Page 38

Wiring an Alarm

In Figure 2-1, the DO_2 relay is used for alarm output. Connect the DO_2 relay to a suitable alarm mechanism, as shown below:

Relay 2 (DO_2) Gnd

NO

NC Com 12V

Alarm

12VDC alarm. Connection normally open.

Operation

If the DI_1 switch is opened, indicting an open door, without a “validate good swipe” having been received from a reader, DO_2 is activated. In any case, the DO_2 relay is activated if: • DI_1 stays active during more than a pre-set time (door not closed). • The tamper switch is opened (enclosure cover removed).

Wiring the Tamper Switch

The tamper switch itself requires no wiring. It is built onto the PC board. If the tamper switch functionality is enabled (DIP switch, position 2, set to OFF), the tamper switch activates the DO_2 relay when the ACU enclosure is opened. Any device you have wired to DO_2 will operate.

Accu-Time® Series 7000 Access Control Unit User’s Guide

2-10

Introduction

When DO_2 is activated, the normally open contact will close, sounding the alarm. Figure 2-5 shows an alternative method of powering an alarm from an external source for a voltage other than 12VDC or if the alarm requires more power than can be supplied by the 12V relay connection.

Page 39

Setting the DIP Switches

The DIP switches (items 4 and 5, Figure 1-2) can by set using a blunt pointed stylus or similar tool to slide a switch up or down. If a proper tool is unavailable, the end of a straightened large-diameter paper clip will serve. Review their functionality (See Table B-4 and Table B-5) and set the switches as required.

1. Test Switch Disable

Set OFF to disable operation of the Test switch (Figure 1-2 item 7).

2. Tamper Switch Disable

Set OFF to disable operation of the Tamper switch (Figure 1-2 item 6).

3. Default Reset

Set ON (with power connected to the ACU), then OFF, to reset the ACU to its factory default conditions. (See Reset on page 1-8.)

4. RS232/RS485 Mode

Set ON to use the RS232 interface, OFF to use the RS485 interface.

5. Reserved

Reserved - always set OFF.

6. Single/Dual Door Mode

Set ON for dual door mode. Set OFF for single door mode. See On Line Mode, Dual Door on page 1-8.

7. ATS Serial Protocol

Always set OFF to use ATS serial protocol.

8. Online/Standalone

Set ON to use ACU in online mode, OFF to use in standalone mode.

Accu-Time® Series 7000 Access Control Unit User’s Guide

2-11

Introduction

DIP Switch 1

Page 40

DIP Switch 2 1-2. Reader 0 Type

Set switches 1 and 2 to select type of reader connected as reader 0. Options are: Off/Off - Magnetic stripe or proximity reader (same as Off/On). Off/On - Magnetic stripe or proximity reader (same as Off/Off). On/Off - Barcode reader. On/On - Keypad. See also Setting the Jumpers on page 2-13. The jumpers must be set correctly for each type of reader.

3. Reader 1 Type

Set switch 3 to select type of reader connected as reader 1. Options are: Off - Same as reader 0.

You cannot use two different types of reader. See also Setting the Jumpers on page 2-13. The jumpers must be set correctly for each type of reader.

4-8. Unit Address

Set switches 4 through 8 to set the ACU’s binary unit address. For example, if switches 4, 5, 6, and 7 are OFF and switch 8 is ON, that is unit 1, or 000012. Use A setting of Off/Off/Off/Off/Off/Off (00000) for address 32. Table 2-5 shows binary equivalents for terminal addresses 1 through 32.

Accu-Time® Series 7000 Access Control Unit User’s Guide

2-12

Introduction

On - Exit button (unlocks without swiping a card).

