Page 38
Wiring an Alarm
In Figure 2-1, the DO_2 relay is used for alarm output. Connect the DO_2 relay to a suitable alarm mechanism, as shown below:
Relay 2 (DO_2) Gnd
NO
NC Com 12V
Alarm
12VDC alarm. Connection normally open.
Operation
If the DI_1 switch is opened, indicting an open door, without a “validate good swipe” having been received from a reader, DO_2 is activated. In any case, the DO_2 relay is activated if: • DI_1 stays active during more than a pre-set time (door not closed). • The tamper switch is opened (enclosure cover removed).
Wiring the Tamper Switch
The tamper switch itself requires no wiring. It is built onto the PC board. If the tamper switch functionality is enabled (DIP switch, position 2, set to OFF), the tamper switch activates the DO_2 relay when the ACU enclosure is opened. Any device you have wired to DO_2 will operate.
Accu-Time® Series 7000 Access Control Unit User’s Guide
2-10
Introduction
When DO_2 is activated, the normally open contact will close, sounding the alarm. Figure 2-5 shows an alternative method of powering an alarm from an external source for a voltage other than 12VDC or if the alarm requires more power than can be supplied by the 12V relay connection.
Page 39
Setting the DIP Switches
The DIP switches (items 4 and 5, Figure 1-2) can by set using a blunt pointed stylus or similar tool to slide a switch up or down. If a proper tool is unavailable, the end of a straightened large-diameter paper clip will serve. Review their functionality (See Table B-4 and Table B-5) and set the switches as required.
1. Test Switch Disable
Set OFF to disable operation of the Test switch (Figure 1-2 item 7).
2. Tamper Switch Disable
Set OFF to disable operation of the Tamper switch (Figure 1-2 item 6).
3. Default Reset
Set ON (with power connected to the ACU), then OFF, to reset the ACU to its factory default conditions. (See Reset on page 1-8.)
4. RS232/RS485 Mode
Set ON to use the RS232 interface, OFF to use the RS485 interface.
5. Reserved
Reserved - always set OFF.
6. Single/Dual Door Mode
Set ON for dual door mode. Set OFF for single door mode. See On Line Mode, Dual Door on page 1-8.
7. ATS Serial Protocol
Always set OFF to use ATS serial protocol.
8. Online/Standalone
Set ON to use ACU in online mode, OFF to use in standalone mode.
Accu-Time® Series 7000 Access Control Unit User’s Guide
2-11
Introduction
DIP Switch 1
Page 40
DIP Switch 2 1-2. Reader 0 Type
Set switches 1 and 2 to select type of reader connected as reader 0. Options are: Off/Off - Magnetic stripe or proximity reader (same as Off/On). Off/On - Magnetic stripe or proximity reader (same as Off/Off). On/Off - Barcode reader. On/On - Keypad. See also Setting the Jumpers on page 2-13. The jumpers must be set correctly for each type of reader.
3. Reader 1 Type
Set switch 3 to select type of reader connected as reader 1. Options are: Off - Same as reader 0.
You cannot use two different types of reader. See also Setting the Jumpers on page 2-13. The jumpers must be set correctly for each type of reader.
4-8. Unit Address
Set switches 4 through 8 to set the ACU’s binary unit address. For example, if switches 4, 5, 6, and 7 are OFF and switch 8 is ON, that is unit 1, or 000012. Use A setting of Off/Off/Off/Off/Off/Off (00000) for address 32. Table 2-5 shows binary equivalents for terminal addresses 1 through 32.
Accu-Time® Series 7000 Access Control Unit User’s Guide
2-12
Introduction
On - Exit button (unlocks without swiping a card).
