The text of a manual · part 9 of 13
Accu-Time Series 7000 Access Control Unit User's Manual: Chapter 3 Commands, pages 74 to 82
Pages 74 to 82 of 105, from Accu-Time Series 7000 Access Control Unit User's Manual
The original document is the PDF (1.2 MB). This is its text as extracted, unedited; tables and drawings read best in the PDF, and each page heading opens it at that page.
For the Accu-Time Series 7000
Page 74
Controlling Relays DO_1, DO_2 DC101
Use the commands described in this section to control the ACU’s relays DO_1 and DO_2.
Turn on DO_1 Syntax: DC101rs Arguments: None. Discussion: Turns on DO_1 relay until turned off by DC100 command. Example: DC101^
DC100
Turn off DO_1 Syntax: DC100rs Arguments: None. Discussion: Turns off DO_1 relay. Example: DC100^
DC111
Turn on DO_1 for Preset Time Syntax: DC111rs Arguments:
Accu-Time® Series 7000 Access Control Unit User’s Guide
3-28
Page 75
None. Discussion: Activates DO_1 relay for length of time previously set by LPB03 or LPB04 command.
DC201
Turn on DO_2 Syntax: DC201rs Arguments: None. Discussion: Turns on DO_2 relay until turned off by DC200 command. Example: DC201^
DC200
Turn off DO_2 Syntax: DC200rs Arguments: None. Discussion: Turns off DO_2 relay. Example: DC200^
DC211
Turn on DO_2 for Preset Time Syntax: DC211rs Arguments: Accu-Time® Series 7000 Access Control Unit User’s Guide
3-29
Page 76
None. Discussion: Activates DO_2 relay for length of time previously set by LPB03 or LPB04 command. Example: DC211^
Accu-Time® Series 7000 Access Control Unit User’s Guide
3-30
Page 77
Messages Received From ACU ALDI1
This section describes the different types of messages that can be sent from an ACU to its host computer. Although they are included in the “commands” chapter, they are more properly thought of as message headers.
Digital IN #1 Alarm Message Syntax: ALDI1rsusYYMMDDHHMMSSrsFORCEDrs or ALDI1rsusYYMMDDHHMMSSrsOPENEDrs Arguments: YY - Two-digit year MM - Two-digit month DD - Two-digit day HH - Two-digit hour (24-hour format) MM - Two-digit minutes SS - Two-digit seconds FORCED - This argument is sent to host if digital IN 1 (DI_1) is open when digital OUT 1 (DO_1) is not activated. OPENED - This argument is sent to host if DI _1 remains open for longer than the wait time set by the LPB05 command. The beeper will sound a bad beep and the DO_2 relay will also be activated. Discussion: Message returned by ACU in response to a Digital IN event. The message indicates the type of event, with a timestamp of when the event occurred. Example: ALDI1^v030416025111^FORCED^ DI_1 open, DO_1 not activated, timestamp April 16, 2003, 2:51:11am.
ALDI2
Digital IN #2 Tamper Alarm Message Syntax: Accu-Time® Series 7000 Access Control Unit User’s Guide
3-31
Page 78
ALDI2rsusYYMMDDHHMMSSrs Arguments: YY - Two-digit year MM - Two-digit month DD - Two-digit day HH - Two-digit hour (24-hour format) MM - Two-digit minutes SS - Two-digit seconds Discussion: Timestamp message sent by ACU to host if Digital IN 2 is open when DO_1 is not activated or DI_2 remains open for longer than the wait time set by the LPB05 command. The beeper will sound a “bad beep” and the DO_2 relay will be activated. Example: ALDI2^v030421092102^ Timestamp April 21, 2003, 9:21:02am.