Page 41

Setting the Jumpers

Decimal

Binary

Decimal

Binary

Decimal

Binary

1

00001

12

01100

23

10111

2

00010

13

01101

24

11000

3

00011

14

01110

25

11001

4

00100

15

01111

26

11010

5

00101

16

10000

27

11011

6

00110

17

10001

28

11100

7

00111

18

10010

29

11101

8

01000

19

10011

30

11110

9

01001

20

10100

31

11111

10

01010

21

10101

32

00000

11

01011

22

10110

In addition to selecting the reader types using positions 1, 2, and 3 of DIP switch 1, you must also set two jumpers on the board (Figure 1-2, item 16). Refer to Figure 1-3, which shows the position in which to set the jumpers for each type of reader. Use the upper jumper positions for a magnetic or proximity reader or for a keypad. Use the lower jumper positions for a barcode reader.

Accu-Time® Series 7000 Access Control Unit User’s Guide

2-13

Introduction

Table 2-5: Decimal/Binary Unit Number Equivalents

Page 42

Figure 2-5: Alternative Series 7000 Inputs and Outputs Wiring Example Relay 1 (DO_1) Gnd

NO

Digital IN 1 (DI_1)

NC Com 12V

Vcc

DI+

DI-

Gnd

Shd

External Power Supply Magnetic Door Sensor

When contact is broken, DI_1 enters alarm state and can trigger DO_2 to sound alarm.

Magnetic Lock

Digital IN 2 (DI_2)

Gnd

External Power Supply

NO

NC Com 12V

Alarm

Vcc

DI+

DI-

Gnd Shd

DI_2 not used. DI+ and DI- connected to power and ground to prevent ACU from entering alarm state.

Lock and alarm wiring for a voltage other than 12VDC or for special power requirements.

Accu-Time® Series 7000 Access Control Unit User’s Guide

2-14

Introduction

Relay 2 (DO_2)

Page 43

Figure 2-6: Dual Door Mode Wiring Example Relay 1 (DO_1) NO

NC Com 12V

Gnd

Magnetic Lock

12VDC magnetic lock. Connection normally closed (powered to maintain locked state).

Digital IN 1 (DI_1) DI+

DI-

NC Com 12V

Magnetic Lock

12VDC magnetic lock. Connection normally closed (powered to maintain locked state).

Vcc

NO

Gnd Shd

Magnetic Door Sensor

When contact is broken, unit will issue an alarm transaction back to the host.

Digital IN 2 (DI_2) Vcc

DI+

DI-

Gnd Shd

Magnetic Door Sensor

When contact is broken, unit will issue an alarm transaction back to the host.

Accu-Time® Series 7000 Access Control Unit User’s Guide

2-15

Introduction

Gnd

Relay 2(DO_2)

Page 44

Figure 2-7: Series 7000 RS232 Serial Installation To host

Eight conductor power/communication cable (up to 50 wire-feet) Comm. adapter DE-9-RJ45

RS485 In

RS485 Out

RS232

NETWORK/COMMS

ACCESS CONTROL UNIT

Series 7000

12 VDC @ 1 Amp Power pack 20 foot reader cable Reader

Accu-Time® Series 7000 Access Control Unit User’s Guide

2-16

Introduction

Alive TX RX DI 1 DI 2 5v 12v

Page 45

12 VDC @ 1/2 Amp Power pack

Comm adapter DE9/DB25-RJ45

To host

12 VDC @ 1 Amp Power pack

RS485 Out RS232

Series 7000

ACCESS CONTROL UNIT

NETWORK/COMMS

RS485 In

Host

Alive TX RX DI 1 DI 2 5v 12v

Reader

Network

12 VDC @ 1 Amp Power pack

RS232 to RS485 converte (For this example, set jumper to "No Network Power")

RS485 Out

RS232

Series 7000

ACCESS CONTROL UNIT

NETWORK/COMMS

RS485 In

Alive TX RX DI 1 DI 2 5v 12v

Reader

Figure 2-8: Series 7000 RS485 Serial Installation

Figure 2-9: Series 7000 Mounting Template (Next Page)

Page 46

Accu-Time® Series 7000 Access Control Unit User’s Guide

2-18

6.300

1.750

8.285

Introduction

Series 7000 Mounting Template

9.900