Page 41
Setting the Jumpers
Decimal
Binary
Decimal
Binary
Decimal
Binary
1
00001
12
01100
23
10111
2
00010
13
01101
24
11000
3
00011
14
01110
25
11001
4
00100
15
01111
26
11010
5
00101
16
10000
27
11011
6
00110
17
10001
28
11100
7
00111
18
10010
29
11101
8
01000
19
10011
30
11110
9
01001
20
10100
31
11111
10
01010
21
10101
32
00000
11
01011
22
10110
In addition to selecting the reader types using positions 1, 2, and 3 of DIP switch 1, you must also set two jumpers on the board (Figure 1-2, item 16). Refer to Figure 1-3, which shows the position in which to set the jumpers for each type of reader. Use the upper jumper positions for a magnetic or proximity reader or for a keypad. Use the lower jumper positions for a barcode reader.
Accu-Time® Series 7000 Access Control Unit User’s Guide
2-13
Introduction
Table 2-5: Decimal/Binary Unit Number Equivalents
Page 42
Figure 2-5: Alternative Series 7000 Inputs and Outputs Wiring Example Relay 1 (DO_1) Gnd
NO
Digital IN 1 (DI_1)
NC Com 12V
Vcc
DI+
DI-
Gnd
Shd
External Power Supply Magnetic Door Sensor
When contact is broken, DI_1 enters alarm state and can trigger DO_2 to sound alarm.
Magnetic Lock
Digital IN 2 (DI_2)
Gnd
External Power Supply
NO
NC Com 12V
Alarm
Vcc
DI+
DI-
Gnd Shd
DI_2 not used. DI+ and DI- connected to power and ground to prevent ACU from entering alarm state.
Lock and alarm wiring for a voltage other than 12VDC or for special power requirements.
Accu-Time® Series 7000 Access Control Unit User’s Guide
2-14
Introduction
Relay 2 (DO_2)
Page 43
Figure 2-6: Dual Door Mode Wiring Example Relay 1 (DO_1) NO
NC Com 12V
Gnd
Magnetic Lock
12VDC magnetic lock. Connection normally closed (powered to maintain locked state).
Digital IN 1 (DI_1) DI+
DI-
NC Com 12V
Magnetic Lock
12VDC magnetic lock. Connection normally closed (powered to maintain locked state).
Vcc
NO
Gnd Shd
Magnetic Door Sensor
When contact is broken, unit will issue an alarm transaction back to the host.
Digital IN 2 (DI_2) Vcc
DI+
DI-
Gnd Shd
Magnetic Door Sensor
When contact is broken, unit will issue an alarm transaction back to the host.
Accu-Time® Series 7000 Access Control Unit User’s Guide
2-15
Introduction
Gnd
Relay 2(DO_2)
Page 44
Figure 2-7: Series 7000 RS232 Serial Installation To host
Eight conductor power/communication cable (up to 50 wire-feet) Comm. adapter DE-9-RJ45
RS485 In
RS485 Out
RS232
NETWORK/COMMS
ACCESS CONTROL UNIT
Series 7000
12 VDC @ 1 Amp Power pack 20 foot reader cable Reader
Accu-Time® Series 7000 Access Control Unit User’s Guide
2-16
Introduction
Alive TX RX DI 1 DI 2 5v 12v
Page 45
12 VDC @ 1/2 Amp Power pack
Comm adapter DE9/DB25-RJ45
To host
12 VDC @ 1 Amp Power pack
RS485 Out RS232
Series 7000
ACCESS CONTROL UNIT
NETWORK/COMMS
RS485 In
Host
Alive TX RX DI 1 DI 2 5v 12v
Reader
Network
12 VDC @ 1 Amp Power pack
RS232 to RS485 converte (For this example, set jumper to "No Network Power")
RS485 Out
RS232
Series 7000
ACCESS CONTROL UNIT
NETWORK/COMMS
RS485 In
Alive TX RX DI 1 DI 2 5v 12v
Reader
Figure 2-8: Series 7000 RS485 Serial Installation
Figure 2-9: Series 7000 Mounting Template (Next Page)
Page 46
Accu-Time® Series 7000 Access Control Unit User’s Guide
2-18
6.300
1.750
8.285
Introduction
Series 7000 Mounting Template
9.900