru +32,767 –32,768 thru +32,767 0 thru 4095 (unscaled) Smin thru Smax (scaled) 0 thru 100% 0 thru 100% 0 thru 100% 0.01 thru 327.67

3 4 5

22

Enabled (EN) Done (DN) Set point out of range Output alarm, lower limit Output alarm, upper limit DB, set when error is in DB Resume last state (0 = yes, 1 = hold last state) Derivative action (0 = PV, 1 = error) Setpoint descaling (0 = no, 1 = yes) Set output (0 = no, 1 = yes) Output limiting ((0 = no, 1 = yes) Control (0 = direct, 1 = reverse) Mode (0 = automatic, 1 = manual) Equation (0 = independent, 1 = ISA)

Page 26

1785 PLC-5 Addressing Reference

Word:

Contains:

14 15 16 17 – 22

Scaled PV value (displayed) Scaled error value (displayed) Output (% of 4095) internal storage; do not use

Term:

Range:

CV

Smin thru Smax Smin thru Smax 0 thru 100%

Table R Message control Mnemonics in MG File Mnemonic .NR .TO .EN .ST .DN .ER .CO .EW .ERR .RLEN .DLEN .DATA[0] thru .DATA[51]

Structure Member No Response Time Out Enable Start Transmission Done Error Continuous Enabled Waiting Error Code Request Length Done Length Reserved / Internal Use

Size 1 bit 1 bit 1 bit 1 bit 1 bit 1 bit 1 bit 1 bit 2 Bytes 2 Bytes 2 Bytes 52 X 2 Bytes

PLC Data Type bit bit bit bit bit bit bit bit signed word signed word signed word signed word

Figure 21 Message Control Structure in MG File

15

14

13

12

11

10

9 8 7 6 5 4 3 2 NR TO EN ST DN ER CO EW ERR Error Code RLEN Requested Length DLEN Done Length

1

0

DATA[0] thru DATA[51] Reserved / Internal Use (52 X 2 bytes)

Table S Example Message Control Addresses To Address:

PLC Data Type:

Example Address:

Whole Message Control Structure structure

$MG14:0

Request Length signed word

$MG14:0.RLEN

Done bit bit

$MG14:0.DN

23

Page 27

1785 PLC-5 Addressing Reference

Figure 22 Message Control Block in Integer File

15 14 13 12 11 10 9 8 EN ST DN ER CO EW NR TO

7

6

5

Reserved / Internal Use (15 words)

24

4 3 2 Error Code

1

0

Page 28

Allen-Bradley, a Rockwell Automation Business, has been helping its customers improve productivity and quality for 90 years. We design, manufacture, and support a broad range of control and automation products worldwide. They include logic processors, power and motion control devices, man-machine interfaces, sensors, and a variety of software. Rockwell is one of the world’s leading technology companies.

Worldwide representation. Algeria • Argentina • Australia • Austria • Bahrain • Belgium • Brazil • Bulgaria • Canada • Chile • China, PRC • Colombia • Costa Rica • Croatia • Cyprus • Czech Republic Denmark • Ecuador • Egypt • El Salvador • Finland • France • Germany • Greece • Guatemala • Honduras • Hong Kong • Hungary • Iceland • India • Indonesia • Israel • Italy Jamaica • Japan • Jordan • Korea • Kuwait • Lebanon • Malaysia • Mexico • New Zealand • Norway • Oman • Pakistan • Peru • Philippines • Poland • Portugal • Puerto Rico Qatar • Romania • Russia–CIS • Saudi Arabia • Singapore • Slovakia • Slovenia • South Africa, Republic • Spain • Switzerland • Taiwan • Thailand • The Netherlands • Turkey United Arab Emirates • United Kingdom • United States • Uruguay • Venezuela • Yugoslavia Allen-Bradley Headquarters, 1201 South Second Street, Milwaukee, WI 53204 USA, Tel: (1) 414 382-2000 Fax: (1) 414 382-4444

Publication 5000–6.4.4 August 1995 Supersedes Publication 5000–6.4.4 February 1995

PN 955123-27

25

Copyright 1995 Allen-Bradley Company, Inc. Printed in USA