ALSTATE
Alarm Query Message Syntax: ALSTATErsusabcrs Arguments: a - Tamper alarm state. 0 = inactive, 1 = active. b - DI_1 state. 0 = inactive, 1 = active. c - DI_2 state. 0 = inactive, 1 = active. Discussion: Message sent from ACU to host on receipt of the AQ10 command. Example: ALSTATE^v010^ Tamper alarm inactive, DI_1 active, DI_2 inactive. Accu-Time® Series 7000 Access Control Unit User’s Guide
3-32
Page 79
ALTAMP
Tamper Alarm Message Syntax: ALTAMPrsusYYMMDDHHMMSSrs Arguments: YY - Two-digit year MM - Two-digit month DD - Two-digit day HH - Two-digit hour (24-hour format) MM - Two-digit minutes SS - Two-digit seconds Discussion:
Message sent to host if the tamper switch inside the ACU case is activated while online. The beeper will sound a “bad beep” and the DO_2 relay will also be activated. The date and time returned is the timestamp when tamper switch was activated. Example: ALTAMP^v030416023741^ Tamper switch activated, timestamp of April 16, 2003, 2:37:41am.
BA01
Normal Power Recover Message Syntax: BA01rsusYYMMDDHHMMSSrs Arguments: YY - Two-digit year MM - Two-digit month DD - Two-digit day HH - Two-digit hour (24-hour format) MM - Two-digit minutes
Accu-Time® Series 7000 Access Control Unit User’s Guide
3-33
Page 80
SS - Two-digit seconds Discussion: Normal power recovery message sent from ACU to host when ACU returns to normal power operation. The timestamp is the time the message is sent. Example: BA01^v030419114500^ Power recovery occurred April 19, 2003, at 11:45:00.
BA02
Low Power Message Syntax: BA02rsusYYMMDDHHMMSSrs Arguments: YY - Two-digit year MM - Two-digit month DD - Two-digit day HH - Two-digit hour (24-hour format) MM - Two-digit minutes SS - Two-digit seconds Discussion: Low power alarm message sent from ACU to host when ACU enters low power operation. Example: BA02^v030419113019^ Low power occurred April 19, 2003, at 11:30:19.
BG00
Initial Power-Up Message Syntax: BG00rsusYYMMDDHHMMSSrs Arguments: Accu-Time® Series 7000 Access Control Unit User’s Guide
3-34
Page 81
YY - Two-digit year MM - Two-digit month DD - Two-digit day HH - Two-digit hour (24-hour format) MM - Two-digit minutes SS - Two-digit seconds Discussion: Power-up message sent by ACU to host on initial power-up, with a timestamp indicating the time the power-up occurred. If BG00 is returned, the ACU does not have a command download in memory and will be in a locked state until one is received. If BG01 is returned, the ACU does have command download in memory. Example: BG00^v030412080307^ Initial power-up message sent by ACU to host indicating an initial power-up occurred April 12, 2003, at 8:03:07.
BG01
Power-Up Power Recovery Message Syntax: BG01rsusYYMMDDHHMMSSrs Arguments: YY - Two-digit year MM - Two-digit month DD - Two-digit day HH - Two-digit hour (24-hour format) MM - Two-digit minutes SS - Two-digit seconds Discussion:
Accu-Time® Series 7000 Access Control Unit User’s Guide
3-35
Page 82
Power-up message sent by ACU to host after a power recovery, with a timestamp indicating the time the power recovery occurred. If BG01 is returned, the ACU has a command download in memory. If BG00 is returned, the ACU does not have command download in memory and will be in a locked state until one is received. Example: BG01^v0306211709042^ Power recovery message sent by ACU to host indicating a power recovery occurred June 21, 2003, at 17:09:42.
BS00
Program Number Request Syntax: BS00PPPRrsusYYMMDDHHMMSSrs Arguments: PPP - Program number R - Program revision YY - Two-digit year MM - Two-digit month DD - Two-digit day HH - Two-digit hour (24-hour format) MM - Two-digit minutes SS - Two-digit seconds Discussion: Message sent from ACU to host in response to program number request from host. The timestamp is the time the message is sent. Example: BS00200J^v030419120317^ The ACU reports a program number of 200, revision J, with a message timestamp of April 19, 2003, 12:03:17.
BS01
Badge And Schedule Size Request (response to S01 command)
Accu-Time® Series 7000 Access Control Unit User’s Guide
3-36